Bryant ERVBBLHU1150 Installation, Start-Up, And Operating Instructions Manual Download Page 4

VI.

CONDENSATE DRAIN

To connect condensate drain, proceed as follows:

1. Insert sleeved grommets into bottom of unit using the

gasket washer and nut (See Fig. 5).

2. Cut two sections of plastic tubing, about 12” long and attach

them to each drain.

3. Join the two short sections of tubing to the “T” connector

and the main tube as shown.

4. Make a loop in the tubing below the “T” connector to create

a trap to prevent sewer gases from entering the ventilation
system (See Fig. 5).

5. Connect unit drain to building’s main drain. Provide slight

slope from unit for run-off.

VII.

WALL CONTROL

1.

Location

The ERV wall control is unique to this unit. The ERV will not
operate without it. This control senses humidity not temperature. It
must be located in an area where it will continually monitor fresh

air circulating within the home. Install ERV wall control as close
as possible to main system thermostat and follow same guidelines
as installing a thermostat (locate approximately 5 ft. above floor,
mount on an inside partitioning wall, etc.).

2.

Wiring

Remove top cover assembly from wall control and pass thermostat
wire through hole located on back of control before attaching to
wall. Connect Y, R, G, and B (yellow, red, green, and black)
between wall control and ERV circuit board following color code
(See Fig. 8 and 9). Replace top cover assembly.

NOTE:

ERV wall control and circuit board operate on 12vdc.

3.

Operation

The ERV wall control has 3 basic modes of operation, OFF, LOW,
and INTERMITTENT. Be sure that all modes of operation are
fully functional. See Table 1 indicating standard control operation.
OFF — When wall control is OFF, ERV is de-energized and both
LED’s are off.
LOW — This mode ensures continuous air exchange with outside
at all times. If relative humidity level inside of building is higher
than setpoint, then air exchange will occur at low speed. If relative
humidity level inside of building is lower than setpoint, then air
exchange occurs at high speed.
INTERMITTENT — If relative humidity level inside of building
is higher than setpoint, then no air exchange will occur and ERV
shuts off. If relative humidity level inside building is lower than
setpoint, then air exchange occurs at high speed, and shuts down
ERV when humidity level reaches set point. This mode is ideal for
maintaining proper humidity level when continuous mode cannot.
To ensure highest degree of humidity control in cooling season,
intermittent mode should not be used.

4.

Humidity Selection

The humidity selector is a built-in humidity controller designed to
properly control humidity level in a house during summer months.
This acts like a limit switch. See Table 2 to select maximum
humidity level. If the house becomes too dry in winter months, put
wall control in INTERMITTENT mode and turn down humidity
selector to provide ventilation less frequently.

5.

Latent Control

NOTE:

To ensure highest degree of humidity control in cooling

season, the INTERMITTENT mode should be used. See Table 1
and reference LOW and INTERMITTENT control operation listed
above.

ELECTRICAL CONNECTIONS

I.

115–VAC WIRING

The ERV operates on 115vac. It comes with a power cord attached
to unit and ready to plug into a fused outlet. Unit must be grounded
for proper operation.
All electrical connections must comply with National and Local
Electrical Codes, or other ordinances that might apply.

CAUTION:

ELECTRICAL / FIRE HAZARD

Failure to follow this warning could result in property or
unit damage.
Do not use an extension cord as a power source for
operating the ERV.

II.

12–VDC WIRING

The ERV circuit board, wall control, and accessories operate on
12vdc. See section, Wall Control, item Wiring, and Fig. 8 and 9 for
more information.

ACCESSORIES

I.

INTERLOCK RELAY

The interlock relay kit, Part No. KVAAC0101VIR is required
when installing ERV into a forced-air heating and cooling system
(See Fig. 10). Mount interlock relay inside of unit below control
box assembly. For additional information, refer to Installation
Instructions supplied with the interlock relay kit.

Fig. 5–Condensate Drain With Loop Trap

A99268

Fig. 6–Flexible Duct Fit-Up

A98382

FLEXIBLE
DUCT

FRESH-AIR
SUPPLY

STALE-AIR
RETURN

DUCTS CONNECTING TO

RETURN-AIR DUCT SYSTEM

—4—

Summary of Contents for ERVBBLHU1150

Page 1: ...able during start up and adjustment procedures and service calls Recognize safety information This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals be...

Page 2: ...etween the 2 airstreams 6 Blowers bring in fresh air from outside and exhaust stale air to outside 7 Electronic control circuit board ensures proper operation of unit 8 Fresh air supply connected to r...

Page 3: ...il will energize See Fig 10 and interlock relay kit for additional information and Installation Instructions NOTE The fresh air from ERV is introduced into return air duct at a point no less than 6 ft...

Page 4: ...inside of building is higher than setpoint then no air exchange will occur and ERV shuts off If relative humidity level inside building is lower than setpoint then air exchange occurs at high speed a...

Page 5: ...n timers that can be applied is 5 III 60 MINUTE ADJUSTABLE TIMER A 60 minute adjustable timer can also be used to override wall control and put ERV into high speed operation for a select amount of tim...

Page 6: ...installed as close to the ERV as possible and in straightest sections of duct to ensure accuracy See Fig 12 If only one flow collar is available install collar in stale air duct of the ERV and record...

Page 7: ...Building Code 1990 version and the CSA F326 1 revision The following 2 methods can be used to evaluate the approximate ventilation needs of a house Accuracy of calculations are depen dent upon the inf...

Page 8: ...lose for 6 minutes while K1 and K2 remain energized This closes the outdoor air damper while running ERV blower on high speed This process recirculates warm indoor air through heat recovery core which...

Page 9: ...low this caution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing and gloves when handling parts Fig 12 Balancing ERVBBLH...

Page 10: ...OTING WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing or servicing system always turn off main power to system There may be mo...

Page 11: ...wire from control board 2 Take ohm reading across thermistor 3 Refer to Table 4 for temperature ohm relationship OPERATING THE ERV WITH THE EVOLUTION CONTROL The ERV may be controlled using the Evolut...

Page 12: ...INAL WIRE AS SUPPLIED MUST BE REPLACED USE THE SAME OR EQUIVALENT WIRE 5 FACTORY SET WIRING FOR BLOWER SPEED SELECTION IS HIGH AND LOW MEDIUM SPEED CAN BE SELECTED INSTEAD OF LOW SPEED DISCONNECT RED...

Page 13: ...ll control Is in defrost Wait until de frost has termi nated maximum of 40 minutes Broken control wire Test wall con trol check con nections check thermistor Unit stops mo mentarily Electrical supply...

Page 14: ...6 993 94 6 661 96 6 368 98 6 085 100 5 811 102 5 571 104 5 313 106 5 088 108 4 869 110 4 660 112 4 450 114 4 268 116 4 019 118 3 918 120 3 750 TABLE 6 FACTORY SET BLOWER CONNECTION HIGH OR LOW SPEED...

Page 15: ...15...

Page 16: ...2005 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 16 Printed in U S A erv643 Catalog No II ERV 64 3...

Reviews: