Bryant ERVBBLHU1150 Installation, Start-Up, And Operating Instructions Manual Download Page 2

II.

SELECT LOCATION

The ERV should be located in a conditioned space and in close
proximity to a fused power source. It should be easily accessible
for routine maintenance.

If ERV is installed independent of a forced-air system, unit should
be located near the center of the air distribution system. If ERV is
installed in conjunction with a forced-air system, unit should be
located next (or close to) the indoor equipment.

COMPONENT DESCRIPTION

The following lists components of the ERVBBLHU (See Fig. 3).

1. Stale air return from building connected to return-air duct

system.

2. Fresh-air intake connected to outdoor-air inlet hood.

3. Exhaust-air connected to outdoor-air exhaust hood.

4. Mechanical filters trap dust contained in the air.

5. Energy recovery core is a cross-flow type. It transfers

sensible and latent energy between the 2 airstreams.

6. Blowers bring in fresh-air from outside and exhaust stale-air

to outside.

7. Electronic control circuit board ensures proper operation of

unit.

8. Fresh-air supply connected to return-air duct system.

9. Terminal connector block for wiring wall and timer con-

trols.

10. Electrical cord connects to standard 115–v outlet.

11. Damper motor.

Fig. 2–Dimensional Drawing ERVBBLHU

MODEL NO.

A

B

C

D

E

F

G

in.

mm.

in.

mm.

in.

mm.

in.

mm.

in.

mm.

in.

mm.

in.

mm.

ERVBBLHU1150

15-1/8

384.2

4-1/16

104

5-5/8

143.3

14-1/2

368.9

10-3/8

288.9

4-3/8

111.3

7-3/4

196.9

ERVBBLHU1200

19

483

5-13/16

147.7

5-1/16

128.6

14-1/2

368.9

11-3/16

283.9

4-3/8

111.3

10-1/16

255.6

A00093

A

20"

(508.0)

B

15"

(381.0)

G

3

4

"

(120.6)

D

C

30 

1

4

"

(768.3)

5

16

"

(58.7)

18 

1

8

"

(460.4)

16 

7

8

"

(428.6)

NOTES:

1. FRESH AIR FROM OUTSIDE TO ERV

2. FRESH AIR FROM ERV TO HOUSE

3. STALE AIR FROM HOUSE TO ERV

4. STALE AIR FROM ERV TO OUTSIDE

4

3

1

2

E

F

7

8

"  DIA

(149.2)
4 PLCS

3

16

"

(56.2)

4 PLCS

1"
(25.4)
2 PLCS

Fig. 3–ERVBBLHU Cross-Flow

A00113

4

9

10

1

2

11

5

6

8

3

7

—2—

Summary of Contents for ERVBBLHU1150

Page 1: ...able during start up and adjustment procedures and service calls Recognize safety information This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals be...

Page 2: ...etween the 2 airstreams 6 Blowers bring in fresh air from outside and exhaust stale air to outside 7 Electronic control circuit board ensures proper operation of unit 8 Fresh air supply connected to r...

Page 3: ...il will energize See Fig 10 and interlock relay kit for additional information and Installation Instructions NOTE The fresh air from ERV is introduced into return air duct at a point no less than 6 ft...

Page 4: ...inside of building is higher than setpoint then no air exchange will occur and ERV shuts off If relative humidity level inside building is lower than setpoint then air exchange occurs at high speed a...

Page 5: ...n timers that can be applied is 5 III 60 MINUTE ADJUSTABLE TIMER A 60 minute adjustable timer can also be used to override wall control and put ERV into high speed operation for a select amount of tim...

Page 6: ...installed as close to the ERV as possible and in straightest sections of duct to ensure accuracy See Fig 12 If only one flow collar is available install collar in stale air duct of the ERV and record...

Page 7: ...Building Code 1990 version and the CSA F326 1 revision The following 2 methods can be used to evaluate the approximate ventilation needs of a house Accuracy of calculations are depen dent upon the inf...

Page 8: ...lose for 6 minutes while K1 and K2 remain energized This closes the outdoor air damper while running ERV blower on high speed This process recirculates warm indoor air through heat recovery core which...

Page 9: ...low this caution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing and gloves when handling parts Fig 12 Balancing ERVBBLH...

Page 10: ...OTING WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing or servicing system always turn off main power to system There may be mo...

Page 11: ...wire from control board 2 Take ohm reading across thermistor 3 Refer to Table 4 for temperature ohm relationship OPERATING THE ERV WITH THE EVOLUTION CONTROL The ERV may be controlled using the Evolut...

Page 12: ...INAL WIRE AS SUPPLIED MUST BE REPLACED USE THE SAME OR EQUIVALENT WIRE 5 FACTORY SET WIRING FOR BLOWER SPEED SELECTION IS HIGH AND LOW MEDIUM SPEED CAN BE SELECTED INSTEAD OF LOW SPEED DISCONNECT RED...

Page 13: ...ll control Is in defrost Wait until de frost has termi nated maximum of 40 minutes Broken control wire Test wall con trol check con nections check thermistor Unit stops mo mentarily Electrical supply...

Page 14: ...6 993 94 6 661 96 6 368 98 6 085 100 5 811 102 5 571 104 5 313 106 5 088 108 4 869 110 4 660 112 4 450 114 4 268 116 4 019 118 3 918 120 3 750 TABLE 6 FACTORY SET BLOWER CONNECTION HIGH OR LOW SPEED...

Page 15: ...15...

Page 16: ...2005 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 16 Printed in U S A erv643 Catalog No II ERV 64 3...

Reviews: