Bryant ERVBBLHU1150 Installation, Start-Up, And Operating Instructions Manual Download Page 10

I.

DOOR

ERV door can be removed by unlatching brief case style latches,
then lifting door up and sliding it sideways (See Fig. 17). Door
must be in place and secured shut for proper operation.

II.

FILTER

Filters in ERV are washable and should be cleaned every 3
months. Use a vacuum cleaner to remove heaviest portion of
accumulated dust, then wash in lukewarm water. Allow filter to
completely dry before re-installing. A dirty air filter will cause
excessive strain on the blower motor. Never operate unit without
a filter (See Fig. 17).

In addition, regularly check and clean screens on exterior intake
and exhaust hoods when necessary.

CAUTION:

UNIT COMPONENT DAMAGE HAZ-

ARD

Failure to follow this caution may result in unit compo-
nent damage.
DO NOT clean filters in a dishwasher and DO NOT dry
them with a heating appliance or permanent damage will
result.

III.

BLOWER MOTOR AND WHEEL

ERV blower motors are factory lubricated for life. Lubricating
bearings is not recommended. However, inspect and clean any
accumulated dirt and grease from blower motor and wheel
annually.

IV.

CLEANING CORE

ERV is equipped with a special energy recovery core which is
made out of paper and allows transfer of sensible and latent
energy. The core should always be vacuumed only every 3 months
to remove dust and dirt that could prevent transfer of energy (See
Fig. 17).

NOTE:

The core should only be serviced when outdoor tempera-

ture is between 60°F and 75°F and it is dry.

CAUTION:

DO NOT use water to clean core or damage

will result. In addition, before servicing or removing the
core inspect the edges to see if they appear soft (or
slightly expanded). This can be normal and due to
moisture in the air. DO NOT handle or service core until
it is dry or air passages can become damaged and/or
closed.

TROUBLESHOOTING

WARNING:

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal
injury or death.
Before installing or servicing system, always turn off
main power to system. There may be more than one
disconnect switch.

CAUTION:

CUT HAZARD

Failure to follow this caution may result in personal
injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing and gloves when
handling parts.

NOTE:

Reference Table 3 Troubleshooting Chart

This can be a quick guide in resolving unit problems. It is also
recommended to review and understand Wall Control Board
Operation and Care and Maintenance sections before continuing.
There are three main parts to focus on when troubleshooting ERV
unit:

1. Wall Control

2. Electronic control board

3. Blower motor

I.

WALL CONTROL

Use Table 1 to determine if wall control is operating correctly. Use
Fig. 9 to check control wire connections.

NOTE:

The electronic control board and wall control operate on

12vdc.

II.

CONTROL BOARD

Electronic control board must have wall control attached before
unit will function properly. Also, configuration jumpers located on
control board must match configuration setup shown on Fig. 16
under Jumper Table. In addition, outside air thermistor must be
connected to control board for it to operate properly. See Table 4,
Temperature —vs— Ohm Chart, for valid temperature range.

III.

BLOWER MOTOR

The ERV blower motor operates on 115vac, with 2–speed opera-
tion.

The easiest way to check blower speed operation is to use the wall
control and initiate a low-speed blower and high-speed blower
operation using intermittent mode (See Table 1, standard control
operation).

NOTE:

If, after making the following test, you still hear relays

clicking upon charge, carefully check wiring, blower capacitor and
blowers.

Alternate procedure to check blower speed:

Fig. 14–Airflow During Exchange

A99269

STALE AIR

TO OUTSIDE

FRESH AIR

TO BUILDING

FRESH AIR
FROM OUTSIDE

STALE AIR
FROM BUILDING

—10—

Summary of Contents for ERVBBLHU1150

Page 1: ...able during start up and adjustment procedures and service calls Recognize safety information This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals be...

Page 2: ...etween the 2 airstreams 6 Blowers bring in fresh air from outside and exhaust stale air to outside 7 Electronic control circuit board ensures proper operation of unit 8 Fresh air supply connected to r...

Page 3: ...il will energize See Fig 10 and interlock relay kit for additional information and Installation Instructions NOTE The fresh air from ERV is introduced into return air duct at a point no less than 6 ft...

Page 4: ...inside of building is higher than setpoint then no air exchange will occur and ERV shuts off If relative humidity level inside building is lower than setpoint then air exchange occurs at high speed a...

Page 5: ...n timers that can be applied is 5 III 60 MINUTE ADJUSTABLE TIMER A 60 minute adjustable timer can also be used to override wall control and put ERV into high speed operation for a select amount of tim...

Page 6: ...installed as close to the ERV as possible and in straightest sections of duct to ensure accuracy See Fig 12 If only one flow collar is available install collar in stale air duct of the ERV and record...

Page 7: ...Building Code 1990 version and the CSA F326 1 revision The following 2 methods can be used to evaluate the approximate ventilation needs of a house Accuracy of calculations are depen dent upon the inf...

Page 8: ...lose for 6 minutes while K1 and K2 remain energized This closes the outdoor air damper while running ERV blower on high speed This process recirculates warm indoor air through heat recovery core which...

Page 9: ...low this caution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing and gloves when handling parts Fig 12 Balancing ERVBBLH...

Page 10: ...OTING WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing or servicing system always turn off main power to system There may be mo...

Page 11: ...wire from control board 2 Take ohm reading across thermistor 3 Refer to Table 4 for temperature ohm relationship OPERATING THE ERV WITH THE EVOLUTION CONTROL The ERV may be controlled using the Evolut...

Page 12: ...INAL WIRE AS SUPPLIED MUST BE REPLACED USE THE SAME OR EQUIVALENT WIRE 5 FACTORY SET WIRING FOR BLOWER SPEED SELECTION IS HIGH AND LOW MEDIUM SPEED CAN BE SELECTED INSTEAD OF LOW SPEED DISCONNECT RED...

Page 13: ...ll control Is in defrost Wait until de frost has termi nated maximum of 40 minutes Broken control wire Test wall con trol check con nections check thermistor Unit stops mo mentarily Electrical supply...

Page 14: ...6 993 94 6 661 96 6 368 98 6 085 100 5 811 102 5 571 104 5 313 106 5 088 108 4 869 110 4 660 112 4 450 114 4 268 116 4 019 118 3 918 120 3 750 TABLE 6 FACTORY SET BLOWER CONNECTION HIGH OR LOW SPEED...

Page 15: ...15...

Page 16: ...2005 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 16 Printed in U S A erv643 Catalog No II ERV 64 3...

Reviews: