Bryant ERVBBLHU1150 Installation, Start-Up, And Operating Instructions Manual Download Page 7

Measure exhaust air first. It is typically the lowest pressure due to
nature of system and ductwork. Next measure fresh air. If fresh air
reading is higher than exhaust reading, adjust damper until reading
is same. If reading is lower, return to exhaust damper and adjust to
obtain same reading. The label on flow collar can be used to
convert static pressure into airflow.

Once ERV is balanced and dampers are adjusted to equalize
airflow, use tape or drive screw to prevent damper blades from
moving. Remove flow collars and secure ducts. This procedure
should be repeated to ensure unit is balanced properly.

NOTE:

The flow collar directional arrow (on flow collar) must be

oriented in the airflow direction of the unit.

NOTE:

Some field modification may be required to ensure proper

temporary installation of flow collar during balancing when
insulated flexible duct is used.

NOTE:

For airflow pattern, see Fig. 14.

CAUTION:

UNIT DAMAGE HAZARD

Failure to follow this caution may result in reduced unit
efficiency, capacity or unit life.
Do NOT use ERV during construction of a house or when
sanding drywall. This type of dust may damage system.

VENTILATION EVALUATION

When ventilation requirement is determined, use Product Data
Digests to reference unit airflow delivery and performance. The
ventilation capacity of an ERV unit while at maximum speed is
defined according to greatest total airflow required. These methods
are derived from the Canadian National Building Code 1990
version and the CSA F326.1 revision.

The following 2 methods can be used to evaluate the approximate
ventilation needs of a house. Accuracy of calculations are depen-
dent upon the information available and knowing critical measure-
ments of the structure (See Fig. 15).

METHOD 1

To calculate approximate ventilation or extend defrost for cold
climate conditions:

The sum of rooms X 10 CFM per room, plus 20 CFM for a master
bedroom or basement are required.

Example: 11 rooms X 10 CFM + 2 X 20 CFM = 150 CFM.

NOTE:

The master bedroom and basement are not included in

first part of this equation, but figured in at second part of the
equation.

METHOD 2

To calculate approximate ventilation:

Referencing same example (See Fig. 15).

Fig. 10–Interlock Relay Wiring Layout

A05042

FOUR WIRE

TWO-WIRE

HEATING ONLY

TWO
WIRE

W

BLK

BLK

WHT

WHT

GND

115V FIELD-
SUPPLIED
FUSED
DISCONNECT

NOTE:

  Connect Y-terminal as

             shown for proper operation.

FURNACE
AUXILIARY
J-BOX

INDOOR UNIT
24V
TERMINAL BLOCK

THERMOSTAT

TERMINALS

INTERLOCK RELAY

GND

W

R

R

G

G

C

Y

Y

3

2

1

1
4
7

2
5
8

3
6
9

CONDENSING

UNIT

9-PIN AMP PLUG

120V FROM
VENTILATOR

C

TABLE 1–WALL CONTROL

MODE

HUMIDITY LEVEL

BOARD FUNCTION

FAN SPEED

INDICATOR LED’S

Off

Any

Off/Intermittent

Off

OFF

Low

Below Setpoint

Exchange High

High

Both ON

Above Setpoint

Exchange Low

Low

Intermittent

Below Setpoint

Exchange High

High

Both ON

Above Setpoint

Off/Intermittent

Off

ON light on Exchange OFF

Below 23°F(-5°C)

Any

Defrost/Exchange

High/Low

Both ON

TABLE 2–MAXIMUM HUMIDITY LEVELS

OUTSIDE TEMPERATURE

PERCENT RELATIVE HUMIDITY

70°F and Above

21°C and above

60 percent

50°F

10°C

55 percent

32°F

0°C

45 percent

—7—

Summary of Contents for ERVBBLHU1150

Page 1: ...able during start up and adjustment procedures and service calls Recognize safety information This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals be...

Page 2: ...etween the 2 airstreams 6 Blowers bring in fresh air from outside and exhaust stale air to outside 7 Electronic control circuit board ensures proper operation of unit 8 Fresh air supply connected to r...

Page 3: ...il will energize See Fig 10 and interlock relay kit for additional information and Installation Instructions NOTE The fresh air from ERV is introduced into return air duct at a point no less than 6 ft...

Page 4: ...inside of building is higher than setpoint then no air exchange will occur and ERV shuts off If relative humidity level inside building is lower than setpoint then air exchange occurs at high speed a...

Page 5: ...n timers that can be applied is 5 III 60 MINUTE ADJUSTABLE TIMER A 60 minute adjustable timer can also be used to override wall control and put ERV into high speed operation for a select amount of tim...

Page 6: ...installed as close to the ERV as possible and in straightest sections of duct to ensure accuracy See Fig 12 If only one flow collar is available install collar in stale air duct of the ERV and record...

Page 7: ...Building Code 1990 version and the CSA F326 1 revision The following 2 methods can be used to evaluate the approximate ventilation needs of a house Accuracy of calculations are depen dent upon the inf...

Page 8: ...lose for 6 minutes while K1 and K2 remain energized This closes the outdoor air damper while running ERV blower on high speed This process recirculates warm indoor air through heat recovery core which...

Page 9: ...low this caution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing and gloves when handling parts Fig 12 Balancing ERVBBLH...

Page 10: ...OTING WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing or servicing system always turn off main power to system There may be mo...

Page 11: ...wire from control board 2 Take ohm reading across thermistor 3 Refer to Table 4 for temperature ohm relationship OPERATING THE ERV WITH THE EVOLUTION CONTROL The ERV may be controlled using the Evolut...

Page 12: ...INAL WIRE AS SUPPLIED MUST BE REPLACED USE THE SAME OR EQUIVALENT WIRE 5 FACTORY SET WIRING FOR BLOWER SPEED SELECTION IS HIGH AND LOW MEDIUM SPEED CAN BE SELECTED INSTEAD OF LOW SPEED DISCONNECT RED...

Page 13: ...ll control Is in defrost Wait until de frost has termi nated maximum of 40 minutes Broken control wire Test wall con trol check con nections check thermistor Unit stops mo mentarily Electrical supply...

Page 14: ...6 993 94 6 661 96 6 368 98 6 085 100 5 811 102 5 571 104 5 313 106 5 088 108 4 869 110 4 660 112 4 450 114 4 268 116 4 019 118 3 918 120 3 750 TABLE 6 FACTORY SET BLOWER CONNECTION HIGH OR LOW SPEED...

Page 15: ...15...

Page 16: ...2005 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 16 Printed in U S A erv643 Catalog No II ERV 64 3...

Reviews: