background image

: Advanced Installation and Configuration Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

12

A200473

Select

 Enable

 If the auxiliary heat source is electric resistance and it is desired to have heat pump and electric heat to run at the same time. The system

will provide heat pump heating at lower stage and then turn on electric heat along with the heat pump at higher stages. If it is a “dual fuel system,”

meaning the auxiliary heat is a fossil fuel furnace, including natural gas, propane, or oil, then select 

Disable

. Do not run the compressor and furnace at

the same time to condition the home.         

A200474

The minimum compressor outdoor temperature is based on the specific model of heat pump used in the system. Nearly all heat pumps can operate in

the  heating  mode  down  to  at  least  17  degrees,  as  this  temperature,  along  with  47  degrees,  are  the  two AHRI  standard  testing  points.  The  best

temperature to disable the compressor depends on a lot of factors. If the auxiliary heat is electric resistance, then shut off the compressor when either…

a. The manufacturer has a published lowest operating temperature (for example, our 5-stage inverters can only run down to 10 degrees) or

b. The COP of the heat pump drops below 1.0, which is the COP of electric resistance heat

Until that low temperature is reached, it is best to use the heat pump as the primary heat source and use the electric resistance as additional stages. Then

below that temperature, shut off the compressor and use the electric heat only.
If the auxiliary heat is fossil fuel, then consider the cost of the fuel vs the cost of electricity, as well as the load of the house, the size of the equipment,

and the models of the equipment. The online OpCost Calculator found on HVAC Partners can be used to determine the “thermal balance point” and the

“economic balance point.” This tool takes only a couple of minutes to use. The thermal balance point is the outdoor temperature at which the heat

pump can no longer handle the load of the house on its own. The economic balance point is the outdoor temperature at which the furnace would be less

expensive to run.  Set the thermostat for the higher of these two numbers, so 43 degrees in the example above.

Summary of Contents for EB-STATE3LTBB-01

Page 1: ...or ERV Also the thermostats can be installed with the PEK if a C wire isn t present Additionally the thermostats can control boilers with or without an AC When connected to a boiler the thermostats s...

Page 2: ...ntify the final assembly number model name country of origin and device serial number A210086 The following final assembly numbers and corresponding model name are as follows c Table 1 Final Assembly...

Page 3: ...mostat can control the equipment it is preferred to allow the Bryant equipment to determine the staging by not connecting W2 See furnace installation instructions for heat staging setup Power Extender...

Page 4: ...dd a Wire Kit works similar to the PEK Normally this would not be needed because the PEK comes with the ecobee However the PEK is limited to one extra wire and only one PEK can be used per system Seve...

Page 5: ...g valve During the startup process the O B should be configured to act as an O terminal with Bryant equipment since the equipment defaults to heating and needs the reversing valve to be energized on a...

Page 6: ...ion and Configuration Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 6 Air Conditioner with Boiler A200461 Boiler...

Page 7: ...bee PEK Venstar Add a Wire or Fast Stat Wiring Extender accessories mentioned above cannot be used The W call gets piggy backed on the common wire with the small black sender module installed at the t...

Page 8: ...ct variable speed furnaces The ACC terminal will wire to the DH or DHUM terminal on the equipment in these applications On the FV fan coils remove jumper J1 from the Easy Select board to enable this f...

Page 9: ...mer and so only Rc is connected It is important to note that in these applications Rc must be used instead of Rh like some Bryant thermostats If the heating and cooling equipment have separate transfo...

Page 10: ...made here Start Up Dehum for Fan Coil or Furnace Initial Start Up Wiring Standard A200469 During installation the thermostat will automatically detect which terminals have wires connected If something...

Page 11: ...entilator Initial Start Up Wiring Accessory Dehumidifier for Fancoil or Furnace A200471 When selecting dehumidifier for using the equipment s DHUM or DH terminal select the appropriate relay action A...

Page 12: ...e auxiliary heat is electric resistance then shut off the compressor when either a The manufacturer has a published lowest operating temperature for example our 5 stage inverters can only run down to...

Page 13: ...y the fan on a W1 allowing the heat exchanger to warm up before engaging airflow so the occupants do not get a blast of cold air This setting only affects the gas heat startup sequence it will not del...

Page 14: ...latent capacity of the evaporator coil while reducing sensible capacity Installation Settings Thresholds Cool Dissipation A200478 Cool Dissipation Time is default on but the feature should only be us...

Page 15: ...to 76 degrees the 2nd stage will come on Then both will run together until the room temperature is satisfied at 74 Reverse staging works example If there is a 74 degree cooling setpoint the 1st stage...

Page 16: ...200482 The Auxiliary Heat Maximum Outdoor Temperature specifies when the heat pump should be able to handle the heating load solo without the need for auxiliary electric heat to assist Aux heat will b...

Page 17: ...the thermostat the maximum difference allowed between the thermostat and hottest or coldest rooms in the home If a sensor measures a temperature that is significantly outside of this range it probabl...

Page 18: ...and the sensor stops detecting occupancy the thermostat s temperature data is gradually and not immediately removed from the calculation A200488 Each sensor can be used with a Comfort Setting Home Aw...

Page 19: ...nd without obligations 19 Training My Learning Center is your central location for professional residential HVAC training resources that help strengthen careers and businesses We believe in providing...

Page 20: ...pany Edition Date 04 21 Catalog No II EBSTATE 02 Replaces II EBSTATE 01 Advanced Installation and Configuration Instructions Manufacturer reserves the right to change at any time specifications and de...

Reviews: