background image

Install Flanges for Ductwork Connections (564A/764A060 only)

The size 060 units are shipped with flanges which must be
field-installed on the unit.

To install unit flanges:

1. Five pieces of flange are shipped on the return air open-

ing of the unit. Remove the flanges from the shipping
position. See Fig. 9. Screws are field-supplied.

2. One piece of flange is used as it is shipped (straight).

Bend the other 4 pieces at right angles.

3. Install the straight flange on the right side of the re-

turn air opening in holes provided. See Fig. 10. Flanges
should stick out from unit to allow for connection of
ductwork.

4. Install 2 hand-formed flanges onto return air opening

in holes provided to form rectangle around the return
air opening.

5. Install remaining 2 hand-formed flanges around dis-

charge air opening in holes provided.

6. Ductwork can now be attached to flanges.

Adhere to the following criteria when selecting, sizing, and
installing the duct system:

1. Select and size ductwork, supply-air registers, and return-

air grilles according to ASHRAE (American Society of
Heating, Refrigeration, and Air Conditioning Engi-
neers) recommendations.

CAUTION:

When drilling the duct system fastening

holes into the side of the unit for duct flanges, do not
drill deeper than

3

4

in., and use extreme care not to

puncture the coil or coil tubes. See Fig. 11.

2. Use flexible transition between rigid ductwork and unit

to prevent transmission of vibration. The transition may
be screwed or bolted to duct flanges. Use suitable gas-
kets to ensure weathertight and airtight seal.

3. Size ductwork for cooling air quantity (cfm).
4. Adequately insulate and weatherproof all ductwork

located outdoors. Insulate ducts passing through un-
conditioned space, and use vapor barrier in accordance
with latest issue of SMACNA (Sheet Metal and Air
Conditioning Contractors National Association) and ACCA
(Air Conditioning Contractors of America) minimum
installation standards for heating and air conditioning
systems. Secure all ducts to building structure.

5. Flash, weatherproof, and vibration-isolate all openings

in building structure in accordance with local codes and
good building practices.

6. Air filters should be installed in return-air ductwork.

Return-air filter grille or filter tracks in duct may be used.

Figure 12 shows a typical duct system with unit installed.

19.17

3.92

Fig. 11 — Area Not To Be Drilled More Than

3

4

-in.

Fig. 9 — Shipping Location of Duct Flanges

(Size 060 Only)

Fig. 10 — Installation of Duct Flanges

(Size 060 Only)

—7—

Summary of Contents for 764A

Page 1: ...al words DANGER WARNING and CAUTION These words are used with the safety alert symbol Danger identifies the most serious hazards which will result in severe personal injury or death Warning indi cates...

Page 2: ...ts Power Entry Side 1066 8 42 00 Unit and Ungrounded Surfaces Power Entry Side 914 0 36 00 Unit and Block or Concrete Walls and Other Grounded Surfaces Power Entry Side 1066 8 42 00 REQUIRED CLEARANCE...

Page 3: ...6 8 42 00 Unit and Ungrounded Surfaces Power Entry Side 914 0 36 00 Unit and Block or Concrete Walls and Other Grounded Surfaces Power Entry Side 1066 8 42 00 REQUIRED CLEARANCES FOR SERVICING mm in C...

Page 4: ...rfaces Power Entry Side 914 0 36 00 Unit and Block or Concrete Walls and Other Grounded Surfaces Power Entry Side 1066 8 42 00 REQUIRED CLEARANCES FOR SERVICING mm in Condenser Coil Access Side 762 0...

Page 5: ...rance of 36 in between the control box side of the unit and any electrically live parts Unit may be installed on wood flooring or on Class A B or C roof covering materials Although unit is weatherproo...

Page 6: ...ditioning and Refrigeration Institute rated airflow at a velocity of 300 ft min for throwaway type or 450 ft min for high capacity type Recommended filters are 1 in thick If the installation requires...

Page 7: ...rilling the duct system fastening holes into the side of the unit for duct flanges do not drill deeper than 3 4 in and use extreme care not to puncture the coil or coil tubes See Fig 11 2 Use flexible...

Page 8: ...of improper voltage and or phase imbalance 4 Insulate low voltage wires for highest voltage con tained within conduit when low voltage control wires are run in same conduit as high voltage wires 5 Do...

Page 9: ...y as described in Special Proce dures for 208 V Operation section on page 11 Accessory Electric Heat Wiring Refer to accessory electric heat installation instructions for information on installing acc...

Page 10: ...9 32 11 3 15 0 31 3 36 1 44 3 50 4 45 60 41 46 15 0 20 0 41 7 48 1 57 4 65 4 60 70 53 60 060 230 1 60 207 254 26 9 128 0 1 4 6 2 41 2 50 40 141 5 0 20 8 41 2 50 40 10 0 41 7 59 8 60 55 15 0 62 5 85 9...

Page 11: ...ed accessories should be installed on the unit Refer to separate accessory installation instructions PRE START UP WARNING Failure to observe the following warn ings could result in serious personal in...

Page 12: ...or heat has been satisfied the evaporator fan will stop For units equipped with time delay relay evaporator fan will stop after a 30 second time delay To shut off unit set system selector switch at OF...

Page 13: ...mended airflow is 350 to 450 cfm per each 12 000 Btuh of rated cooling capacity Table 3 shows dry coil air delivery for horizontal discharge units WARNING Disconnect electrical power to the unit be fo...

Page 14: ...personal injury can result from sharp edges etc 3 Never place anything combustible either on or in con tact with the unit 4 Should overheating occur shut off all of the electri cal supply s I AIR FIL...

Page 15: ...l volume of filter drier NOTE See Adjusting Refrigerant Charge on page 16 C Condenser Coil Evaporator Coil and Condensate Drain Pan WARNING Be careful Coil fins are sharp Protect hands with gloves whe...

Page 16: ...rant system is factory charged When recharging is necessary weigh in total charge indicated on unit name plate Remove and recover any refrigerant remaining in system before recharging If system has lo...

Page 17: ...Fig 19 Cooling Charging Chart 564A 764A024 Fig 20 Cooling Charging Chart 564A 764A030 Fig 21 Cooling Charging Chart 564A 764A036 Fig 22 Cooling Charging Chart 564A 764A042 17...

Page 18: ...Fig 23 Cooling Charging Chart 564A 764A048 Fig 24 Cooling Charging Chart 564A 764A060 18...

Page 19: ...er fan motor or capacitor Replace Restriction in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease loa...

Page 20: ......

Page 21: ......

Page 22: ...n Overview Maintenance Operating Sequence A large selection of product theory and skills programs is available All programs include a video cassette and or slides and a companion booklet Use these for...

Page 23: ......

Page 24: ...NS AND TERMINALS FOR TIGHTNESS M VERIFY THAT UNIT INSTALLATION IS LEVEL M CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE L1...

Reviews: