—13—
DETAILED COOLING CAPACITIES* Continued
See notes on page 18.
EVAPORATOR
AIR
CONDENSER ENTERING AIR TEMPERATURES °F
85
95
105
115
125
CFM
EWB
Capacity
MBtuh†
Total
System
Kw**
Capacity
MBtuh†
Total
System
Kw**
Capacity
MBtuh†
Total
System
Kw**
Capacity
MBtuh†
Total
System
Kw**
Capacity
MBtuh†
Total
System
Kw**
Total
Sens‡
Total
Sens‡
Total
Sens‡
Total
Sens‡
Total
Sens‡
594D024-E Outdoor Section With CC5A/CD5AA030 Indoor Section
700
72
25.7
12.8
2.11
24.7
12.4
2.34
23.7
12.1
2.59
22.7
11.7
2.8
21.6
11.3
3.17
67
23.6
16.3
2.08
22.7
15.9
2.30
21.8
15.5
2.55
20.8
15.2
2.8
19.8
14.8
3.13
62
21.6
19.7
2.06
20.8
19.3
2.27
19.9
18.8
2.52
19.0
18.4
2.7
18.1
17.8
3.10
57
20.8
20.8
2.05
20.1
20.1
2.25
19.4
19.4
2.49
18.7
18.7
2.7
17.9
17.9
3.07
800
72
26.0
13.3
2.15
25.0
12.9
2.38
24.0
12.6
2.63
22.9
12.2
2.9
21.8
11.8
3.21
67
23.9
17.3
2.13
23.0
16.9
2.35
22.0
16.5
2.59
21.0
16.1
2.8
20.0
15.7
3.17
62
22.0
20.9
2.10
21.1
20.4
2.32
20.2
19.9
2.56
19.3
19.3
2.8
18.5
18.5
3.14
57
21.5
21.5
2.09
20.8
20.8
2.31
20.1
20.1
2.56
19.3
19.3
2.8
18.5
18.5
3.14
900
72
26.3
13.8
2.19
25.3
13.5
2.42
24.2
13.1
2.67
23.1
12.7
2.9
21.9
12.3
3.25
67
24.2
18.2
2.17
23.2
17.8
2.39
22.2
17.4
2.63
21.2
17.0
2.9
20.1
16.6
3.21
62
22.3
22.0
2.14
21.4
21.4
2.36
20.6
20.6
2.60
19.8
19.8
2.8
19.0
19.0
3.18
57
22.1
22.1
2.14
21.5
21.5
2.37
20.6
20.6
2.60
19.8
19.8
2.8
19.0
19.0
3.18
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section
Size
Cooling
Indoor
Section
Size
Cooling
Capacity
Power
Capacity
Power
CC5A/CD5AA
024
1.00
1.00
FG3AAA
024
0.98
1.00
030
1.00
1.00
FK4CNF
001
1.04
0.94
CC5A/CD5AW
024
1.00
1.00
002
1.05
0.94
030
1.01
1.00
003
1.06
0.91
CE3AA
024
1.00
1.00
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE
030
1.01
1.00
CC5A/CD5AA
030
1.01
0.92
CF5AA
024
1.00
1.00
CE3AA
030
1.01
0.92
CG5AA
024
1.00
1.00
CK5A/CK5BA
030
1.01
0.92
CK3BA
024
1.00
1.00
COILS + 355MAV042040 VARIABLE SPEED FURNACE
030
1.00
1.00
CC5A/CD5AA
030
1.01
0.94
CK5A/CK5BA
024
1.00
1.00
CK5A/CK5BA
030
1.01
0.94
030
1.00
1.00
COILS + 355MAV042060 VARIABLE SPEED FURNACE
CK5A/CK5BW
024
1.00
1.00
CC5A/CD5AA
030
1.01
0.94
F(A,B)4AN(F,C)
024
1.00
1.00
CK5A/CK5BA
030
1.01
0.94
030
1.02
0.99
COILS + 355MAV042080 VARIABLE SPEED FURNACE
FC4BNF
024
1.00
1.00
CC5A/CD5AA
030
1.01
0.94
030
1.02
0.99
CK5A/CK5BA
030
1.01
0.94
FF1(B,C,D)NA
024
1.00
1.01
—
—
—
030
1.02
1.01
Summary of Contents for 594D
Page 22: ... 22 MATCHED SYSTEM A98599 ...
Page 23: ... 23 ...