SPECIFICATIONS Continued
* Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.
Copper wire must be used from service disconnect to unit.
† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).
The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70)
Article 336-26.
‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2 percent.
All motors/compressors contain internal overload protection.
** Time-delay fuse.
†† Use with Low-Ambient Controller.
‡‡ Fan motor with ball bearings required.
UNIT SIZE - SERIES
042-E
048-E/F
060-E
OPERATING WT (Lb)
213
247
287
ELECTRICAL
Unit Volts—Hertz—Phase
208/230—60—1
208/230—60—1
208/230—60—1
Operating Voltage Range*
187—253
187—253
187—253
Compressor— Rated Load Amps
20.0
23.7/21.3
28.8
Locked Rotor Amps
104.0
129.0/137.0
169.0
Condenser Fan Motor—Full Load Amps
1.1
1.4
1.4
Min Unit Ampacity for Wire Sizing
26.1
31.0/28.0
37.4
Min Wire Size (60°C Copper) AWG†
10
8/10
8
Min Wire Size (75°C Copper) AWG†
10
10
8
Max Wire Length (60°C) (Ft)‡
96
71
104
Max Wire Length (75°C) (Ft)‡
91
68
99
Max Branch Circuit Fuse Size**
40
50/40
60
COMPRESSOR AND REFRIGERANT
Compressor—Manufacturer & Type
Copeland Scroll
Temperature & Current Protection
Internal Line Break
Refrigerant—R-22 Amount (Lb)
6.68
6.34
9.25
CONDENSER COIL AND FAN
Coil Face Area (Sq Ft)
15.2
18.3
Fins per In.—Rows—Circuits
25—1—3
25—1—4
Fan Motor—HP, Type, & RPM
1/5 PSC & 825
1/4 PSC & 1100
Volts—Hertz—Phase
208/230—60—1
Condenser Airflow (CFM)
3000
3300
OPTIONAL EQUIPMENT
Support Feet Kit
KSASF0101AAA
Coastal Filter
KAACF0201MED
Time-Delay Relay
KAATD0101TDR
Cycle Protector
KSACY0101AAA
Standard
Crankcase Heater
KAACH1201AAA
Start Assist—Capacitor/Relay Type
KSAHS1501AAA
KSAHS1601AAA
Start Assist—PTC Type
KAACS0201PTC
TXV Kit (RPB)
KAATX0501RPB
KAATX0601RPB
KAATX0701RPB
TXV Kits (Hard Shutoff)
KSATX0601HSO
KSATX0701HSO
Low-Pressure Switch
KAALP0101LPS
High-Pressure Switch
KSAHI0101HPS
Filter Drier
P502-8163S (RCD)
Evaporator Freeze Thermostat††
KAAFT0101AAA
Liquid-Line Solenoid Valve
KAALS0101LLS
Winter Start Control††
KAAWS0101AAA
Low-Ambient Kit
KSALA0201R22
Low-Ambient Controller
P251-0083 (RCD)
MotorMaster® Control‡‡
32LT660004 (RCD)
Ball Bearing Fan Motor
HC38GE231 (RCD)
HC40GE232 (RCD)
Thermostat, Auto Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
TSTATBBNAC01-B
Thermostat, Auto Changeover,
7-Day Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
TSTATBBPAC01-B
Builder’s Thermostat, Manual
Changeover, Non-Programmable,
°F/°C, 1-Stage Heat, 1-Stage Cool
TSTATBBBAC01-B
Thermidistat™ Control—Programmable/
Non-Programmable Thermostat with
Humidity Control
TSTATBBPRH01-B
Outdoor Air Temperature Sensor
TSTATXXSEN01-B
Backplate for Non-Programmable
Thermostat
TSTATXXNBP01
Backplate for Builder’s Thermostat
TSTATXXBBP01
Backplate for Programmable Thermostat
TSTATXXPBP01
Thermostat Conversion Kit (4 to 5 wire)
— 10 Pack
TSTATXXCNV10