GUIDE SPECIFICATIONS

GENERAL

System Description
Outdoor-mounted, air-cooled, split-system air conditioner unit
suitable for ground or rooftop installation. Unit consists of a her-
metic compressor, an air-cooled coil, propeller-type condenser
fan, and a control box. Unit will discharge supply air upward as
shown on contract drawings. Unit will be used in a refrigeration
circuit to match up to a packaged fan coil or coil unit.
Quality Assurance
Unit will be rated in accordance with the latest edition of ARI
Standard 210.
Unit will be certified for capacity, efficiency, and listed in the latest
ARI directory.
Unit construction will comply with latest edition of ANSI/
ASHRAE and with NEC.
Unit will be constructed in accordance with UL standards and
will carry the UL label of approval. Unit will have c-UL approval.
Unit cabinet will be capable of withstanding Federal Test Method
Standard No. 141 (Method 6061) 500-hr salt spray test.
Air-cooled condenser coils will be leak tested at 150 psig and
pressure tested at 300 psig.
Unit constructed in ISO 9001 approved facility.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored and
handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only.

PRODUCTS

Equipment
Factory assembled, single piece, air-cooled air conditioner unit.
Contained within the unit enclosure will be all factory wiring,
piping, controls, compressor, refrigerant charge (R22), and
special features required prior to field start-up.
Unit Cabinet
Unit cabinet will be constructed of galvanized steel, bonderized,
and coated with a powder coat paint.
Fans
Condenser fan will be direct-drive propeller type, discharging air
upward.

Air-Cooled, Split-System

Air Conditioner

594D

1-1/2 to 5 Tons Nominal

Condenser fan motors will be totally enclosed, 1-phase type
with class B insulation and permanently lubricated bearings.
Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with  steel wire safety
guards.

Compressor
Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.
Condenser Coil
Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanically bonded
to copper tubes which are then cleaned, dehydrated, and
sealed.
Refrigeration Components
Refrigeration circuit components will include liquid-line shutoff
valve with sweat connections, suction line shutoff valves with
sweat connections, system charge of R22 (R-410A) refrigerant,
and compressor oil.

Operating Characteristics
The capacity of the unit will meet or exceed _____ Btuh at a
suction temperature of _____ °F. The power consumption at full
load will not exceed _____ kw.
Combination of the unit and the evaporator or fan coil unit will
have a total net cooling capacity of _____ Btuh or greater at
conditions of   _____   CFM entering air temperature at the
evaporator at _____ °F wet bulb and _____ °F dry bulb, and air
entering the unit at _____ °F.
The system will have an SEER of _____ Btuh/watt or greater at
DOE conditions.

Electrical Requirements
Nominal unit electrical characteristics will be _____ v, single
phase, 60 hertz. The unit will be capable of satisfactory opera-
tion within voltage limits of _____ v to _____ v.
Unit electrical power will be single point connection.
Control circuit will be 24v.

Special Features
Refer to section of this literature identifying accessories and
descriptions for specific features and available enhancements.

Summary of Contents for 594D

Page 1: ...ting refrigerant pressures EASY SERVICEABILITY One panel provides access to elec trical controls and compressor Removal of wire dome grille gives access to fan motor while removal of top gives access to coil COMPRESSOR PROTECTION Each model is protected with internal temperature and current sensitive overloads An inter nal pressure relief valve provides high pressure protection to the refrigerant ...

Page 2: ... IN DIA TIEDOWN KNOCKOUTS 2 PLACES IN BASEPAN 10 1 2 FIELD CONTROL SUPPLY CONN 1 9 16 L C F N G A B M K E D C L A97001 DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H K L M N 018 E 23 13 16 22 1 2 26 3 16 4 1 8 7 1 8 13 13 16 18 3 8 5 8 12 14 5 8 10 2 3 8 20 x 27 024 E 27 13 16 22 1 2 26 3 16 4 1 8 7 1 8 15 15 16 22 3 8 5 8 12 14 5 8 11 2 3 8 20 x 27 ...

Page 3: ... 060 1 1 8 1 1 8 UNIT SIZE SERIES PISTON IDENTIFICATION NO 018 E 55 024 E 59 030 E 67 036 E 73 042 E 78 048 E F 84 060 E 93 UNIT SIZE SOUND LEVEL dBA OCTAVE BAND CENTER FREQUENCY Hz 125 250 500 1000 2000 4000 8000 018 72 54 5 63 0 65 5 66 0 63 5 59 0 51 5 024 74 51 5 61 0 62 5 65 5 62 0 58 5 52 5 030 74 57 0 64 0 67 0 69 0 64 0 60 0 52 5 036 76 59 0 66 0 67 0 69 5 66 5 62 5 56 0 042 76 58 0 65 0 6...

Page 4: ...er KAACF0601SML KAACF0201MED Time Delay Relay KAATD0101TDR Cycle Protector KSACY0101AAA Crankcase Heater KAACH1201AAA Start Assist Capacitor Relay Type KSAHS1501AAA Start Assist PTC Type KAACS0201PTC TXV Kit RPB KAATX0201RPB KAATX0301RPB KAATX0401RPB KAATX0501RPB TXV Kits Hard Shutoff KSATX0601HSO Low Pressure Switch KAALP0101LPS High Pressure Switch KSAHI0101HPS Filter Drier P502 8083S RCD Evapor...

Page 5: ...reak Refrigerant R 22 Amount Lb 6 68 6 34 9 25 CONDENSER COIL AND FAN Coil Face Area Sq Ft 15 2 18 3 Fins per In Rows Circuits 25 1 3 25 1 4 Fan Motor HP Type RPM 1 5 PSC 825 1 4 PSC 1100 Volts Hertz Phase 208 230 60 1 Condenser Airflow CFM 3000 3300 OPTIONAL EQUIPMENT Support Feet Kit KSASF0101AAA Coastal Filter KAACF0201MED Time Delay Relay KAATD0101TDR Cycle Protector KSACY0101AAA Standard Cran...

Page 6: ...ions are frequent Where user is likely to play with the room thermostat All commercial installations Installations where interconnecting tube length exceeds 50 ft High rise applications 7 Evaporator Freeze Thermostat An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze up conditions SUGGESTED USE All units where Winter Start Control has been added Use with ...

Page 7: ...tures below 55 F All commercial installations 14 Outdoor Air Temperature Sensor A device that allows the temperature at a remote location outdoors to be displayed at the thermostat SUGGESTED USE All corporate programmable thermostats 15 Support Feet Four stick on plastic feet which raise the unit 4 in above the mounting pad This allows sand dirt and other debris to be flushed from the unit base mi...

Page 8: ...24 23 000 NONE 10 80 11 00 11 00 9 70 CK3BA030 23 000 NONE 10 80 11 00 11 00 9 80 CK5A CK5BA024 23 000 NONE 10 80 11 00 11 00 9 70 CK5A CK5BA030 23 000 NONE 10 80 11 00 11 00 9 80 CK5A CK5BW024 23 000 NONE 10 80 11 00 11 00 9 70 CK5A CK5BW030 23 200 NONE 10 80 11 00 11 00 9 80 F A B 4AN F C 024 23 000 TDR 11 00 11 00 9 80 F A B 4AN F C 030 23 400 TDR 11 40 11 40 10 00 FC4BNF024 23 000 TDR TXV 11 0...

Page 9: ...000 NONE 11 00 11 20 11 20 10 15 CK5A CK5BA042 35 000 NONE 11 00 11 20 11 20 10 15 CK5A CK5BW036 35 000 NONE 11 00 11 20 11 20 10 15 CK5A CK5BW042 34 800 NONE 11 00 11 20 11 20 10 05 F A B 4AN F B C 042 35 000 TDR 11 20 11 20 10 10 F A B 4AN F C 036 34 400 TDR 11 00 11 00 9 80 FC4BNB054 36 600 TDR TXV 12 00 10 80 FC4BNF036 34 400 TDR TXV 11 00 9 80 FC4BN F B 042 35 000 TDR TXV 11 20 10 10 FC4BNF03...

Page 10: ...1 000 TDR 12 00 12 00 11 15 COILS 355MAV060100 VARIABLE SPEED FURNACE CD5AA048 41 000 TDR 12 50 12 50 11 15 CK5A CK5BA048 41 000 TDR 12 50 12 50 11 15 048 E F CC5A CD5AA060 46 800 NONE 10 60 11 00 11 00 9 65 CC5A CD5AC048 45 000 NONE 10 50 10 80 10 80 9 50 CC5A CD5AW048 46 000 NONE 10 50 11 00 11 00 9 60 CC5A CD5AW060 48 000 NONE 10 80 11 20 11 20 9 85 CD5AA048 46 500 NONE 10 50 11 00 11 00 9 60 C...

Page 11: ...TDR 11 00 11 00 9 75 CK5A CK5BA048 46 000 TDR 11 00 11 00 9 75 COILS 355MAV060080 VARIABLE SPEED FURNACE CC5A CD5AA060 46 000 TDR 11 00 11 00 9 70 CC5A CD5AW060 47 000 TDR 11 20 11 20 9 95 CD5AA048 46 000 TDR 11 00 11 00 9 60 CK3BA048 46 000 TDR 11 00 11 00 9 70 CK5A CK5BA060 46 500 TDR 11 00 11 00 9 90 CK5A CK5BX060 47 000 TDR 11 20 11 20 10 15 CK5A CK5BA048 46 000 TDR 11 00 11 00 9 70 COILS 355M...

Page 12: ... 46 15 9 15 9 1 64 15 3 15 3 1 83 14 7 14 7 2 00 14 1 14 1 2 29 675 72 20 1 10 5 1 54 19 3 10 2 1 72 18 6 9 98 1 92 17 7 9 68 2 10 16 9 9 38 2 38 67 18 6 13 8 1 52 17 9 13 5 1 70 17 1 13 2 1 89 16 3 12 9 2 10 15 4 12 6 2 33 62 17 1 16 7 1 51 16 4 16 3 1 68 15 8 15 8 1 87 15 1 15 1 2 00 14 4 14 4 2 31 57 16 9 16 9 1 49 16 4 16 4 1 68 15 8 15 8 1 87 15 1 15 1 2 00 14 5 14 5 2 32 Multipliers for Dete...

Page 13: ...5 2 42 24 2 13 1 2 67 23 1 12 7 2 9 21 9 12 3 3 25 67 24 2 18 2 2 17 23 2 17 8 2 39 22 2 17 4 2 63 21 2 17 0 2 9 20 1 16 6 3 21 62 22 3 22 0 2 14 21 4 21 4 2 36 20 6 20 6 2 60 19 8 19 8 2 8 19 0 19 0 3 18 57 22 1 22 1 2 14 21 5 21 5 2 37 20 6 20 6 2 60 19 8 19 8 2 8 19 0 19 0 3 18 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size...

Page 14: ... 67 30 6 22 8 2 66 29 4 22 3 3 05 28 0 21 7 3 54 26 4 21 1 4 1 24 3 20 3 5 15 62 28 2 27 6 2 67 27 0 26 8 3 07 25 8 25 8 3 56 24 5 24 5 4 1 22 6 22 6 5 34 57 27 9 27 9 2 68 26 9 26 9 3 08 25 8 25 8 3 58 24 6 24 6 4 1 22 8 22 8 5 18 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA ...

Page 15: ... 91 30 1 30 1 4 3 28 6 28 6 4 71 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 036 1 00 1 00 CE3AA 042 0 99 0 95 042 1 00 1 00 CK5A CK5BA 042 0 99 0 94 CC5A CD5AW 042 0 99 1 00 COILS 333 B J AV048080 VARIABLE SPEED FURNACE CD5AW 036 1 00 1 00 CC5A CD5AA 042 0 99 0 94 CE3AA 036 ...

Page 16: ...1 41 5 30 9 4 09 39 7 30 2 4 51 37 9 29 5 4 9 36 1 28 8 5 53 62 39 6 38 3 3 68 38 1 38 3 4 05 36 5 36 3 4 48 35 0 35 0 4 9 33 6 33 6 5 49 57 39 0 39 0 3 67 37 7 37 7 4 05 36 4 36 4 4 48 35 0 35 0 4 9 33 6 33 6 5 50 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 042 1 00 1 00 FK4...

Page 17: ...9 COILS 333 B J AV060120 VARIABLE SPEED FURNACE CC5A CD5AW 048 0 98 1 00 CC5A CD5AA 060 0 99 0 95 060 1 03 1 00 CC5A CD5AW 048 0 98 0 95 CD5AA 048 0 99 1 00 060 1 00 0 95 CE3AA 048 0 99 1 00 CK3BA 060 0 99 0 95 060 1 03 1 00 CK5A CK5BA 060 0 99 0 95 CF5AA 048 0 99 0 99 CK5A CK5BW 048 0 98 0 95 CK3BA 048 0 99 1 00 CK5A CK5BX 060 1 00 0 95 060 1 00 1 00 COILS 355MAV042080 VARIABLE SPEED FURNACE CK5A...

Page 18: ...2 29 4 6 35 54 9 28 2 6 7 50 9 26 8 7 13 67 57 8 39 6 5 36 55 4 38 6 5 79 52 5 37 5 6 21 49 0 36 1 6 5 44 8 34 4 6 76 62 52 4 47 6 5 28 49 9 46 4 5 68 46 9 44 8 6 02 43 4 42 8 6 2 39 7 39 7 6 37 57 50 2 50 2 5 20 48 2 48 2 5 59 45 9 45 9 5 93 43 2 43 2 6 2 40 1 40 1 6 37 2000 72 64 7 32 8 5 44 62 1 31 8 5 91 59 3 30 8 6 38 56 0 29 7 6 8 52 1 28 3 7 22 67 59 0 42 0 5 38 56 5 41 0 5 82 53 6 39 9 6 2...

Page 19: ...KW 1 30 1 48 1 66 1 87 2 09 2 33 2 60 55 TCG 33 5 32 5 31 4 30 0 28 6 27 1 25 6 SDT 92 7 101 0 110 0 120 0 129 0 138 0 147 0 KW 1 32 1 49 1 69 1 90 2 13 2 38 2 65 594D030 E 30 TCG 28 3 27 0 25 7 24 2 22 8 21 2 19 7 SDT 80 4 90 3 100 0 110 0 120 0 130 0 140 0 KW 1 47 1 72 1 99 2 30 2 63 2 99 3 34 35 TCG 31 0 29 6 28 2 26 7 25 1 23 5 21 8 SDT 82 0 91 9 102 0 112 0 122 0 132 0 142 0 KW 1 46 1 71 1 99...

Page 20: ...65 4 13 4 64 5 17 35 TCG 50 4 48 1 45 7 43 2 40 7 38 1 35 5 SDT 81 9 91 6 101 0 111 0 121 0 131 0 140 0 KW 2 49 2 85 3 25 3 69 4 18 4 71 5 25 40 TCG 55 1 52 6 50 1 47 4 44 7 41 9 39 1 SDT 83 9 93 4 103 0 113 0 123 0 132 0 142 0 KW 2 52 2 88 3 29 3 74 4 23 4 77 5 34 45 TCG 60 0 57 4 54 7 51 9 49 0 46 0 43 0 SDT 86 0 95 5 105 0 115 0 124 0 134 0 144 0 KW 2 55 2 92 3 33 3 79 4 29 4 84 5 43 50 TCG 65 ...

Page 21: ...n 50 ft consult Residential Split System Long Line Application Guidelines available from equipment distributor 7 Crankcase heater required when interconnecting refrigerant tube length exceeds 50 ft 8 Not more than 3 ft of refrigerant tube should be buried in the ground If necessary to bury tubes under a sidewalk provide a minimum 6 in vertical rise to the valve connections at the unit For buried l...

Page 22: ... 22 MATCHED SYSTEM A98599 ...

Page 23: ... 23 ...

Page 24: ...nit cabinet will be constructed of galvanized steel bonderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Air Conditioner 594D 1 1 2 to 5 Tons Nominal Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant ...

Reviews: