221
PERFORMANCE DATA (cont)
ALTITUDE COMPENSATION* —
580F180-300
*Includes a 4% input reduction per each 1,000 feet.
†Orifices available through your Bryant dealer.
ALTITUDE DERATING FACTOR*
*Derating of the unit is not required unless the heating value of the gas
exceeds the values listed in the table above, or if the elevation
exceeds 6000 ft. Derating conditions must be 4% per thousand ft
above 2000 ft. For example, at 4000 ft, if the heating value of the gas
exceeds 1000 Btu/ft
3
, the unit will require a 16% derating. For ele-
vations above 6000 ft, the same formula applies. For example, at 7000
ft, the unit will require a 28% derating of the maximum heating value
per the National Fuel Gas Code.
IMPORTANT:
Local utility companies may be reducing heat content of
gas at altitudes above 2000 ft. If this is being done, changing spuds
may not be required.
ALTITUDE COMPENSATION — 580F180-300
(LP Gas Units)
OUTDOOR SOUND POWER
LEGEND
NOTE:
Indoor sound power is available in Bryant’s Electronic Catalog
program (ECAT) for specific operating parameters.
ELEVATION
(ft)
NATURAL GAS ORIFICE SIZE†
Low Heat
High Heat
0-3,000
30
29
3,000- 7,000
31
30
7,000- 9,000
32
31
9,000-10,000
33
31
above 10,000
35
32
Fan Performance Using Accessory
Power Exhaust (580F180-300)
a50-4028
ELEVATION
(ft)
MAXIMUM HEATING VALUE
(Btu/ft
3
)
0-2,000
1,100
2,001-3,000
1,050
3,001-4,000
1,000
4,001-5,000
950
5,001-6,000
900
ELEVATION
(ft)
LIQUID PROPANE
ORIFICE SIZE
Low Heat and High Heat
0-2,000
36
2,000
37
3,000
38
4,000
38
5,000
39
6,000
40
7,000
41
8,000
41
9,000
42
10,000
43
UNIT
580F
SOUND
RATING
(60 Hz)
A-WEIGHTED
(dB)
OCTAVE BANDS
63
125
250
500
1000
2000
4000
8000
180
88 dB
87.6
90.8
88.7
86.4
84.3
83.5
78.4
75.6
66.8
210
88 dB
87.8
90.8
88.7
86.4
84.3
83.5
78.4
75.6
66.8
240
94 dB
94.4
99.7
93.0
93.7
91.8
89.7
85.9
80.7
74.4
300
94 dB
94.1
98.7
92.3
93.8
90.9
89.6
85.9
80.3
74.3
Bels
—
Sound Levels (1 bel = 10 decibels)
5
80F
180
-3
00
Summary of Contents for 581A
Page 30: ...30 BASE UNIT DIMENSIONS 580F036 072 a48 8195 580F036 151 ...
Page 31: ...31 BASE UNIT DIMENSIONS 580F073 a48 8196 580F036 151 ...
Page 32: ...32 BASE UNIT DIMENSIONS 580F090 120 150 a48 8197 580F036 151 ...
Page 33: ...33 BASE UNIT DIMENSIONS 580F091 103 121 151 a48 8198 580F036 151 ...
Page 91: ...91 BASE UNIT DIMENSIONS 581B036 072 a48 8199 581B036 150 ...
Page 93: ...93 ACCESSORY DIMENSIONS 581B036 072 a48 8201 581B036 150 ...
Page 94: ...94 ACCESSORY DIMENSIONS 581B090 150 a48 8202 581B036 150 ...
Page 150: ...150 BASE UNIT DIMENSIONS 581C024 060 581C024 060 ...
Page 198: ...198 TYPICAL WIRING SCHEMATICS 579F 579F240 208 230 V Shown a48 7929 ...
Page 205: ...205 BASE UNIT DIMENSIONS 580F180 210 a48 8203 580F180 300 ...
Page 206: ...206 BASE UNIT DIMENSIONS 580F240 a48 8204 ...
Page 207: ...207 BASE UNIT DIMENSIONS 580F300 a48 8205 580F180 300 ...
Page 209: ...209 ACCESSORY DIMENSIONS 580F300 Vertical Roof Curbs 580F300 a48 7456 580F180 300 ...
Page 233: ...233 BASE UNIT DIMENSIONS 581A210 300 a48 8206 581A155 180 ...
Page 237: ...237 ACCESSORY DIMENSIONS 581A210 300 a48 8234 581A155 180 ...
Page 280: ...280 TYPICAL PIPING AND WIRING 581A 581A155 Shown LEGEND NEC National Electrical Code b48 1258 ...
Page 297: ...297 ...