230
PHYSICAL DATA (cont)
EVAPORATOR FAN DATA — 581A210-300 VERTICAL SUPPLY/RETURN UNITS
LEGEND
EVAPORATOR FAN DATA — 581A210-300 HORIZONTAL SUPPLY/RETURN UNITS
LEGEND
581A
210
240
300
203/230 and 460 V
575 V
203/230 and 460 V
575 V
203/230 and 460 V
575 V
LOW RANGE
Motor Hp
3.7
3
5
5
5
5
Motor Nominal RPM
1725
1725
1745
1745
1745
1745
Maximum Continuous Bhp
4.25
3.45
5.75
5.75
5.75
5.75
Maximum Continuous Watts
3698
3149
4900
4900
4900
4900
Motor Frame Size
56HZ
56HZ
S184T
184T
S184T
184T
Motor Shaft Diameter (in.)
7
/
8
7
/
8
1
1
/
8
1
1
/
8
1
1
/
8
1
1
/
8
Fan Rpm Range
647-886
810-1072
949-1206
949-1206
805-1007
805-1007
Motor Pulley Min. Pitch Diameter (in.)
2.7
3.1
3.7
3.7
4.8
4.8
Motor Pulley Max. Pitch Diameter (in.)
3.7
4.1
4.7
4.7
6.0
6.0
Blower Pulley Pitch Diameter (in.)
7.2
6.6
6.8
6.8
10.4
10.4
Blower Pulley Shaft Diameter (in.)
1.1875
1.1875
1.1875
1.1875
1.1875
1.1875
Blower Pulley Type
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Pulley Center Line Distance (in.)
11.293-13.544
11.286-14.475
9.81-13.055
9.81-13.055
9.81-13.055
9.81-13.055
Belt, Quantity...Type...Length (in.)
1...BX...38
1...BX...38
1...BX...38
1...BX...38
1...BX...45
1...BX...45
Speed Change Per Turn — Moveable Pulley (rpm)
48
52
51
51
40
40
Moveable Pulley Maximum Full Turns
6
6
6
6
6
6
Factory Speed Setting (rpm)
767
941
1078
1078
906
906
HIGH RANGE
Motor Hp
5
5
7.5
7.5
7.5
7.5
Motor Nominal Rpm
1745
1745
1745
1745
1745
1745
Maximum Continuous Bhp
5.75
5.75
8.63
8.63
8.63
8.63
Maximum Continuous Watts
4900
4900
7267
7267
7267
7267
Motor Frame Size
S184T
184T
S213T
S213T
S213T
S213T
Motor Shaft Diameter (in.)
1
1
/
8
1
1
/
8
1
3
/
8
1
3
/
8
1
3
/
8
1
3
/
8
Fan Rpm Range
897-1139
873-1108
941-1176
941-1176
941-1176
941-1176
Motor Pulley Min. Pitch Diameter (in.)
3.7
3.7
4.8
4.8
4.8
4.8
Motor Pulley Max. Pitch Diameter (in.)
4.7
4.7
6.0
6.0
6.0
6.0
Blower Pulley Pitch Diameter (in.)
7.2
7.4
8.9
8.9
8.9
8.9
Blower Pulley Shaft Diameter (in.)
1.1875
1.1875
1.1875
1.1875
1.1875
1.1875
Blower Pulley Type
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Pulley Center Line Distance (in.)
9.81-13.055
9.81-13.055
9.025-12.179
9.025-12.179
9.025-12.179
9.025-12.179
Belt, Quantity...Type...Length (in.)
1...BX...38
1...BX...38
1...BX...42
1...BX...42
1...BX...42
1...BX...42
Speed Change Per Turn — Moveable Pulley (rpm)
48
47
47
47
47
47
Moveable Pulley Maximum Full Turns
6
6
6
6
6
6
Factory Speed Setting (rpm)
1018
991
1059
1059
1059
1059
Bhp
—
Brake Horsepower
581A
210
240
300
203/230 and 460 V
575 V
203/230 and 460 V
575 V
203/230 and 460 V
575 V
LOW RANGE
Motor Hp
3.7
3
3.7
5
5
5
Motor Nominal Rpm
1725
1725
1725
1745
1745
1745
Maximum Continuous Bhp
4.25
3.45
4.25
5.75
5.75
5.75
Maximum Continuous Watts
3698
3149
3698
4900
4900
4900
Motor Frame Size
56HZ
56HZ
56HZ
184T
S184T
184T
Motor Shaft Diameter (in.)
7
/
8
7
/
8
7
/
8
1
1
/
8
1
1
/
8
1
1
/
8
Fan Rpm Range
896-1227
863-1141
896-1227
873-1108
805-1007
805-1007
Motor Pulley Min. Pitch Diameter (in.)
2.7
3.1
2.7
3.7
4.8
4.8
Motor Pulley Max. Pitch Diameter (in.)
3.7
4.1
3.7
4.7
6.0
6.0
Blower Pulley Pitch Diameter (in.)
5.2
6.2
5.2
7.4
10.4
10.4
Blower Pulley Shaft Diameter (in.)
1.1875
1.1875
1.1875
1.1875
1.1875
1.1875
Blower Pulley Type
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Pulley Center Line Distance (in.)
11.293-13.544
11.286-14.475
11.293-13.544
9.81-13.055
9.81-13.055
9.81-13.055
Belt, Quantity...Type...Length (in.)
1...BX...35
1...BX...38
1...BX...35
1...BX...38
1...BX...45
1...BX...45
Speed Change Per Turn — Moveable Pulley (rpm)
66
56
66
47
40
40
Moveable Pulley Maximum Full Turns
6
6
6
6
6
6
Factory Speed Setting (rpm)
1062
1002
1062
991
906
906
HIGH RANGE
Motor Hp
5
5
5
5
7.5
7.5
Motor Nominal Rpm
1745
1745
1745
1745
1745
1745
Maximum Continuous Bhp
5.75
5.75
5.75
5.75
8.63
8.63
Maximum Continuous Watts
4900
4900
4900
4900
7267
7267
Motor Frame Size
S184T
184T
S184T
184T
S213T
S213T
Motor Shaft Diameter (in.)
1
1
/
8
1
1
/
8
1
1
/
8
1
1
/
8
1
3
/
8
1
3
/
8
Fan Rpm Range
1113-1414
1042-1285
1113-1414
1113-1414
941-1176
941-1176
Motor Pulley Min. Pitch Diameter (in.)
3.7
4.3
3.7
3.7
4.8
4.8
Motor Pulley Max. Pitch Diameter (in.)
4.7
5.3
4.7
4.7
6.0
6.0
Blower Pulley Pitch Diameter (in.)
5.8
7.2
5.8
5.8
8.9
8.9
Blower Pulley Shaft Diameter (in.)
1.1875
1.1875
1.1875
1.1875
1.1875
1.1875
Blower Pulley Type
Fixed
Fixed
Fixed
Fixed
Fixed
Fixed
Pulley Center Line Distance (in.)
9.81-13.055
9.81-13.055
9.81-13.055
9.81-13.055
9.025-12.179
9.025-12.179
Belt, Quantity...Type...Length (in.)
1...BX...35
1...BX...38
1...BX...35
1...BX...35
1...BX...42
1...BX...42
Speed Change Per Turn — Moveable Pulley (rpm)
60
48
60
60
47
47
Moveable Pulley Maximum Full Turns
6
6
6
6
6
6
Factory Speed Setting (rpm)
1264
1164
1264
1264
1059
1059
Bhp
—
Brake Horsepower
Summary of Contents for 581A
Page 30: ...30 BASE UNIT DIMENSIONS 580F036 072 a48 8195 580F036 151 ...
Page 31: ...31 BASE UNIT DIMENSIONS 580F073 a48 8196 580F036 151 ...
Page 32: ...32 BASE UNIT DIMENSIONS 580F090 120 150 a48 8197 580F036 151 ...
Page 33: ...33 BASE UNIT DIMENSIONS 580F091 103 121 151 a48 8198 580F036 151 ...
Page 91: ...91 BASE UNIT DIMENSIONS 581B036 072 a48 8199 581B036 150 ...
Page 93: ...93 ACCESSORY DIMENSIONS 581B036 072 a48 8201 581B036 150 ...
Page 94: ...94 ACCESSORY DIMENSIONS 581B090 150 a48 8202 581B036 150 ...
Page 150: ...150 BASE UNIT DIMENSIONS 581C024 060 581C024 060 ...
Page 198: ...198 TYPICAL WIRING SCHEMATICS 579F 579F240 208 230 V Shown a48 7929 ...
Page 205: ...205 BASE UNIT DIMENSIONS 580F180 210 a48 8203 580F180 300 ...
Page 206: ...206 BASE UNIT DIMENSIONS 580F240 a48 8204 ...
Page 207: ...207 BASE UNIT DIMENSIONS 580F300 a48 8205 580F180 300 ...
Page 209: ...209 ACCESSORY DIMENSIONS 580F300 Vertical Roof Curbs 580F300 a48 7456 580F180 300 ...
Page 233: ...233 BASE UNIT DIMENSIONS 581A210 300 a48 8206 581A155 180 ...
Page 237: ...237 ACCESSORY DIMENSIONS 581A210 300 a48 8234 581A155 180 ...
Page 280: ...280 TYPICAL PIPING AND WIRING 581A 581A155 Shown LEGEND NEC National Electrical Code b48 1258 ...