APPLICATION DATA (cont)
c.
E-COATED ALUMINUM FIN
coils undergo a precisely
controlled scientific process that bonds an impermeable
epoxy coating to the specially prepared fin coil surface.
E-Coating produces a smooth, consistent coating that is
less brittle, more resilient and more durable than previ-
ous postcoating processes. E-Coated aluminum-fin coils
offer economical protection and improved coil life in
many contaminated environments.
d.
E-COATED COPPER-FIN COILS
provide maximum
protection in virtually all environments, this option com-
bines the continuous, impenetrable barrier of the E-
Coating process with the natural resistance of an all-cop-
per construction. E-Coated copper-fin coil assemblies
ensure long life, even in environments that combine
harsh coastal conditions with industrial contamination.
16.
ECONOMI$ER IV —
The EconoMi$er IV factory-installed
economizer package includes a gear-driven damper sys-
tem that modulates the return air and outdoor air supply to
the rooftop unit in order to take advantage of “free cooling”
with outdoor air when conditions are suitable. The system
utilizes industry proven technology available for integrating
the use of outdoor air for cooling with mechanical cooling
for 3 through 25-ton rooftop units. The intuitive
EconoMi$er IV microprocessor-based controller optimizes
and enhances rooftop operation through reduced energy
consumption, optimal zone comfort, and efficient equip-
ment cycling. This is accomplished by operating the com-
pressors when the outdoor air temperature is too warm,
integrating the compressors with outdoor air when free
cooling is available, and locking out the compressor when
outdoor air temperature is too cold. The detailed sequence
of operation is described in the Controls section with a brief
description of selected application items here.
a.
THERMOSTAT INTERFACE —
The EconoMi$er IV con-
trol was designed to work with conventional thermostats
that have Y1 (cooling stage 1), Y2 (cooling stage 2), W1
(heat stage 1), W2 (heat stage 2), and G (fan). In addi-
tion, the EconoMi$er IV will support an occupied/
unoccupied switch (typically integrated into the thermo-
stat or Thermidistat™ device). When the switch is
closed, it provides a 24-vac signal to the unit for occu-
pied mode, and provides no signal to indicate unoccu-
pied mode. The EconoMi$er IV control can be
configured to allow different minimum economizer
damper positions and to allow the use of mechanical
cooling in the occupied mode.
CONDENSER COIL PROTECTION APPLICATIONS
LEGEND
CONCENTRIC DUCT DISTRIBUTION
CONCENTRIC DUCT DETAILS
NOTE:
Do not drill in this area, damage to basepan may result in
water leak.
6'-2 3/8'' MAX.
5'-9 3/16'' MAX.
5 3/16''
B
A
BAFFLE
A
B
24'' MIN.
1'-0 3/16''
1'-7 15/16''
4'-6 13/16''
1'-0 3/16''
1'-10 11/16''
MAX.
Shaded area indicates block-off panels.
NOTE:
Dimensions A, A
′
and B, B
′
are obtained from field-supplied
ceiling diffuser.
Concentric Duct Details
a48-7482
a50-530
DESCRIPTION
(Dura-Shield Option)
ENVIRONMENT
Standard, Non-Corrosive
Mild Coastal
Severe Coastal
Industrial
Combined Coastal
and Industrial
Standard, Al/Cu
X
Pre-Coated Al/Cu
X
Cu/Cu
X
E-Coated Al/Cu
X
X
E-Coated Cu/Cu
X
Al/Cu
—
Aluminum Fin with Copper Tube Coil
E-Coated
—
Extremely Flexible and Durable Epoxy Coating Uniformly
Cu/Cu
—
Copper Fin with Copper Tube Coil
Applied to the Coil Surfaces
Dura-Shield
—
Family of Coil Protection Options
Pre-Coated —
Epoxy Coating Applied to Fin Stock Material
Summary of Contents for 581A
Page 30: ...30 BASE UNIT DIMENSIONS 580F036 072 a48 8195 580F036 151 ...
Page 31: ...31 BASE UNIT DIMENSIONS 580F073 a48 8196 580F036 151 ...
Page 32: ...32 BASE UNIT DIMENSIONS 580F090 120 150 a48 8197 580F036 151 ...
Page 33: ...33 BASE UNIT DIMENSIONS 580F091 103 121 151 a48 8198 580F036 151 ...
Page 91: ...91 BASE UNIT DIMENSIONS 581B036 072 a48 8199 581B036 150 ...
Page 93: ...93 ACCESSORY DIMENSIONS 581B036 072 a48 8201 581B036 150 ...
Page 94: ...94 ACCESSORY DIMENSIONS 581B090 150 a48 8202 581B036 150 ...
Page 150: ...150 BASE UNIT DIMENSIONS 581C024 060 581C024 060 ...
Page 198: ...198 TYPICAL WIRING SCHEMATICS 579F 579F240 208 230 V Shown a48 7929 ...
Page 205: ...205 BASE UNIT DIMENSIONS 580F180 210 a48 8203 580F180 300 ...
Page 206: ...206 BASE UNIT DIMENSIONS 580F240 a48 8204 ...
Page 207: ...207 BASE UNIT DIMENSIONS 580F300 a48 8205 580F180 300 ...
Page 209: ...209 ACCESSORY DIMENSIONS 580F300 Vertical Roof Curbs 580F300 a48 7456 580F180 300 ...
Page 233: ...233 BASE UNIT DIMENSIONS 581A210 300 a48 8206 581A155 180 ...
Page 237: ...237 ACCESSORY DIMENSIONS 581A210 300 a48 8234 581A155 180 ...
Page 280: ...280 TYPICAL PIPING AND WIRING 581A 581A155 Shown LEGEND NEC National Electrical Code b48 1258 ...
Page 297: ...297 ...