TWO-POSITION DAMPER HOOD REMOVAL —
FACTORY OPTION (SIZE 16)
1. The hood is shipped in knock-down form and assembled
to a metal support tray using plastic stretch wrap. Located
in the return air compartment, the assembly’s metal tray is
attached to the basepan and also attached to the damper
using two plastic tie-wraps.
2. To gain access to the hood, remove the filter access panel.
3. Locate the (2) screws holding the metal tray to the basepan
and remove. In order to remove the screws, it may be neces-
sary to remove the panel underneath the two-position damp-
er. Remove the two screws. Locate and cut the (2) plastic tie-
wraps securing the assembly to the damper. (See Fig. 16.) Be
careful to not damage any wiring or cut tie-wraps securing
any wiring.
4. Carefully lift the hood assembly (with metal tray) through
the filter access opening and assemble per the steps outlined
in ECONOMIZER AND TWO-POSITION DAMPER
HOOD SETUP, SIZE 16 on page 20.
5. If removed, reattach the panel under the damper.
ECONOMIZER AND TWO-POSITION DAMPER
HOOD SETUP (SIZE 08-14)
NOTE: If the power exhaust accessory is to be installed on the
unit, the hood shipped with the unit will not be used and must be
discarded. Save the aluminum filter for use in the power exhaust
hood assembly.
1. The indoor coil access panel will be used as the top of the
hood. Remove the screws along the sides and bottom of
the indoor coil access panel. See Fig. 17.
2. Swing out indoor coil access panel and insert the hood sides
under the panel (hood top). Use the screws provided to at-
tach the hood sides to the hood top. Use screws provided to
attach the hood sides to the unit. See Fig. 18.
3. Remove the shipping tape holding the economizer baromet-
ric relief damper in place (economizer only).
4. Insert the hood divider between the hood sides. See Fig. 18
and 19. Secure hood divider with 2 screws on each hood
side. The hood divider is also used as the bottom filter rack
for the aluminum filter.
5. Open the filter clips which are located underneath the hood
top. Insert the aluminum filter into the bottom filter rack
(hood divider). Push the filter into position past the open fil-
ter clips. Close the filter clips to lock the filter into place. See
6. Caulk the ends of the joint between the unit top panel and the
hood top.
7. Replace the filter access panel.
Fig. 17 — Indoor Coil Access Panel Relocation (Size 08-14
Shown)
Fig. 18 — Economizer Hood Construction
(Size 08-14 Shown)
Fig. 19 — Economizer Filter Installation
(Size 08-14 Shown)
TOP
PANEL
INDOOR
COIL
ACCE
SS
PANEL
INDOOR
COIL
ACCE
SS
PANEL
CAULK
HERE
TOP
PANEL
B
TOP
PANEL
INDOOR COIL
ACCE
SS
PANEL
19 1/16
”
S
CREW
HOOD DIVIDER
LEFT
HOOD
S
IDE
33 3
/
8”
(
8
4
8
mm)
(4
83
mm)
DIVIDER
BAROMETRIC
RELIEF
CLEANABLE
ALUMINUM
FILTER
FILTER
HOOD
FILTER
CLIP
OUT
S
IDE
AIR
Summary of Contents for 580J*16D Series
Page 4: ...4 Fig 2 Unit Dimensional Drawing Sizes 08 09 and 12 ...
Page 5: ...5 Fig 2 Unit Dimensional Drawing Sizes 08 09 and 12 cont ...
Page 6: ...6 Fig 3 Unit Dimensional Drawing Size 14 ...
Page 7: ...7 Fig 3 Unit Dimensional Drawing Size 14 cont ...
Page 8: ...8 Fig 4 Unit Dimensional Drawing Size 16 ...
Page 9: ...9 Fig 4 Unit Dimensional Drawing Size 16 cont ...
Page 15: ...15 Fig 9 580J 16 Roof Curb Details ...
Page 32: ...32 Fig 58 580J 08 14 Typical Perfect Humidity Dehumidification System Humidistat Wiring ...
Page 33: ...33 Fig 59 580J 16 Typical Perfect Humidity Dehumidification System Humidistat Wiring ...
Page 48: ...48 Fig 67 580J 08 12N P Typical RTU Open System Control Wiring Diagram ...
Page 49: ...49 Fig 68 580J 08 14 Typical RTU Open System Control Wiring Diagram ...
Page 50: ...50 Fig 69 580J 16 Typical RTU Open System Control Wiring Diagram ...
Page 52: ...52 Fig 71 580J 16 Typical RTU Open System Control Wiring Diagram with Perfect Humidity System ...