18
SIZE 16 CONVERSION —
Unit is shipped in the vertical duct
configuration. Unit without factory-installed economizer or return
air smoke detector option may be field-converted to horizontal
ducted configuration using accessory CRDUCTCV002A00. To
convert to horizontal configuration, remove screws from side duct
opening covers and remove covers.
Discard the supply duct cover. Install accessory
CRDUCTCV002A00 to cover the vertical supply duct opening.
Use the return duct cover removed from the end panel to cover the
vertical return duct opening.
ALL UNITS —
Field-supplied flanges should be attached to
horizontal duct openings and all ductwork should be secured to
the flanges. Insulate and weatherproof all external ductwork,
joints, and roof or building openings with counter flashing and
mastic in accordance with applicable codes.
Do not cover or obscure visibility to the unit’s informative data
plate when insulating horizontal ductwork.
Step 8 — Install Outside Air Hood
ECONOMIZER AND TWO POSITION DAMPER HOOD
PACKAGE REMOVAL — FACTORY OPTION
(SIZE 08-14)
1. The hood is shipped in knock-down form and must be
field assembled. The indoor coil access panel is used as
the hood top while the hood sides, divider and filter are
packaged together, attached to a metal support tray using
plastic stretch wrap, and shipped in the return air com-
partment behind the indoor coil access panel. The hood
assembly’s metal tray is attached to the basepan and also
attached to the damper using two plastic tie-wraps.
2. To gain access to the hood, remove the filter access panel.
3. Locate the (2) screws holding the metal tray to the basepan
and remove. Locate and cut the (2) plastic tie-wraps securing
the assembly to the damper (see Fig. 15). Be careful to not
damage any wiring or cut tie-wraps securing any wiring. The
indoor coil access panel will be used as the top of the damper
hood. Remove the screws along the sides and bottom of the
indoor coil access panel.
4. Carefully lift the hood assembly (with metal tray) through
the filter access opening and assemble per the steps outlined
in Economizer Hood and Two–Position Damper Hood, on
ECONOMIZER HOOD REMOVAL — FACTORY
OPTION (SIZE 16)
1. The hood is shipped in knock-down form and located in
the return air compartment. It is attached to the econo-
mizer using two plastic tie-wraps.
2. To gain access to the hood, remove the filter access panel
3. Locate and cut the (2) plastic tie-wraps being careful (see
Fig. 16). Be careful to not damage any wiring or cut tie-
wraps securing any wiring.
4. Carefully lift the hood assembly (with metal tray) through
the filter access opening and assemble per the steps outlined
in
Economizer Hood and Two–Position Hood, Size 16
, on
Fig. 14 — Typical Access Panel Locations
(Size 16 Shown)
Fig. 15 — Economizer and Two Position Damper Hood
Package Location
(Two Position Damper Only for Size 16)
Fig. 16 — Economizer Hood Package Location (Size 16)
FILTER ACCE
SS
PANEL
INDOOR COIL ACCESS PANEL
Hood Parts
Plastic Tie Wrap
Qty (2)
Screws for Metal Tray
Qty (2)
Economizer
Cut Plastic Ties
(2) Places
Remove Hood Parts
Summary of Contents for 580J*16D Series
Page 4: ...4 Fig 2 Unit Dimensional Drawing Sizes 08 09 and 12 ...
Page 5: ...5 Fig 2 Unit Dimensional Drawing Sizes 08 09 and 12 cont ...
Page 6: ...6 Fig 3 Unit Dimensional Drawing Size 14 ...
Page 7: ...7 Fig 3 Unit Dimensional Drawing Size 14 cont ...
Page 8: ...8 Fig 4 Unit Dimensional Drawing Size 16 ...
Page 9: ...9 Fig 4 Unit Dimensional Drawing Size 16 cont ...
Page 15: ...15 Fig 9 580J 16 Roof Curb Details ...
Page 32: ...32 Fig 58 580J 08 14 Typical Perfect Humidity Dehumidification System Humidistat Wiring ...
Page 33: ...33 Fig 59 580J 16 Typical Perfect Humidity Dehumidification System Humidistat Wiring ...
Page 48: ...48 Fig 67 580J 08 12N P Typical RTU Open System Control Wiring Diagram ...
Page 49: ...49 Fig 68 580J 08 14 Typical RTU Open System Control Wiring Diagram ...
Page 50: ...50 Fig 69 580J 16 Typical RTU Open System Control Wiring Diagram ...
Page 52: ...52 Fig 71 580J 16 Typical RTU Open System Control Wiring Diagram with Perfect Humidity System ...