70
PERFORMANCE DATA (cont)
GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES
1. Values include losses for filters, unit casing, and wet coils. See this
page for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that
the full range of the motor can be utilized with confidence. Using fan
motors up to the wattage ratings shown will not result in nuisance
tripping or premature motor failure. Unit warranty will not be
affected. See Evaporator-Fan Motor Performance table on page 73
for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your
Bryant representative for details.
4. Interpolation is permissible. Do not extrapolate. (Belt drive units
only.)
OUTDOOR SOUND POWER (Total Unit)
NOTE:
Indoor sound power is available in Bryant’s Electronic Catalog program (ECAT) for specific operating parameters.
ACCESSORY/FIOP ECONOMIZER IV AND ECONOMI$ER2 STATIC PRESSURE* (in. wg) — 580F036-073
LEGEND
*The static pressure must be added to external static pressure. The
sum and the evaporator entering-air cfm should be used in conjunction
with the Fan Performance tables to determine indoor blower rpm and
watts.
ACCESSORY/FIOP ECONOMISER IV AND ECONOMI$ER2 STATIC PRESSURE* (in. wg) — 580F090-151
LEGEND
*The static pressure must be added to external static pressure. The
sum and the evaporator entering-air cfm should then be used in con-
junction with the Fan Performance tables to determine blower rpm and
watts.
UNIT 580F
SOUND
RATING
60 Hz (dB)
A-WEIGHTED
(dB)
OCTAVE BANDS
63
125
250
500
1000
2000
4000
8000
036-072
81
80.5
56.8
75.8
72.4
72.9
74.8
75.4
71.3
69.1
073
80
80.0
59.1
68.9
68.7
71.9
74.0
68.9
65.7
59.0
090
87
86.4
83.2
87.4
83.5
82.8
83.0
77.7
71.8
67.0
091, 103
82
82.0
62.2
69.3
71.5
74.7
76.2
72.9
68.7
61.5
120
88
87.6
97.6
90.4
85.7
84.8
83.9
77.5
71.3
65.8
121
84
84.0
64.6
71.7
73.3
76.9
77.6
73.7
70.6
63.7
150
87
86.4
83.7
87.2
83.4
82.8
83.0
77.7
71.8
67.0
151
86
86.0
63.7
69.9
72.5
78.2
81.1
77.3
73.3
66.8
COMPONENT
CFM
1250
1500
1750
2000
2250
2500
2750
3000
Vertical EconoMi$er IV and EconoMi$er2
0.045
0.065
0.08
0.12
0.145
0.175
0.22
0.255
Horizontal EconoMi$er IV and EconoMi$er2
—
—
0.1
0.125
0.15
0.18
0.225
0.275
FIOP —
Factory-Installed Option
COMPONENT
CFM
2250
2500
2750
3000
3250
3500
3750
4000
4250
4500
4750
5000
5250
6250
Vertical EconoMi$er IV
and EconoMi$er2
0.06
0.075
0.09
0.115
0.13
0.15
0.17
0.195
0.22
0.25
0.285
0.325
0.36
—
Horizontal EconoMi$er IV
and EconoMi$er2
—
0.1
0.125
0.15
0.18
0.21
0.25
0.275
0.3
0.34
0.388
—
—
—
FIOP —
Factory-Installed Option
58
0F0
3
6
-15
1
Summary of Contents for 579F180
Page 26: ...26 BASE UNIT DIMENSIONS 580F036 072 a48 8195 580F036 151 ...
Page 27: ...27 BASE UNIT DIMENSIONS 580F073 a48 8196 580F036 151 ...
Page 28: ...28 BASE UNIT DIMENSIONS 580F090 120 150 a48 8197 580F036 151 ...
Page 29: ...29 BASE UNIT DIMENSIONS 580F091 103 121 151 a48 8198 580F036 151 ...
Page 87: ...87 BASE UNIT DIMENSIONS 581B036 072 a48 8199 581B036 150 ...
Page 89: ...89 ACCESSORY DIMENSIONS 581B036 072 a48 8201 581B036 150 ...
Page 90: ...90 ACCESSORY DIMENSIONS 581B090 150 a48 8202 581B036 150 ...
Page 135: ...135 TYPICAL WIRING SCHEMATICS 581B SIZES 036 150 581B090 460 3 60 Shown a48 8233 581B036 150 ...
Page 167: ...167 TYPICAL WIRING SCHEMATICS 579F 579F240 208 230 V Shown a48 7929 0TFQ004 012 579F180 300 ...
Page 174: ...174 BASE UNIT DIMENSIONS 580F180 210 a48 8203 0TFQ004 012 580F180 300 ...
Page 175: ...175 BASE UNIT DIMENSIONS 580F240 a48 8204 0TFQ004 012 580F180 300 ...
Page 176: ...176 BASE UNIT DIMENSIONS 580F300 a48 8205 0TFQ004 012 580F180 300 ...
Page 178: ...178 ACCESSORY DIMENSIONS 580F300 Vertical Roof Curbs 580F300 a48 7456 0TFQ004 012 580F180 300 ...
Page 202: ...202 BASE UNIT DIMENSIONS 581A210 300 a48 8206 581A155 300 ...
Page 206: ...206 ACCESSORY DIMENSIONS 581A210 300 a48 8234 581A155 300 ...