
251
GUIDE SPECIFICATIONS — 579F/580F180-300 AND 581A155,180 SIZE UNITS (cont)
4. All gas piping shall enter the unit at a single location.
5. Gas piping shall be capable of being routed through
the roof curb directly into unit.
G. Refrigerant Components:
Refrigerant circuit components shall include:
1. Thermostatic expansion valve (TXV).
2. Filter driers.
3. Gage port and connections on suction, discharge,
and liquid lines.
H. Filter Section:
Standard filter section shall consist of 2 sizes of factory-
installed 2-in. thick throwaway fiberglass filters of com-
mercially available sizes. Filters shall be approximately
10% efficient with an airside pressure drop of approxi-
mately 0.07 in. wg (clean).
I. Controls and Safeties:
1. Unit Controls:
a. Economizer control (optional).
b. Capacity control (2-step).
c. Unit shall be complete with self-contained low-
voltage control circuit.
J. Safeties:
a. Unit shall incorporate a solid-state compressor
lockout which provides reset capability at the
space thermostat, should any of the following
safety devices trip and shut off compressor:
1) Compressor lockout protection provided for
either internal or external overload.
2) Low-pressure switch.
3) Dual freezestats (evaporator coil).
4) High-pressure switch.
b. Supply-air thermostat shall be located in the unit.
c. Heating section shall be provided with the follow-
ing minimum protections:
1) High-temperature limit switch.
2) Induced-draft motor speed sensor.
3) Flame rollout switch.
4) Flame proving controls.
5) Redundant gas valve.
K. Operating Characteristics:
1. Unit shall be capable of starting and running at 120 F
ambient outdoor temperature per maximum load cri-
teria of ARI Standard 360.
2. Unit with standard controls will operate in cooling
down to an outdoor ambient temperature of 40 F.
3. Unit shall be provided with fan time delay to prevent
cold air delivery.
L. Electrical Requirements:
All unit power wiring shall enter unit cabinet at a single
location.
M. Motors:
1. Compressor motors shall be cooled by refrigerant
gas passing through motor windings and shall have
line break thermal and current overload protection.
2. All fan motors shall have permanently lubricated,
sealed bearings and inherent automatic-reset ther-
mal overload protection or manual reset calibrated
circuit breakers.
3. All indoor-fan motors 5 hp and larger shall meet the
minimum efficiency requirements as established by
the Energy Policy Act of 1992 (EPACT) effective
October 24, 1997.
N. Special Features:
Certain features are not applicable when the features
designated * are specified. For assistance in amending
the specifications, contact your local Bryant Sales Office.
1. Coils:
a. Optional pre-coated aluminum-fin coils shall have
a durable epoxy-phenolic coating to provide pro-
tection in mildly corrosive coastal environments.
Coating shall be applied to the aluminum fin stock
prior to the fin stamping process to create an inert
barrier between the aluminum fin and copper
tube. Epoxy-phenolic barrier shall minimize gal-
vanic action between dissimilar metals.
b. Optional copper-fin coils shall be constructed of
copper fins mechanically bonded to copper tubes
and copper tube sheets. Galvanized steel tube
sheets shall not be acceptable. A polymer strip
shall prevent coil assembly from contacting the
sheet metal coil pan to minimize potential for gal-
vanic corrosion between coil and pan. All copper
construction shall provide protection in moderate
coastal environments.
c. E-Coated aluminum-fin coils shall have a flexible
epoxy polymer coating uniformly applied to all coil
surface areas without material bridging between
fins. Coating process shall ensure complete coil
encapsulation. Color shall be high gloss black
with gloss — 60 deg of 65 to 90% per ASTM
D523-89. Uniform dry film thickness from 0.8 to
1.2 mil on all surface areas including fin edges.
Superior hardness characteristics of 2H per
ASTM D3363-92A and cross-hatch adhesion of
4B-5B per ASTM D3359-93. Impact resistance
shall be up to 160 in./lb (ASTM D2794-93).
Humidity and water immersion resistance shall be
up to minimum 1000 and 250 hours respectively
(ASTM D2247-92 and ASTM D870-92). Corro-
sion durability shall be confirmed through testing
to be no less than 1000 hours salt spray per
ASTM B117-90. Coil construction shall be alumi-
num fins mechanically bonded to copper tubes.
d. E-Coated copper-fin coils shall have a flexible
epoxy polymer coating uniformly applied to all coil
surface areas without material bridging between
fins. Coating process shall ensure complete coil
encapsulation. Color shall be high gloss black
with gloss — 60 deg of 65 to 90% per ASTM
D523-89. Uniform dry film thickness from 0.8 to
1.2 mil on all surface areas including fin edges.
Superior hardness characteristics of 2H per
ASTM D3363-92A and cross-hatch adhesion of
4B-5B per ASTM D3359-93. Impact resistance
shall be up to 160 in./lb (ASTM D2794-93).
Humidity and water immersion resistance shall be
up to minimum 1000 and 250 hours respectively
(ASTM D2247-92 and ASTM D870-92). Corro-
sion durability shall be confirmed through testing
to be no less than 1000 hours salt spray per
ASTM B117-90. Coil construction shall be copper
fins mechanically bonded to copper tubes with
copper tube sheets. Galvanized steel tube sheets
shall not be acceptable. A polymer strip shall pre-
vent coil assembly from contacting sheet metal
coil pan to maintain coating integrity and minimize
corrosion potential between coil and pan.
5
79F
/5
80F
/5
81A1
55-
30
0
Summary of Contents for 579F180
Page 26: ...26 BASE UNIT DIMENSIONS 580F036 072 a48 8195 580F036 151 ...
Page 27: ...27 BASE UNIT DIMENSIONS 580F073 a48 8196 580F036 151 ...
Page 28: ...28 BASE UNIT DIMENSIONS 580F090 120 150 a48 8197 580F036 151 ...
Page 29: ...29 BASE UNIT DIMENSIONS 580F091 103 121 151 a48 8198 580F036 151 ...
Page 87: ...87 BASE UNIT DIMENSIONS 581B036 072 a48 8199 581B036 150 ...
Page 89: ...89 ACCESSORY DIMENSIONS 581B036 072 a48 8201 581B036 150 ...
Page 90: ...90 ACCESSORY DIMENSIONS 581B090 150 a48 8202 581B036 150 ...
Page 135: ...135 TYPICAL WIRING SCHEMATICS 581B SIZES 036 150 581B090 460 3 60 Shown a48 8233 581B036 150 ...
Page 167: ...167 TYPICAL WIRING SCHEMATICS 579F 579F240 208 230 V Shown a48 7929 0TFQ004 012 579F180 300 ...
Page 174: ...174 BASE UNIT DIMENSIONS 580F180 210 a48 8203 0TFQ004 012 580F180 300 ...
Page 175: ...175 BASE UNIT DIMENSIONS 580F240 a48 8204 0TFQ004 012 580F180 300 ...
Page 176: ...176 BASE UNIT DIMENSIONS 580F300 a48 8205 0TFQ004 012 580F180 300 ...
Page 178: ...178 ACCESSORY DIMENSIONS 580F300 Vertical Roof Curbs 580F300 a48 7456 0TFQ004 012 580F180 300 ...
Page 202: ...202 BASE UNIT DIMENSIONS 581A210 300 a48 8206 581A155 300 ...
Page 206: ...206 ACCESSORY DIMENSIONS 581A210 300 a48 8234 581A155 300 ...