245
ELECTRICAL DATA — 581A (cont)
ELECTRICAL DATA — 581A210-300 WITHOUT CONVENIENCE OUTLET
LEGEND
*Fuse or HACR circuit breaker.
NOTES:
1.
In compliance with NEC requirements for multimotor and combination load equipment
(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be
fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percent of voltage imbalance.
% Voltage Imbalance
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
This amount of phase imbalance is satisfactory as it is below the maximum allowable
2%.
IMPORTANT
:
If the supply voltage phase imbalance is more than 2%, contact your local
electric utility company immediately.
UNIT
581A
NOMINAL
VOLTAGE
(3 Ph,
60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
IFM
POWER
EXHAUST
COMBUSTION
FAN MOTOR
POWER SUPPLY
DISCONNECT
SIZE
No. 1
No. 2
No. 3
Min
Max
RLA
LRA
RLA
LRA
RLA
LRA
Qty
Hp
FLA
(ea)
Hp
FLA
Qty
Hp
FLA
(ea)
FLA
MCA
MOCP*
FLA
210
208/230
187
253
16.7
130
16.7
130
22.4
184
4
0.25
1.5
3.7
10.6/ 9.6
—
—
—
0.5
78/ 77
100/ 90
83/ 82
2
1
5.9
90/ 89
100/100
97/ 96
5
16.7/15.2
—
—
—
84/ 83
100/100
90/ 89
2
1
5.9
96/ 94
100/100
104/102
7.5
24.2/22
—
—
—
92/ 89
100/100
99/ 96
2
1
5.9
104/101
125/110
112/110
460
414
506
9
70
9
70
10.7
90
4
0.25
0.7
3.7
4.8
—
—
—
0.3
39
45
42
2
1
3.1
45
50
49
5
7.6
—
—
—
42
50
45
2
1
3.1
48
50
52
7.5
11
—
—
—
45
50
49
2
1
3.1
51
60
56
575
518
633
7
55
7
55
9.3
73
4
0.25
0.7
3
3.9
—
—
—
0.24
32
40
35
2
1
2.4
37
45
40
5
6.1
—
—
—
35
40
37
2
1
2.4
39
45
43
7.5
9
—
—
—
37
45
40
2
1
2.4
42
50
46
240
208/230
187
253
22.4
184
22.4
184
22.4
184
4
0.25
1.5
3.7
10.6/ 9.6
—
—
—
0.5
89/ 88
100/100
96/ 95
2
1
5.9
101/100
110/110
110/109
5
16.7/15.2
—
—
—
96/ 94
100/100
103/102
2
1
5.9
107/106
125/125
117/115
7.5
24.2/22
—
—
—
103/101
125/110
112/109
2
1
5.9
115/113
125/125
126/123
10
30.8/28
—
—
—
112/108
125/125
120/116
2
1
5.9
124/120
150/125
133/130
460
414
506
10.7
90
10.7
90
10.7
90
4
0.25
0.7
3.7
4.8
—
—
—
0.3
42
50
46
2
1
3.1
49
50
53
5
7.6
—
—
—
45
50
49
2
1
3.1
51
60
56
7.5
11
—
—
—
49
50
53
2
1
3.1
55
60
60
10
14
—
—
—
52
60
56
2
1
3.1
59
60
63
575
518
633
9.3
73
9.3
73
9.3
73
4
0.25
0.7
5
6.1
—
—
—
0.24
39
45
42
2
1
2.4
44
50
48
7.5
9
—
—
—
42
50
46
2
1
2.4
47
50
51
10
11
—
—
—
44
50
48
2
1
2.4
49
60
53
300
208/230
187
253
47.1
245
47.1
245
—
—
6
0.25
1.5
5
16.7/15.2
—
—
—
0.5
132/130
175/175
138/136
2
1
5.9
143/142
175/175
151/150
7.5
24.2/22
—
—
—
139/137
175/175
147/144
2
1
5.9
151/149
175/175
160/158
10
30.8/28
—
—
—
146/143
175/175
154/151
2
1
5.9
158/155
200/200
168/164
460
414
506
19.6
125
19.6
125
—
—
6
0.25
0.7
5
7.6
—
—
—
0.3
56
60
59
2
1
3.1
62
80
66
7.5
11
—
—
—
59
60
63
2
1
3.1
66
80
70
10
14
—
—
—
62
80
66
2
1
3.1
69
80
73
575
518
633
15.8
100
15.8
100
—
—
6
0.25
0.7
5
6.1
—
—
—
0.24
46
60
48
2
1
2.4
51
60
54
7.5
9
—
—
—
49
60
52
2
1
2.4
54
60
57
10
11
—
—
—
51
60
54
2
1
2.4
56
60
59
FLA
—
Full Load Amps
MCA —
Minimum Circuit Amps
HACR —
Heating, Air Conditioning and
MOCP—
Maximum Overcurrent Protection
Refrigeration
NEC —
National Electrical Code
IFM
—
Indoor (Evaporator) Fan Motor
OFM —
Outdoor (Condenser) Fan Motor
LRA
—
Locked Rotor Amps
RLA
—
Rated Load Amps
MCA
—
Minimum Circuit Amps
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
=
457
% Voltage Imbalance = 100 x
7
457
= 1.53%
5
81A1
55-
30
0
Summary of Contents for 579F180
Page 26: ...26 BASE UNIT DIMENSIONS 580F036 072 a48 8195 580F036 151 ...
Page 27: ...27 BASE UNIT DIMENSIONS 580F073 a48 8196 580F036 151 ...
Page 28: ...28 BASE UNIT DIMENSIONS 580F090 120 150 a48 8197 580F036 151 ...
Page 29: ...29 BASE UNIT DIMENSIONS 580F091 103 121 151 a48 8198 580F036 151 ...
Page 87: ...87 BASE UNIT DIMENSIONS 581B036 072 a48 8199 581B036 150 ...
Page 89: ...89 ACCESSORY DIMENSIONS 581B036 072 a48 8201 581B036 150 ...
Page 90: ...90 ACCESSORY DIMENSIONS 581B090 150 a48 8202 581B036 150 ...
Page 135: ...135 TYPICAL WIRING SCHEMATICS 581B SIZES 036 150 581B090 460 3 60 Shown a48 8233 581B036 150 ...
Page 167: ...167 TYPICAL WIRING SCHEMATICS 579F 579F240 208 230 V Shown a48 7929 0TFQ004 012 579F180 300 ...
Page 174: ...174 BASE UNIT DIMENSIONS 580F180 210 a48 8203 0TFQ004 012 580F180 300 ...
Page 175: ...175 BASE UNIT DIMENSIONS 580F240 a48 8204 0TFQ004 012 580F180 300 ...
Page 176: ...176 BASE UNIT DIMENSIONS 580F300 a48 8205 0TFQ004 012 580F180 300 ...
Page 178: ...178 ACCESSORY DIMENSIONS 580F300 Vertical Roof Curbs 580F300 a48 7456 0TFQ004 012 580F180 300 ...
Page 202: ...202 BASE UNIT DIMENSIONS 581A210 300 a48 8206 581A155 300 ...
Page 206: ...206 ACCESSORY DIMENSIONS 581A210 300 a48 8234 581A155 300 ...