207
SELECTION PROCEDURE
I DETERMINE COOLING AND HEATING REQUIRE-
MENTS AT DESIGN CONDITIONS.
Given:
Required Gross Cooling
Capacity (TC) . . . . . . . . . . . . . . . . . . . . . 168,000 Btuh
Gross Sensible Heat
Capacity (SHC) . . . . . . . . . . . . . . . . . . . . 121,000 Btuh
Required Heating Capacity . . . . . . . . . . . . . 190,000 Btuh
Condenser Entering Air
Temperature . . . . . . . . . . . . . . . . . . . . . . . 95 F Summer
Indoor Air Temperature . . . . . . . . . . . .80 F edb, 67 F ewb
Evaporator Air Quantity . . . . . . . . . . . . . . . . . . . 6,000 cfm
External Static Pressure . . . . . . . . . . . . . . . . . 1.40 in. wg
Electrical Characteristics (V-Ph-Hz). . . . . . . . . . . 230-3-60
II SELECT UNIT BASED ON REQUIRED COOLING
CAPACITY.
Enter Cooling Capacities table for 581A180 at condenser
entering temperature of 95 F, evaporator air quantity of
6,000 cfm, and indoor air temperature of 67 F. The
581A180 unit will provide a total cooling capacity of
190,000 Btuh and a SHC of 136,000 Btuh. For evaporator
air temperatures other than 80 F, calculate SHC correction
using formula in notes under cooling capacity tables.
Unit meets design conditions for TC and SHC.
NOTE:
Unit ratings are gross capacities and do not
include the effect of indoor fan motor heat. To calculate net
capacities, see Step V.
III SELECT HEATING CAPACITY OF UNIT TO PROVIDE
DESIGN CONDITION REQUIREMENT.
In Heating Capacities and Efficiencies table, note that
581A180275 unit will provide 223,000 Btuh with an input
of 275,000 Btuh.
IV DETERMINE FAN SPEED AND POWER REQUIRE-
MENTS AT DESIGN CONDITIONS.
Before entering the Fan Performance tables, calculate the
total static pressure required based on unit components.
Tabulated fan performance includes filters and wet evapo-
rator coil. Refer to Accessory/FIOP Static Pressure table
for added pressure drops.
Calculate pressure drop:
Design External Static Pressure 1.40
EconoMi$er IV
0.07
1.47 in. wg (ESP)
Enter Fan Performance tables for 581A180 (low heat
units) at 6,000 cfm and 1.47 in. wg. The rpm is 1228 and
the Bhp is 4.73. The factory-installed 5 hp motor and alter-
nate high-static drive are sufficient for this operation.
V DETERMINE NET COOLING CAPACITIES.
Cooling capacities are gross capacities and do not include
indoor (evaporator) fan motor (IFM) heat. To determine
input power to the motor, enter the Fan Performance
tables for 581A180 (low heat units) at 6,000 cfm and
1.47 in. wg. Input watts to the motor are 4035.
Determine net cooling capacity and net sensible cooling
capacity using the following formulas:
IFM Heat
= Input Watts x 3.412 Btuh/Watt
= 4035 x 3.412
= 13,767 Btuh
Net Capacity
= Gross Capacity – IFM Heat
= 190,000 – 13,767
= 176,233 Btuh
Net Sensible Cap.
= Gross Sensible Cap. – IFM Heat
= 136,000 – 13,767
= 122,233 Btuh
The calculations show that a 581A180275 unit is the cor-
rect selection for the given conditions.
VI SELECT THE UNIT THAT CORRESPONDS TO POWER
SOURCE AVAILABLE.
The electrical data table shows that the 230-3-60 unit is
available.
5
81A1
55-
30
0
Summary of Contents for 579F180
Page 26: ...26 BASE UNIT DIMENSIONS 580F036 072 a48 8195 580F036 151 ...
Page 27: ...27 BASE UNIT DIMENSIONS 580F073 a48 8196 580F036 151 ...
Page 28: ...28 BASE UNIT DIMENSIONS 580F090 120 150 a48 8197 580F036 151 ...
Page 29: ...29 BASE UNIT DIMENSIONS 580F091 103 121 151 a48 8198 580F036 151 ...
Page 87: ...87 BASE UNIT DIMENSIONS 581B036 072 a48 8199 581B036 150 ...
Page 89: ...89 ACCESSORY DIMENSIONS 581B036 072 a48 8201 581B036 150 ...
Page 90: ...90 ACCESSORY DIMENSIONS 581B090 150 a48 8202 581B036 150 ...
Page 135: ...135 TYPICAL WIRING SCHEMATICS 581B SIZES 036 150 581B090 460 3 60 Shown a48 8233 581B036 150 ...
Page 167: ...167 TYPICAL WIRING SCHEMATICS 579F 579F240 208 230 V Shown a48 7929 0TFQ004 012 579F180 300 ...
Page 174: ...174 BASE UNIT DIMENSIONS 580F180 210 a48 8203 0TFQ004 012 580F180 300 ...
Page 175: ...175 BASE UNIT DIMENSIONS 580F240 a48 8204 0TFQ004 012 580F180 300 ...
Page 176: ...176 BASE UNIT DIMENSIONS 580F300 a48 8205 0TFQ004 012 580F180 300 ...
Page 178: ...178 ACCESSORY DIMENSIONS 580F300 Vertical Roof Curbs 580F300 a48 7456 0TFQ004 012 580F180 300 ...
Page 202: ...202 BASE UNIT DIMENSIONS 581A210 300 a48 8206 581A155 300 ...
Page 206: ...206 ACCESSORY DIMENSIONS 581A210 300 a48 8234 581A155 300 ...