13
ARI* CAPACITY RATINGS — 580F180-300
LEGEND
*Air Conditioning and Refrigeration Institute.
NOTES:
1. Rated in accordance with ARI Standards 360 and 270.
2. ARI ratings are net values, reflecting the effects of circulating fan
heat.
3. Ratings are based on:
Cooling Standard:
80 F db, 67 F wb indoor entering-air tempera-
ture and 95 F db air entering outdoor unit.
IPLV Standard:
80 F db, 67 F wb indoor entering-air temperature
and 80 F db outdoor entering-air temperature.
4. All 580F180-300 units are in compliance with ASHRAE 90.1-
1999 Energy Standard for minimum SEER and EER require-
ments. Refer to state and local codes or visit the following website:
http://solstice.crest.org/efficiency/bcap to determine if compliance
with this standard pertains to a given geographical area of the
United States.
HEATING CAPACITIES AND EFFICIENCIES — 580F180-300
*All units are 2-stage heat.
NOTE:
Minimum allowable temperature of mixed-air entering the heat exchanger during first-stage
heating is 45 F. There is no minimum mixed-air temperature limitation during second-stage heating.
For entering-air temperatures below 45 F both stages of heat must be energized together to minimize
condensation issues and ensure proper unit operation.
AIR QUANTITY LIMITS (Cooling)
COOLING OPERATION
LOW OUTDOOR TEMPERATURE OPERATING LIMITS (F)
UNIT SIZE
580F
(Low Heat)
NOMINAL
TONS
NET COOLING
CAPACITY (Btuh)
TOTAL
WATTS
EER
SOUND
RATING
(dB)
IPLV
180
15
176,000
17,064
9.5
88
9.5
210
18
202,000
21,166
9.7
88
10.2
240
20
236,000
24,832
9.5
94
10.1
300
25
278,000
28,535
9.7
94
10.4
UNIT SIZE
580F
(High Heat)
NOMINAL
TONS
NET COOLING
CAPACITY (Btuh)
TOTAL
WATTS
EER
SOUND
RATING
(dB)
IPLV
180
15
176,000
17,179
9.5
88
9.5
210
18
202,000
21,301
9.7
88
10.1
240
20
236,000
24,832
9.5
94
10.0
300
25
277,000
29,067
9.5
94
10.0
Bels —
Sound Levels (1 bel = 10 decibels)
db
—
Dry Bulb
EER —
Energy Efficiency Ratio
IPLV —
Integrated Part-Load Values
wb
—
Wet Bulb
UNIT
580F
HEATING INPUT
(Btuh)
Stage 2/Stage 1*
OUTPUT CAPACITY
(Btuh)
TEMPERATURE
RISE (F)
STEADY-STATE
EFFICIENCY (%)
MINIMUM
HEATING CFM
180275
275,000/206,000
223,000
15-45
81.0
3750
180360
360,000/270,000
292,000
20-50
81.0
3830
210275
275,000/206,000
223,000
15-45
81.0
4580
210360
360,000/270,000
292,000
20-50
81.0
5400
240275
275,000/206,000
223,000
15-45
81.0
4580
240360
360,000/270,000
292,000
20-50
81.0
5400
300275
275,000/206,000
223,000
15-45
81.0
4580
300360
360,000/270,000
292,000
20-50
81.0
5400
UNIT 580F
MINIMUM CFM
MAXIMUM CFM
180
4500
7,500
210
5400
9,000
240
6000
10,000
300
7000
11,250
UNITS
TEMPERATURE
All — Standard Unit
40
180 and 210 with Low Ambient Kit
10
240 and 300 with Low Ambient Kit
25
All with Motormaster® Head Pressure Control
–20
Summary of Contents for 579F180
Page 26: ...26 BASE UNIT DIMENSIONS 580F036 072 a48 8195 580F036 151 ...
Page 27: ...27 BASE UNIT DIMENSIONS 580F073 a48 8196 580F036 151 ...
Page 28: ...28 BASE UNIT DIMENSIONS 580F090 120 150 a48 8197 580F036 151 ...
Page 29: ...29 BASE UNIT DIMENSIONS 580F091 103 121 151 a48 8198 580F036 151 ...
Page 87: ...87 BASE UNIT DIMENSIONS 581B036 072 a48 8199 581B036 150 ...
Page 89: ...89 ACCESSORY DIMENSIONS 581B036 072 a48 8201 581B036 150 ...
Page 90: ...90 ACCESSORY DIMENSIONS 581B090 150 a48 8202 581B036 150 ...
Page 135: ...135 TYPICAL WIRING SCHEMATICS 581B SIZES 036 150 581B090 460 3 60 Shown a48 8233 581B036 150 ...
Page 167: ...167 TYPICAL WIRING SCHEMATICS 579F 579F240 208 230 V Shown a48 7929 0TFQ004 012 579F180 300 ...
Page 174: ...174 BASE UNIT DIMENSIONS 580F180 210 a48 8203 0TFQ004 012 580F180 300 ...
Page 175: ...175 BASE UNIT DIMENSIONS 580F240 a48 8204 0TFQ004 012 580F180 300 ...
Page 176: ...176 BASE UNIT DIMENSIONS 580F300 a48 8205 0TFQ004 012 580F180 300 ...
Page 178: ...178 ACCESSORY DIMENSIONS 580F300 Vertical Roof Curbs 580F300 a48 7456 0TFQ004 012 580F180 300 ...
Page 202: ...202 BASE UNIT DIMENSIONS 581A210 300 a48 8206 581A155 300 ...
Page 206: ...206 ACCESSORY DIMENSIONS 581A210 300 a48 8234 581A155 300 ...