Form No. PDS 580F.36.3
COMMERCIAL
SINGLE PACKAGE ROOFTOP UNITS
GAS HEATING/ELECTRIC COOLING UNITS
Standard efficiency units (580F072, 090, 120, 150 and
579F180-300) are available. Standard efficiency units
(580F036-060, 073, 091,103,121,151, and 180-300) that meet
ASHRAE 90.1-04 minimum energy efficiency requirements are
also available. High efficiency units (581B036-150 and
581A155-300) well exceed ASHRAE 90.1-04 energy efficiency
requirements and must comply with Energy Star high efficiency
requirements. Gas heating with electric cooling rooftops offer:
• Pre-painted galvanized steel cabinet for long life and quality
appearance
• Commercial strength base rails with built-in rigging capability
• Convertible design for vertical or horizontal supply/return
(036-151 and 210-300 only)
• Non-corrosive, sloped condensate drain pan, meets
ASHRAE 62 (IAQ)
• Two-inch return-air filters
• A wide assortment of factory-installed options available,
including high-static drives that provide additional perfor-
mance range
• Factory-installed optional gear driven EconoMi$er IV (vertical
return for sizes 036-151 only) for use with standard rooftop
unit controls (includes CO
2
sensor control capability)
• Factory-installed optional gear driven EconoMi$er2 (vertical
return only) for use with third party DDC controls (includes
4 to 20 mA actuator for demand control ventilation)
• Perfect Humidity™ dehumidification package (581B036-150
only)
• Hot gas reheat dehumidification package (581A181-300 only)
Heat Options
• Exclusive integrated gas control board with diagnostics
• Alumagard™ heat exchanger coating
• Induced-draft fan for gas combustion
• Tubular, dimpled heat exchangers
• Natural gas
• LP conversion kits
• Low NO
X
(size 036-060 only)
• Optional stainless steel heat exchangers.
FEATURES/BENEFITS
Every compact one-piece unit arrives fully assembled,
charged, tested, and ready to run.
GAS HEAT MODELS
— All ignition components are contained
in the compact IGC (integrated gas controller) which is easily
accessible for servicing. The IGC control board, designed and
manufactured exclusively for Bryant rooftop units, provides
built-in diagnostic capability. An LED (light-emitting diode) sim-
plifies troubleshooting by providing visual fault notification and
system status confirmation.
The IGC also contains an exclusive anti-cycle protection for
gas heat operation. After 4 continuous cycles on the unit high-
temperature limit switch, the gas heat operation is disabled,
and an error code is issued. This feature greatly improves reli-
ability of the rooftop unit.
The IGC also contains burner control logic for accurate and
dependable gas ignition. The LED is visible without removing
the unit control box access panel. This LED fault-notification
system reduces service person troubleshooting time and mini-
mizes service costs. The IGC also maximizes heating effi-
ciency by controlling evaporator-fan on and off delays.
Tubular, dimpled gas heat exchangers optimize heat transfer
for improved efficiency. The tubular design permits hot gases
to make multiple passes across the path of the supply air. The
dimpled design creates a turbulent gas flow to maximize heat-
ing efficiency.
580F, 579F, 581A/B
Dura
Pac
and
Dura
Pac
Plus Series
Sizes 036-300
3 to 25 Tons
SIZES 036-073
SIZES 090-151
579F180-216
581A155,180
580F180,210
580F240
579F240-300
580F300
581A210-300
48-910df
a48-8207
50-1242f
50-1214df
a48-5997
48-831df
Summary of Contents for 579F180
Page 26: ...26 BASE UNIT DIMENSIONS 580F036 072 a48 8195 580F036 151 ...
Page 27: ...27 BASE UNIT DIMENSIONS 580F073 a48 8196 580F036 151 ...
Page 28: ...28 BASE UNIT DIMENSIONS 580F090 120 150 a48 8197 580F036 151 ...
Page 29: ...29 BASE UNIT DIMENSIONS 580F091 103 121 151 a48 8198 580F036 151 ...
Page 87: ...87 BASE UNIT DIMENSIONS 581B036 072 a48 8199 581B036 150 ...
Page 89: ...89 ACCESSORY DIMENSIONS 581B036 072 a48 8201 581B036 150 ...
Page 90: ...90 ACCESSORY DIMENSIONS 581B090 150 a48 8202 581B036 150 ...
Page 135: ...135 TYPICAL WIRING SCHEMATICS 581B SIZES 036 150 581B090 460 3 60 Shown a48 8233 581B036 150 ...
Page 167: ...167 TYPICAL WIRING SCHEMATICS 579F 579F240 208 230 V Shown a48 7929 0TFQ004 012 579F180 300 ...
Page 174: ...174 BASE UNIT DIMENSIONS 580F180 210 a48 8203 0TFQ004 012 580F180 300 ...
Page 175: ...175 BASE UNIT DIMENSIONS 580F240 a48 8204 0TFQ004 012 580F180 300 ...
Page 176: ...176 BASE UNIT DIMENSIONS 580F300 a48 8205 0TFQ004 012 580F180 300 ...
Page 178: ...178 ACCESSORY DIMENSIONS 580F300 Vertical Roof Curbs 580F300 a48 7456 0TFQ004 012 580F180 300 ...
Page 202: ...202 BASE UNIT DIMENSIONS 581A210 300 a48 8206 581A155 300 ...
Page 206: ...206 ACCESSORY DIMENSIONS 581A210 300 a48 8234 581A155 300 ...