For any chimney or vent, this should include the following:

1. Inspection for any deterioration in chimney or vent. If

deterioration is discovered, chimney must be repaired or
vent must be replaced.

2. Inspection to ascertain that vent system is clear and free of

obstructions. Any blockage must be cleared before install-
ing furnace.

3. Cleaning chimney or vent if previously used for venting a

solid fuel burning appliance or fireplace.

4. Confirming that all unused chimney or vent connections are

properly sealed.

5. Verification that chimney is properly lined and sized per the

applicable codes. (Refer to list of codes in Safety Consid-
erations section.)

MASONRY CHIMNEYS

This furnace can be vented into an existing masonry chimney. This
furnace must not be vented into a chimney servicing a solid fuel
burning appliance. Before venting furnace into a chimney, the
chimney MUST be checked for deterioration and repaired if
necessary. The chimney must be properly lined and sized per local
or national codes.

If furnace is vented into a common chimney, the chimney must be
of sufficient area to accommodate the total flue products of all
appliances vented into chimney.

The following requirements are provided for a safe venting
system:

1. Be sure that chimney flue is clear of any dirt or debris.

2. Be sure that chimney is not servicing an open fireplace.

3. Never reduce pipe size below the outlet size of furnace.

(See Fig. 2.)

4. All pipe should be supported using proper clamps and/or

straps. These supports should be at least every 4 ft.

5. All horizontal runs of pipe should have at least 1/4 in. per

ft of upward slope.

6. All runs of pipe should be as short as possible with as few

turns as possible.

7. Seams should be tightly joined and checked for leaks.

8. The flue pipe must not extend into chimney but be flush

with inside wall.

9. The chimney must extend 3 ft above highest point where it

passes through the roof of a building and at least 2 ft higher
than any portion of a building within a horizontal distance
of 10 ft. It shall also be extended at least 5 ft above highest
connected equipment flue collar.

10. Check local codes for any variance.

FACTORY-BUILT CHIMNEYS

Listed factory-built chimneys may be used. Refer to chimney
manufacturer’s instructions for proper installation.

E.

Oil Burner

This furnace is supplied with a high-pressure atomizing retention
head-type burner (for use with grade 1 or 2 fuel oil). The Riello oil
burner operates with a prepurge period of 10 sec and a safety

timing of 5 sec. The burner flange is factory installed for an
inspection length of 3-3/4–in. The oil pump is set to operate on a
single line system. To operate on a two-line system the by-pass
plug must be installed.

F.

Oil Connections

CAUTION:

UNIT DAMAGE HAZARD

Failure to follow this caution may result in unit compo-
nent damage.
This burner is shipped with the oil pump set to operate on
single line system. To operate on a two-line system the
by-pass plug must be installed. Do not operate a single
line 
system with the by-pass plug installed. Operating a
single line system with the by-pass plug installed will
result in damage to the pump shaft seal.
Pump pressure must be set at time of burner start-up. A
pressure gauge is attached to the PRESSURE PORT for
pressure readings. Two PIPE CONNECTORS are sup-
plied with the burner for connection to either a single or
two-line system. Also supplied are two ADAPTORS,
two female 1/4–in. NPT, to adapt oil lines to burner pipe
connectors. All pump ports are British Parallel Thread
design. Direct connection of NPT threads to the pump
will damage the pump body.
Riello manometers and vacuum gauges do not require
any adapters and can be safely connected to the pump
ports. An NPT (metric) adapter must be used when
connecting other gauge models.

Complete instructions for installing fuel oil piping can be found in
oil burner Installation Instructions included with furnace.

Oil line entry holes are provided in side panels. Two holes are
provided in each location so that a 2-pipe system may be used if
desired.

An oil filter should be used with all oil burners and should be
installed as close to burner as possible.

G.

Barometric Draft Control

The barometric draft control shipped with furnace MUST be used
with furnace to ensure proper operation. Instructions for installing
control are packed with control.

H.

Electrical Connections

WARNING:

ELECTRICAL SHOCK AND FIRE

HAZARD
Failure to follow this warning could result in serious
injury, death, or property damage.
The unit cabinet must have an uninterrupted or unbroken
electrical ground to minimize personal injury if an
electrical fault should occur. A green ground screw is
provided in control box for this connection.

115-V WIRING

Before proceeding with electrical connections, make certain that
voltage, frequency, and phase correspond to that specified on unit

TABLE 7—ELECTRICAL DATA

UNIT

SIZE

VOLTS—
HERTZ—

PHASE—

OPERATING

VOLTAGE RANGE

MAX

UNIT

AMPS

MIN

WIRE

GAGE

MAX WIRE

LENGTH (FT)†

MAX FUSE OR

CKT BKR AMPS‡

Max*

Min*

036105

115—60—1

132

104

12.2

14

26

15

060120

115—60—1

132

104

15.7

12

26

20

* Permissible limits of voltage range at which unit will operate satisfactorily.
† Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
‡ Time-delay fuse is recommended.

—6—

Summary of Contents for 368RAN Series A

Page 1: ...INITY OF THIS OR ANY OTHER APPLIANCE DO NOT ATTEMPT TO START THE BURNER WHEN EXCESS OIL HAS ACCUMULATED WHEN THE FURNACE IS FULL OF VAPOR OR WHEN THE COMBUSTION CHAMBER IS VERY HOT WARNING CARBON MONO...

Page 2: ...esult in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injur...

Page 3: ...tion debris from all HVAC system components after construction is completed This furnace is approved for reduced clearances to combustible construction therefore it may be installed in a closet or sim...

Page 4: ...n and dilution of flue gases This determi nation must be made on an individual installation basis and must take into consideration the overall volume of unconfined space the number of windows and vent...

Page 5: ...and Air Conditioning Systems or Canadian equivalent The supply duct work should be attached to flanged front opening provided at discharge end of furnace The return air duct work should be attached to...

Page 6: ...tion length of 3 3 4 in The oil pump is set to operate on a single line system To operate on a two line system the by pass plug must be installed F Oil Connections CAUTION UNIT DAMAGE HAZARD Failure t...

Page 7: ...ply line is open 6 RESET BUTTON on primary control is pushed down 7 Flame observation door is closed 8 Thermostat is set for heating mode and set above room temperature If all of the above items have...

Page 8: ...Fig 3 Wiring Diagram A04182 8...

Page 9: ...Wiring with 1 Speed Air Conditioner Fig 5 24 VAC Oil Furnace Wiring with 2 Speed Air Conditioner A04184 A04185 Fig 6 24 VAC Oil Furnace Wiring with 1 Speed Heat Pump A04186 Fig 7 24 VAC Oil Furnace W...

Page 10: ...ic board ACCORDING TO OIL INPUT SELECTED AND A C SIZE See Tables 11A 11B and 11C or Tables 12A 12B and 12C WARNING FIRE HAZARD AND UNIT RELIABILITY Failure to follow this warning could result in prope...

Page 11: ...R1 JW6 R3 D20 D1 D3 D04 D02 D13 R13 JW2 JW3 JW7 LED7 GRN R14 R12 D17 D18 D19 D21 D15 D16 LED4 LED3 LED5 LED7 LED8 LED1 GRN GRN GRN GRN GRN GRN P3 Y Y Y2 G DH O W R C HSC 1 1168 83 1 NOTES 1 The Red LE...

Page 12: ...TURNED OFF IF BURNER IS SHUT DOWN FOR AN EXTENDED PERIOD OF TIME II OIL BURNER For optimum performance oil burner nozzle should be replaced once a year Contact your service technician if you are unsur...

Page 13: ...de with no 24 VAC input to DH the CFM STD is reduced by 15 COOLING MODE OR HEAT PUMP HEATING MODE 2 SPEED LOW 24 VAC INPUT R TO G Y1 AND O FOR COOLING SW2 COOL Dip Switch Position A C Size TON CFM STD...

Page 14: ...COOLING SW2 COOL Dip Switch Position A C Size TON CFM STD with SW3 ADJ Dip Switch A Position CFM HIGH with SW3 ADJ Dip Switch B Position CFM LOW with SW3 ADJ Dip Switch C Position A 1 OFF 2 OFF 5 0 9...

Page 15: ...oduct theory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom ServiceTraining plus hands on the products i...

Page 16: ...2004 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 16 Printed in U S A ii368r361 Catalog No 5336 800...

Reviews: