background image

LOCATION

I.

GENERAL

WARNING:

ELECTRICAL

SHOCK,

FIRE

OR

UNIT DAMAGE HAZARD
Failure to follow this warning could result in property
damage or personal injury or death.
This furnace is not water tight and is not designed for
outdoor installation. This furnace shall be installed in
such a manner as to protect electrical components from
water. Outdoor installation would lead to a hazardous
electrical condition and to premature furnace failure.

CAUTION:

UNIT DAMAGE HAZARD

This oil furnace may be used for construction heat provided that:
-The furnace operating conditions, including ignition, input rate, temperature rise and venting, are verified per instructions in this manual.
-The furnace is permanently installed with all electrical wiring, piping, venting and ducting installed according to these installation
instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This
prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion
products into the structure.
-The furnace is controlled by a thermostat. It may not be

hot wired

to provide heat continuously to the structure without thermostatic

control.
-Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction
materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace
components.
-The temperature of the return air to the furnace is no less than 55°F, with no evening setback or shutdown. The use of the furnace while
the structure is under construction is deemed to be intermittent operation per our installation instructions.
-The air temperature rise is within the rated rise range on the furnace rating plate, and the firing rate has been set to the nameplate value.
-The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to
occupancy.
-The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system
components after construction is completed.

This furnace is approved for reduced clearances to combustible
construction, therefore, it may be installed in a closet or similar
enclosure. It may be located in a basement or on the same level as
area to be heated. In any case, unit should always be installed level.

The required minimum clearances for this furnace are specified in
Table 1. The furnace should be located as close as possible to
chimney or vent in order to keep vent connections short and direct.

The furnace should also be located as near as possible to center of
air distribution system.

II.

LOCATION RELATIVE TO COOLING EQUIPMENT

When installing furnace with cooling equipment for year-round
operation, the following recommendations must be followed for
series or parallel airflow:

1. In series airflow applications, coil is mounted after furnace

in an enclosure in supply-air stream. The furnace blower
used for both heating and cooling airflow.

WARNING:

UNIT DAMAGE HAZARD

The coil MUST be installed on air discharge side of
furnace. Under no circumstances should airflow be such
that cooled, conditioned air can pass over furnace heat
exchanger. This will cause condensation in heat ex-
changer and possible failure of heat exchanger which
could lead to a fire hazard and/or a hazardous condition
which may lead to bodily harm. Heat exchanger failure
due to improper installation may not be covered by
warranty.

2. In parallel airflow applications, dampers must be provided

to direct air over furnace heat exchanger when heat is
desired and over cooling coil when cooling is desired.

IMPORTANT:

The dampers should be adequate to prevent

cooled air from entering furnace. If manually operated, dampers
must be equipped with a means to prevent operation of either
cooling unit or furnace unless damper is in full cool or heat
position.

TABLE 1—MINIMUM CLEARANCES TO

COMBUSTIBLE MATERIALS (IN.)

UNIT APPLICATION

LOW-BOY

Sides

Furnace

1

Supply Plenum and Warm-Air Duct Within 6 ft
of Furnace

1

Back

Service Clearance

19

Top

Furnace Casing or Plenum

2

Horizontal Warm-Air Duct Within 6 ft of
Furnace

2

Bottom*

0

Flue
Pipe

Horizontally or Below Pipe

4

Vertically Above Pipe

9

Front

8

* Floor may be combustible.
NOTE: Adequate service clearances should be provided over and above these
dimensions as required.

—3—

Summary of Contents for 368RAN Series A

Page 1: ...INITY OF THIS OR ANY OTHER APPLIANCE DO NOT ATTEMPT TO START THE BURNER WHEN EXCESS OIL HAS ACCUMULATED WHEN THE FURNACE IS FULL OF VAPOR OR WHEN THE COMBUSTION CHAMBER IS VERY HOT WARNING CARBON MONO...

Page 2: ...esult in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injur...

Page 3: ...tion debris from all HVAC system components after construction is completed This furnace is approved for reduced clearances to combustible construction therefore it may be installed in a closet or sim...

Page 4: ...n and dilution of flue gases This determi nation must be made on an individual installation basis and must take into consideration the overall volume of unconfined space the number of windows and vent...

Page 5: ...and Air Conditioning Systems or Canadian equivalent The supply duct work should be attached to flanged front opening provided at discharge end of furnace The return air duct work should be attached to...

Page 6: ...tion length of 3 3 4 in The oil pump is set to operate on a single line system To operate on a two line system the by pass plug must be installed F Oil Connections CAUTION UNIT DAMAGE HAZARD Failure t...

Page 7: ...ply line is open 6 RESET BUTTON on primary control is pushed down 7 Flame observation door is closed 8 Thermostat is set for heating mode and set above room temperature If all of the above items have...

Page 8: ...Fig 3 Wiring Diagram A04182 8...

Page 9: ...Wiring with 1 Speed Air Conditioner Fig 5 24 VAC Oil Furnace Wiring with 2 Speed Air Conditioner A04184 A04185 Fig 6 24 VAC Oil Furnace Wiring with 1 Speed Heat Pump A04186 Fig 7 24 VAC Oil Furnace W...

Page 10: ...ic board ACCORDING TO OIL INPUT SELECTED AND A C SIZE See Tables 11A 11B and 11C or Tables 12A 12B and 12C WARNING FIRE HAZARD AND UNIT RELIABILITY Failure to follow this warning could result in prope...

Page 11: ...R1 JW6 R3 D20 D1 D3 D04 D02 D13 R13 JW2 JW3 JW7 LED7 GRN R14 R12 D17 D18 D19 D21 D15 D16 LED4 LED3 LED5 LED7 LED8 LED1 GRN GRN GRN GRN GRN GRN P3 Y Y Y2 G DH O W R C HSC 1 1168 83 1 NOTES 1 The Red LE...

Page 12: ...TURNED OFF IF BURNER IS SHUT DOWN FOR AN EXTENDED PERIOD OF TIME II OIL BURNER For optimum performance oil burner nozzle should be replaced once a year Contact your service technician if you are unsur...

Page 13: ...de with no 24 VAC input to DH the CFM STD is reduced by 15 COOLING MODE OR HEAT PUMP HEATING MODE 2 SPEED LOW 24 VAC INPUT R TO G Y1 AND O FOR COOLING SW2 COOL Dip Switch Position A C Size TON CFM STD...

Page 14: ...COOLING SW2 COOL Dip Switch Position A C Size TON CFM STD with SW3 ADJ Dip Switch A Position CFM HIGH with SW3 ADJ Dip Switch B Position CFM LOW with SW3 ADJ Dip Switch C Position A 1 OFF 2 OFF 5 0 9...

Page 15: ...oduct theory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom ServiceTraining plus hands on the products i...

Page 16: ...2004 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 16 Printed in U S A ii368r361 Catalog No 5336 800...

Reviews: