Follow these examples to determine cooling and continuous fan airflows:
Example 1
Model No.
333BAV060120AAJA
060---2000 CFM Blower Drive Package
Single-Speed Cooling Unit
If you select:
COOL SIZE
(YEL WIRE)
COOL CFM/TON
(BLU WIRE)
AC HP
(ORN WIRE)
CONTINUOUS FAN
CFM (GRN WIRE)
HI
400
AC
HI
You selected HI (5 ton) maximum blower capacity of furnace model, 400 CFM/TON of cooling CFM, AC setting for air conditioner,
and HI continuous fan setting for 100% of cool size and cool CFM/TON airflow CFM for continuous fan operation.
Cooling Air Flow = (5 X 400) = 2000 CFM
Continuous Fan = (5 X 400) X 100% = 2000 CFM
Example 2
Model No.
333BAV060120AAJA
060---2000 CFM Blower Drive Package
Single-Speed Cooling Unit
If you select:
COOL SIZE
(YEL WIRE)
COOL CFM/TON
(BLU WIRE)
AC HP
(ORN WIRE)
CONTINUOUS FAN
CFM (GRN WIRE)
HI
400
HP CMFT
MED
You selected HI (5 ton) maximum blower capacity of furnace model, 400 CFM/TON of cooling CFM, HP CMFT for 90% of selected
cool size and cool CFM/TON airflow CFM settings for heat pump heating operation, and 100% of selected cool size and cool CFM/TON
airflow CFM settings for cooling operation, and MED continuous fan setting for 65% of cooling airflow CFM for continuous fan
operation.
Heat Pump Heating Air Flow = (5 X 400) X 90% = 1800 CFM
Heat Pump Cooling Air Flow = (5 X 400) X 100% = 2000 CFM
Continuous Fan = (5 X 400) X 65% = 1300 CFM
Example 3
Model No.
333BAV060120AAJA
060---2000 CFM Blower Drive Package
2-Speed Cooling Unit
If you select:
COOL SIZE
(YEL WIRE)
COOL CFM/TON
(BLU WIRE)
AC HP
(ORN WIRE)
CONTINUOUS FAN
CFM (GRN WIRE)
M-LO
350
AC
LO
You selected M-LO (3.5 ton) of blower capacity of furnace model, 350 CFM/TON of cooling CFM, AC setting for air conditioner, and
LO continuous fan setting for 50% of single-speed cooling airflow CFM for continuous fan operation.
Low Cooling Airflow = (3.5 X 350) X 65% = 796 CFM
High Cooling Air Flow = (3.5 X 350) X 105% = 1286 CFM
Continuous Fan = (3.5 X 350) X 50% = 612 CFM—NOTE: This is less than 700 CFM minimum airflow. Furnace will run
Continuous Fan at 700 CFM. (See Table 4.)
—35—