Fig. 6—EZ-SELECT Airflow Control
COOL
CFM
PER
TON
BLU
AC
HP
ORN
GAS
HEAT
TEMP
RISE
RED
HI
MED
LO
MID
M-HI
HI
HP
AC
HI
BLU
HSCI
1081-83-38
YYWW
ICM2+
AIRFLOW SELECTOR
K1
RED
R1
Q1
R2
R3
D6
D7
A
B
C
D
GRN
D8
D5
D11
D10
P12
D4
D3
D9
D1
D2
400
350
315
M-HI
M-LO
LO
HP
EFFY
CMFT
CONTINUOUS FAN
CFM
GRN
A95362
COOL
YEL
S
I
Z
E
P12 is the main plug connection and is
depicted as PL7 on wiring schematic.
3 Ton Drive
HI - 3 Ton
M-HI - 2.5 Ton
M-LO - 2 Ton
LO - 1.5 Ton
4 Ton Drive
HI - 4 Ton
M-HI - 3.5 Ton
M-LO - 3 Ton
LO - 2.5 Ton
5 Ton Drive
HI - 5 Ton
M-HI - 4 Ton
M-LO - 3.5 Ton
LO - 3 Ton
Yellow Wire from blower harness is for Cool
Size selection. It is used to select airflow to match
the needed tons for cooling or heat pump system.
This setting works in conjunction with
Blue and Orange jumper.
Violet Wire from blower wire harness
is factory connected to PIN A, B, C, or D on
EZ-SELECT airflow control. The PIN selection
can be verified by checking the PIN marking
in lower right-hand of furnace rating plate.
Blue Wire is called the CFM/TON jumper. It is
used to select a slight adjustment to cooling
airflow. The traditional airflow value is
400 CFM/TON. The 350 CFM/TON setting is for
best efficiency with our units.
The 315 CFM/TON setting is used for improved
dehumidification and/or with undersized
ductwork. This setting works in conjunction
with Yellow and Orange jumper.
Orange Wire from blower harness is called
the AC/HP jumper. It Is used to select
cooling-only AC, heat pump efficiency HP EFFY,
or heat pump comfort HP CMFT. HP EFFY
provides the same heating airflow used for
cooling. HP CMFT reduces heating airflow to
90% of cooling airflow.
Red Wire is called the GAS HEAT TEMP RISE
jumper. It is used to select gas heating air
temperature rise. The selections are MID for
midpoint of temperature rise range stated
on rating plate, HI for high end of rise range,
and M-HI which is about half way between MID
and HI. This jumper selects the rise for both
low- and high-heat.
Green Wire is called the CONTINUOUS FAN CFM
jumper. It is used to select continuous fan
airflow CFM. The selections are LO for 50% of
cooling airflow, MED for 65% of cooling airflow,
and HI for 100% of cooling airflow.
—33—