background image

WARNING:

The cabinet MUST have an uninterrupted

or unbroken ground according to NEC ANSI/NFPA
70-1996 and Canadian Electrical Code, CSA C22.1 or
local codes to minimize personal injury if an electrical
fault should occur. This may consist of electrical wire or
conduit approved for electrical ground when installed in
accordance with existing electrical codes. Do not use gas
piping as an electrical ground.

The junction box can be moved to left-hand side of furnace when
a left-hand side power supply is desired. Remove 2 screws holding
junction box. Mount junction box on left-hand side of furnace. The
blower door interlock switch must also be moved to left-hand side
of furnace due to length of wiring harness. (Holes have been
provided in casing). When moved, tuck wiring harness behind clip
provided to keep extra wire lengths out of the way.

NOTE:

Proper polarity must be maintained for 115-v wiring. If

polarity is incorrect, the furnace control status LED will flash
rapidly and prevent heating operation.

B.

24-v Wiring

Refer to ESD Precautions Procedure before proceeding with 24-v
connections.

Make field 24-v connections at 24-v terminal block. (See Fig. 11.)
Connect terminal Y/Y2 as shown in Fig. 9 or 10 for proper cooling
operation. Use only AWG No. 18 or larger, color-coded copper
thermostat wire.

The 24-v circuit contains an automotive-type, 3-amp fuse located
on main control. Any 24-v electrical shorts during installation,
service, or maintenance could cause this fuse to blow. If fuse
replacement is required, use ONLY a 3-amp fuse. The control will
flash code 24 when fuse needs replacement.

C.

Accessories

1. Electronic air cleaner (EAC)

A terminal block (EAC-1 [hot] and EAC-2 [neutral]) is
provided for EAC connection. (See Fig. 11.) The terminals
are energized with 115v, 1-amp maximum during blower
motor operation.

2. Humidifier (HUM)

TABLE 5—ELECTRICAL DATA

UNIT SIZE

VOLTS—
HERTZ—

PHASE

OPERATING

VOLTAGE RANGE

MAX

UNIT

AMPS

MIN

WIRE

GAGE

MAX WIRE

LENGTH (FT)‡

MAX FUSE OR

HACR-TYPE

CKT BKR AMPS†

Max*

Min*

036040

115—60—1

127

104

11.4

14

32

15

024060

115—60—1

127

104

8.2

14

45

15

036060

115—60—1

127

104

10.6

14

34

15

042080

115—60—1

127

104

11.7

14

31

15

048080

115—60—1

127

104

13.4

14

27

15

036100

115—60—1

127

104

10.5

14

35

15

048100

115—60—1

127

104

13.2

14

28

15

060100

115—60—1

127

104

17.7

12

32

20

048120

115—60—1

127

104

13.2

14

28

15

060120

115—60—1

127

104

18.2

12

31

20

060135

115—60—1

127

104

17.4

12

33

20

* Permissible limits of the voltage range at which the unit will operate satisfactorily.
† Time-delay fuse is recommended.
‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.

Fig. 9—Heating and Cooling Application Wiring Diagram 1-Stage Thermostat and Condensing Unit

A97443

115-VOLT FUSED

DISCONNECT

SWITCH

(WHEN REQUIRED)   

JUNCTION
BOX   

CONTROL

BOX

24-VOLT

TERMINAL

BLOCK  

TWO-WIRE

HEATING-

ONLY   

FIVE

WIRE

   

1-STAGE THERMOSTAT TERMINALS

FIELD-SUPPLIED

FUSED DISCONNECT

CONDENSING

UNIT   

FURNACE

COM

R

W

Y

R

G

C

GND   

GND   

FIELD 24-VOLT WIRING
FIELD 115-, 208/230-, 460-VOLT WIRING
FACTORY 24-VOLT WIRING
FACTORY 115-VOLT WIRING   

208/230- OR
460-VOLT
THREE
PHASE   

208/230-
VOLT
SINGLE
PHASE   

WHT   

BLK   

WHT   

BLK   

W/W1

W2

Y/Y2

G

NOTES: 

  

1.  Connect Y-terminal as shown for proper operation.

                2.  Some thermostats require a "C" terminal connection as shown.

3.  If any of the original wire, as supplied, must be replaced,
     use same type or equivalent wire.

—8—

Summary of Contents for 330AAV B Series

Page 1: ...vailable during start up and adjustment procedures and service calls Recognize safety information This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals...

Page 2: ...mbustible wood flooring in alcoves attics TABLE 1 DIMENSIONS IN UNIT SIZE A D E FLUE COLLAR SHIP WT 036040 14 3 16 12 9 16 12 11 16 4 124 024060 14 3 16 12 9 16 12 11 16 4 132 036060 14 3 16 12 9 16 1...

Page 3: ...justment alter ation service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qua...

Page 4: ...accordance with NSCNGPIC and all authorities having jurisdiction CAUTION Air for combustion must not be contami nated by halogen compounds which include fluoride chloride bromide and iodide These ele...

Page 5: ...onal injury or death III FILTER ARRANGEMENT The factory supplied filter s is shipped in the blower compart ment Determine location for filter and move filter retaining hardware if necessary before att...

Page 6: ...with national and local codes Refer to the NFGC NFPA 54 1996 ANSI Z223 1 1996 Canadian installations must be installed in accordance with NSC NGPIC and all authorities having jurisdiction The gas sup...

Page 7: ...RNING Use the proper length of pipes to avoid stress on the gas control manifold A failure to follow this warning can cause a gas leak resulting in a fire explosion personal injury or death CAUTION Us...

Page 8: ...Accessories 1 Electronic air cleaner EAC A terminal block EAC 1 hot and EAC 2 neutral is provided for EAC connection See Fig 11 The terminals are energized with 115v 1 amp maximum during blower motor...

Page 9: ...ition at end of furnace installation This overrides built in control process for selecting high and low fire and allows the 2 stage thermostat to select gas heating modes The W2 from thermostat must b...

Page 10: ...e low heat gas valve solenoid GV permits gas flow to the burners where it is ignited After 5 sec the ignitor HSI is de energized and a 2 sec flame proving period begins If high heat gas valve solenoid...

Page 11: ...e start up and shutdown functions and delays described in item 1 above apply to 2 stage heating mode as well except for switching from low to high gas heat and vice versa a Switching from low to high...

Page 12: ...itches ALS1 2 used on some horizontal and some downflow models 7 This wire must be connected to furnace sheet metal for control to prove flame 8 Factory connected when LGPS not used RED LS FRS2 RED RE...

Page 13: ...d Y Y2 circuits start the fur nace blower motor BLWM on high cool speed NOTE The furnace control CPU controls blower motor BLWM speed by sensing only G for low cool speed and Y2 for high cool speed 2...

Page 14: ...9 NOTE For Canada altitudes of 2000 to 4500 ft use U S A altitudes of 2001 to 3000 ft in Table 9 e Find closest natural gas heat value and specific gravity in Table 9 f Follow heat value and specific...

Page 15: ...f the furnace input rate NOTE Measured gas inputs high heat and low heat must be within 2 percent of that stated on furnace rating plate when installed at sea level or derated per that stated above wh...

Page 16: ...3 6 1 5 44 3 8 1 6 43 3 4 1 4 43 3 5 1 5 43 3 6 1 5 2001 825 44 3 4 1 4 44 3 5 1 5 44 3 7 1 5 44 3 8 1 6 43 3 4 1 4 to 850 44 3 2 1 4 44 3 3 1 4 44 3 4 1 5 44 3 6 1 5 44 3 7 1 5 3000 875 45 3 7 1 6 4...

Page 17: ...4 750 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 775 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 5001 800 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 825 48 3 8 1 6...

Page 18: ...Pressure High Low U S A Only 600 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 625 47 3 7 1 6 45 3 2 1 4 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 8001 650 47 3 4 1 4 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3...

Page 19: ...ment Return SW 2 to final de sired location after completing the reading See thermo stat manufacturer s instructions for adjusting heat antici pator TABLE 10 GAS RATE CU FT HR SECONDS FOR 1 REVOLUTION...

Page 20: ...Wait 5 minutes and then reset draft safeguard switch 3 Check flow sensing pressure switches This control proves operation of draft inducer blower a Turn off 115 v power to furnace b Remove gas control...

Reviews: