background image

a. Calculate high-altitude adjustment (if required).

UNITED STATES
At altitudes above 2000 ft, this furnace has been ap-
proved for a 4 percent derate for each 1000 ft above sea
level. See Table 8 for derate multiplier factor and
example.

EXAMPLE:
85,000 Btuh input furnace installed at 4300 ft.

Furnace Input

Rate at

Sea Level

X

Derate

Multiplier

Factor

=

Furnace Input Rate

at Installation

Altitude

85,000

X

0.82

=

69,700

CANADA
At installation altitudes from 2000 to 4500 ft, this
furnace must be derated 10 percent by an authorized Gas
Conversion Station or Dealer. To determine correct input
rate for altitude, see example above and use 0.82 as
derate multiplier factor.

b. Check that gas valve adjustment caps are in place for

proper input to be clocked.

c. Obtain yearly heat value average for local gas supply.

NOTE:

Be sure heating value of gas used for calculations is

correct for your altitude. Consult local gas utility for altitude
adjustment of gas heating value.

d. Check and verify orifice size in furnace. NEVER AS-

SUME THE ORIFICE SIZE. ALWAYS CHECK AND
VERIFY.

e. Turn off all other gas appliances and pilots.

f. Move setup switch SW-2 to ON position. (See Fig. 12.)

This keeps furnace locked in low-heat operation.

g. Jumper R to W/W1.

h. Let furnace run for 3 minutes in low-heat operation.

i. Measure time (in sec) for gas meter to complete 1

revolution. Note reading.

j. Refer to Table 10 for cubic ft of gas per hr.

k. Multiply gas rate cu ft/hr by heating value (Btu/cu ft).

l. Move setup switch SW-2 to OFF position and jumper R

and W2 thermostat connections. (See Fig. 12.) This keeps
furnace locked in high-heat operation. Repeat items h
through k for high-heat operation.

EXAMPLE: (High-heat operation at 0—2000 ft altitude)
Furnace input from rating plate is 85,000 Btuh
Btu heating input = Btu/cu ft X cu ft/hr
Heating value of gas = 1050 Btu/cu ft
Time for 1 revolution of 2-cu ft dial = 92 sec
Gas rate = 80 cu ft/hr (from Table 10)
Btu heating input = 80 X 1050 = 84,000 Btuh In this
example, the orifice size and manifold pressure adjustment
is within

±

2 percent of the furnace input rate.

NOTE:

Measured gas inputs (high heat and low heat) must be

within

±

2 percent of that stated on furnace rating plate when

installed at sea level or derated per that stated above when installed
at higher altitudes.

m. Remove jumper across R, W/W1, and W2 thermostat

connections to terminate call for heat.

5. Set temperature rise.

Place SW-2 in ON position. Jumper R to W/W1 and W2 to
check high-gas-heat temperature rise. To check low-gas-
heat temperature rise, remove jumper to W2. Determine air
temperature rise for both high and low fire. Do not exceed
temperature rise ranges specified on unit rating plate for
high and low fire.
a. Place duct thermometers in return and supply ducts as

near furnace as possible. Be sure thermometers do not
see heat exchangers so that radiant heat will not affect
thermometer readings. This is particularly important
with straight run ducts.

b. When thermometer readings stabilize, subtract return-air

temperature from supply-air temperature to determine
temperature rise.

NOTE:

If the temperature rise is outside this range, first check:

(1.) Gas input for low- and high-fire operation.

(2.) Derate for altitude if applicable.

(3.) Return and supply ducts for excessive restrictions

causing static pressures greater than 0.50-in. wc.

c. Adjust air temperature rise by adjusting blower speed.

Increase blower speed to reduce temperature rise. De-
crease blower speed to increase temperature rise. For
high fire, speed selection can be med-high, med (5-speed
blowers only), or med-low (factory setting). For low fire,
speed selection can be low (factory setting), med-low, or
med (5-speed blowers only).

CAUTION:

DO NOT redrill orifices. Improper drilling

(burrs, out-of-round holes, etc.) can cause excessive
burner noise and misdirection of burner flames. This can
result in flame impingement of burners and heat exchang-
ers, causing failures.

A93059

BURNER 

ORIFICE

TABLE 8—ALTITUDE DERATE MULTIPLIER FOR U.S.A.

ALTITUDE

(FT)

% OF

DERATE

DERATE MULTIPLIER

FACTOR FOR U.S.A.*

0—2000

0

1.00

2001—3000

8—12

0.90

3001—4000

12—16

0.86

4001—5000

16—20

0.82

5001—6000

20—24

0.78

6001—7000

24—28

0.74

7001—8000

18—32

0.70

8001—9000

32—36

0.66

9001—10,000

36—40

0.62

* Derate multiplier factor is based on midpoint altitude for altitude range.

—15—

Summary of Contents for 330AAV B Series

Page 1: ...vailable during start up and adjustment procedures and service calls Recognize safety information This is the safety alert symbol When you see this symbol on the furnace and in instructions or manuals...

Page 2: ...mbustible wood flooring in alcoves attics TABLE 1 DIMENSIONS IN UNIT SIZE A D E FLUE COLLAR SHIP WT 036040 14 3 16 12 9 16 12 11 16 4 124 024060 14 3 16 12 9 16 12 11 16 4 132 036060 14 3 16 12 9 16 1...

Page 3: ...justment alter ation service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions which may cause personal injury or property damage Consult a qua...

Page 4: ...accordance with NSCNGPIC and all authorities having jurisdiction CAUTION Air for combustion must not be contami nated by halogen compounds which include fluoride chloride bromide and iodide These ele...

Page 5: ...onal injury or death III FILTER ARRANGEMENT The factory supplied filter s is shipped in the blower compart ment Determine location for filter and move filter retaining hardware if necessary before att...

Page 6: ...with national and local codes Refer to the NFGC NFPA 54 1996 ANSI Z223 1 1996 Canadian installations must be installed in accordance with NSC NGPIC and all authorities having jurisdiction The gas sup...

Page 7: ...RNING Use the proper length of pipes to avoid stress on the gas control manifold A failure to follow this warning can cause a gas leak resulting in a fire explosion personal injury or death CAUTION Us...

Page 8: ...Accessories 1 Electronic air cleaner EAC A terminal block EAC 1 hot and EAC 2 neutral is provided for EAC connection See Fig 11 The terminals are energized with 115v 1 amp maximum during blower motor...

Page 9: ...ition at end of furnace installation This overrides built in control process for selecting high and low fire and allows the 2 stage thermostat to select gas heating modes The W2 from thermostat must b...

Page 10: ...e low heat gas valve solenoid GV permits gas flow to the burners where it is ignited After 5 sec the ignitor HSI is de energized and a 2 sec flame proving period begins If high heat gas valve solenoid...

Page 11: ...e start up and shutdown functions and delays described in item 1 above apply to 2 stage heating mode as well except for switching from low to high gas heat and vice versa a Switching from low to high...

Page 12: ...itches ALS1 2 used on some horizontal and some downflow models 7 This wire must be connected to furnace sheet metal for control to prove flame 8 Factory connected when LGPS not used RED LS FRS2 RED RE...

Page 13: ...d Y Y2 circuits start the fur nace blower motor BLWM on high cool speed NOTE The furnace control CPU controls blower motor BLWM speed by sensing only G for low cool speed and Y2 for high cool speed 2...

Page 14: ...9 NOTE For Canada altitudes of 2000 to 4500 ft use U S A altitudes of 2001 to 3000 ft in Table 9 e Find closest natural gas heat value and specific gravity in Table 9 f Follow heat value and specific...

Page 15: ...f the furnace input rate NOTE Measured gas inputs high heat and low heat must be within 2 percent of that stated on furnace rating plate when installed at sea level or derated per that stated above wh...

Page 16: ...3 6 1 5 44 3 8 1 6 43 3 4 1 4 43 3 5 1 5 43 3 6 1 5 2001 825 44 3 4 1 4 44 3 5 1 5 44 3 7 1 5 44 3 8 1 6 43 3 4 1 4 to 850 44 3 2 1 4 44 3 3 1 4 44 3 4 1 5 44 3 6 1 5 44 3 7 1 5 3000 875 45 3 7 1 6 4...

Page 17: ...4 750 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 775 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 5001 800 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3 45 3 3 1 4 45 3 4 1 4 825 48 3 8 1 6...

Page 18: ...Pressure High Low U S A Only 600 45 3 4 1 4 45 3 5 1 5 45 3 6 1 5 45 3 7 1 6 45 3 8 1 6 625 47 3 7 1 6 45 3 2 1 4 45 3 3 1 4 45 3 4 1 4 45 3 5 1 5 8001 650 47 3 4 1 4 47 3 5 1 5 47 3 6 1 5 45 3 2 1 3...

Page 19: ...ment Return SW 2 to final de sired location after completing the reading See thermo stat manufacturer s instructions for adjusting heat antici pator TABLE 10 GAS RATE CU FT HR SECONDS FOR 1 REVOLUTION...

Page 20: ...Wait 5 minutes and then reset draft safeguard switch 3 Check flow sensing pressure switches This control proves operation of draft inducer blower a Turn off 115 v power to furnace b Remove gas control...

Reviews: