Section 1
GT1600 Alarm Contact (Reed Switch) Meter Size 7 to 10
Applica
ti
on
Electrical Equipment for use in Hazardous loca
ti
on
Area Classi
fi
ca
ti
on
II 2 G/ II 2 D
Protec
ti
on Technique
encapsula
ti
on (m)
Cer
tifi
cate
IECEx KIWA 18.0008X and KIWA 18ATEX0013 X
Electrical Data:
Switching Voltage:
max. 30 V
Switching Current:
max. 250 mA
Switching Power:
max. 3 W
Meter Op
ti
ons
Standard Version
Junc
ti
on Box Version
Details
1000 mm cable connec
ti
on
With junc
ti
on box and terminal connec
ti
ons
Ambient Temperature:
-20°C … +65°C
-20°C … +55°C
Marking
Ex mb IIC T6 Gb
Ex mb IIC T5 Gb
Ex mb IIIC T85°C Db
Ex mb IIIC T100°C Db
Installa
ti
on Notes:
•
•
•
Special condi
ti
ons for safe use:
•
•
•
•
Standard Version
Junc
ti
on box Version
1 = Customer connec
ti
on
2 = Poten
ti
al free
(2 wires for each reed switch)
3 = Connec
ti
on to customer device
The current through the Reed Switch must be limited to its max switching current using a suitably rated fuse
of max 0.5Amps. The fuse must have a breaking capacity in accordance with the prospec
ti
ve short-circuit
current of the circuit to properly break the systems highest short circuit current.
In case device is mounted in an area where the use of EPL Gb/Db (Category 2G/D) or EPL Gc/Dc (Category 3G/D)
apparatus is required, the transparent cover must be installed such, that igni
ti
on sources due to electros ta
ti
c
discharge sparks are excluded.
Standard Version:
All entry devices shall only be installed such that there is a low risk from mechanical impact.
The cable of the reed switch shall be protected against damage.
Junc
ti
on box Version:
If the M20X1.5- M to ½” NPT –F Adaptor is used it shall be protected from mechanical impact.
An addi
ti
onal external connec
ti
on facility for an equipoten
ti
al bonding conductor is provided on the metallic
enclosure.
Since the reed contact is poten
ti
al-free, the terminals/wires are not labeled.
Standard Version:
The connec
ti
ng cables of the reed switch alarm either have to be outside the explosive
area or if within shall have to be connected with an appropriate connection housing which complies with the Ex-protection-class.
10
11
Summary of Contents for GT1600
Page 10: ...Section 1 Figure 1 4 Dimensions GT1600 Series See Dimensions Tables on following pages 5...
Page 18: ...Section 1 13 Figure 1 5 Reed Switch Alarm UL Installation...
Page 21: ...Section 1 Figure 1 7 Dimensions and Specs Intrinsically Safe Switch Isolators 16...
Page 26: ...Section 4 Overview 21...
Page 29: ...Section 5 Figure 5 2 GT1600 Sizes 7 10 Parts Assembly Drawing Ref GT16XX002_1 24...