Owner's Manual
BARFS-1 Rev 2.1.1
38 of 50
6.2.10
End of Line (EOL) Test
Step 1
Precede to the smoke/heat alarm containing the end of line (EOL)
device, this is the last smoke/heat alarm on the circuit. For location see
the as installed diagrams.
Step 2
Remove any of the three wires of the end of line (EOL) device; the panel
should now
be in defect mode as per “Defect Mode Test”
Step 3
Restore the EOL, the defect mode is cancelled.
If you are unsure of any test results please contact your nearest Brooks office or
distributor.