![Brooks BARFS-1 Owner'S Manual Download Page 36](http://html1.mh-extra.com/html/brooks/barfs-1/barfs-1_owners-manual_2818773036.webp)
Owner's Manual
BARFS-1 Rev 2.1.1
36 of 50
6.2.2
System operation
Before you apply power to your BARFS-1 system it is important to ensure that you
advise any relevant people i.e. tenants or a security / fire monitoring company, that
system commissioning is occurring as alarm and defect warnings will be initiated.
6.2.3
Power Supply
Power supply voltage is pre-set at the factory to 13.8V DC.
Step 1
Insert the fuse holder (with fuse fitted) in the 3 way mains terminal block
to switch the mains power ON, the power on LED illuminates green.
The panel sounder will sound and the defect LED illuminates red until
the battery is fitted. Only the green power ON indicator should stay
illuminated green; no other facility or indicator should function.
Step 2
Remove the fuse holder to switch off the AC supply few times to check
that the system will not false alarm.
Step 3
Connect the battery leads to the battery, the panel sounder will stop
sounding and the defect LED distinguishes. Ensure that only the power
ON LED is illuminating.
6.2.4
Smoke Heat Alarm Test
Step 1
Proceed to each smoke or heat alarm in turn: check that the green light
on the mounti
ng plate is ‘on’.
Step 2
Press the test button for up to 10 seconds to ensure the sensor
chamber, electronics and sounder are working. A red light on the cover
will flash while horn is sounding. The alarm will stop when the button is
released.
Where smoke/heat alarms are interconnected when pressing the test button of any
smoke or heat alarm all alarms should sound within about 5 seconds of the first alarm
sounding. The red alarm light on the first unit only will flash once a second and the
alarm LED on the control panel BARFS-1 will illuminate.
Pressing the test button simulates the effect of smoke or heat during a real fire and
is the best way to ensure the Alarm is operating correctly.
WARNING: DO NOT TEST WITH FLAME.
This will damage both the Alarm and the
house.
We do not recommend testing with smoke or heat as the results can be misleading
unless special apparatus is used.
6.2.5
Alarm Output Test
Step 1
Ensure alarm outputs are not isolated
Step 2
Proceed to any smoke or heat alarm (only heat alarm if priority 1
selected) and press the test button, within 5 seconds the alarm outputs
should activate.
Step 3
Check for the operation of any ancillary devices i.e. strobe etc
connected to the alarm output.
Step 4
Check that the remote indicator (if fitted) illuminates
– Red LED
(Note: this will only illuminate while the alarm sounds)