Owner's Manual
BARFS-1 Rev 2.1.1
17 of 50
4.2
Control Panel
4.2.1
Specifications
Table 1 BARFS-1 Specifications
Feature
Specification
Enclosure
Zink steel 1.6mm powder coated oyster
Dimensions 280mm H x 305mm W x 75mm D
Power Supply
Input voltage 85-264V AC, 40W switch mode power supply
Output 13.5-16.5V DC, Typical 13.8V
Current 3 Amp
Note: Larger power supply 60W is available on request
Standby Supply
12V / 7AH Sealed lead acid battery
Nominal Voltage
13.8V dc
Current Draw
90mA Single Display
130mA Dual Display
Operating
Temperature
0°C to +50°C
No. of Alarm Circuits
One supervised circuit with discrimination between heat alarm /
manual actuation and smoke alarm (priority 1 & priority 2)
No. of Devices per
Circuit
15 Smoke/Heat Alarms, and or
15 MCP, Sprinkler Clean Contact, and or
3 Strobe Modules, and or
4 Vibration Patrice Modules
Note:
current consumption must be calculated using “Battery
capacity calcul
ation sheet” page 43
Zone Monitoring
Wiring loop in / loop out to smoke / heat alarms and zone devices
fully supervised by active end of line device
Alarm Output
Supervised 12Vdc / 1A fused output
1 set of changeover clean contact
Fault / Defect Output
1 set of changeover clean contact
Fault / Defect Mode
Initiated by abnormal system condition:
1. Power Supply fault, mains fail, battery low or removed, etc
2. Alarm circuit wiring open or short circuit
3. Supervised alarm output open or short
4. Device removed
5. Communications fault
6. Memory fault
Control Switches
Ack
Silences panel buzzer until another event occur
Locate
Silences all smoke / heat alarms except those that have
actuated, restores after approximately 5 minutes. Locate LED
illuminates during the 5 minutes timer
Mute
Silences all smoke / heat alarms, restores after approximately
10 minutes. Mute LED illuminates during the 10 minutes timer
Test
activates all smoke / heat alarm sounders, vibration pad and
strobes, during test, the test LED illuminates
Visual Indications
Power ON
LED, mains power available
Alarm
LED, priority P1 alarm or Priority P1&P2 alarm
Defect
LED common defect / fault
Keypad
1. One keypad per panel and one optional remote keypad can
be fitted or 2 remote keypads without panel keypad.
2. Four wires (RS485) required for remote keypad.