Owner's Manual
BARFS-1 Rev 2.1.1
22 of 50
4.4
Operator’s Module
Alarm
Defect
Model RFS-1
Pow er
Mute
Locate
Ack
Test
BROOKS
Alarm
Residential Fire Safety System
Fire
Figure 9 BARFS-1 Front decal
The display module is connected to the main control module via four way screw
terminal, the front display is shown in Figure 6 above. Two wires for 12V supply and
the other two wires for RS485 bus which used for the communication between main
and display modules. If two display modules have been used, the address in the
main control and display modules must be set as per the following table
System
Main Control
(JP2
– Display Count)
Display Board
(JP1
– Address)
Single Display
X1
#1
Dual Displays
X2
#1 and #2
Notes
:
1. Remote display module requires the same four wires, RS485 bus and
power.
2. Terminating resistor 1K Ohm must be fitted across the comms terminal of
RS485 bus.
4.4.1
Indicators
Table 6 Indictors identification
Descriptor Colour Function
Buzz
er
Power
Green
Steady On, mains power ok
Flashing, mains power off, system running on battery
No
Yes
Alarm
Red
Steady on for priority 1 (P1) alarm or common priority
(P1 & P2)
Off for priority 2 alarm
Yes
Defect
Yellow
One blink : Zone circuit fault
Two Blinks, Strobe fault
Three blinks, Power supply fault
Steady On, Memory fault
Yes
Mute
Yellow
Mute 10 minutes timer running
No
Locate
Yellow
Locate 5 minutes timer running
No
Test
Yellow
Steady On
Yes
Ack
Yellow
Steady On
No