Bronkhorst®
Instruction Manual mini CORI-FLOW ML120
9.17.097G
10
Code
Description
B1V
4…20 mA sourcing output, controller
Analog signal for pump or external valve steering (control signal only).
When the controller output is used for pump or external valve steering (only applicable to mass flow
meters with the controller function enabled), make sure to set parameter
Valve maximum
to 0.3 [A]. For mass
flow controllers, the controller output signal represents the valve actuator current. This output is limited to
a value below 20mA, due to the maximum valve current restriction.
C3A
Digital output, min/max alarm
During a min/max alarm, pin 5 is pulled down to 0 Vdc.
C4A
Digital output, counter alarm
During a counter alarm, pin 5 is pulled down to 0 Vdc.
C5S
Example for C5S or C0I hook-up
Digital output, enabled by setpoint (for shut-off control)
Pin 5 is pulled down to 0 Vdc at a controller setpoint, e.g. for shut-off
valve activation.
For factory selected analog control (…-A#-C5S):
If parameter
Control mode
is set for analog control by factory, the
minimum setpoint at which the device (shut-off valve) connected to pin 5
is activated is 1.9%. This prevents possible noise on the analog input
activating the device accidentally.
For factory selected digital control (…-D#-C5S):
If parameter
Control mode
is set for digital control by factory, the setpoint threshold for activating the
device connected to pin 5 is any value > 0.
Note: If the instrument is forced into Valve Safe State, the digital output is not affected, so a (n/c) shut-off
valve connected to pin 5 will not close when the (n/c) controller is in Valve Safe State’
Make sure to use 24Vdc power supply corresponding to the shut-off valve specifications. Cable 7.03.572 (T-
part 9-pin D-sub/loose end) or 7.03.603 (T-part 9-pin D-sub/DIN43650C) can be used for this operating
option.
C0I
Digital output, high/low switch via remote parameter (e.g. for shut-off valve control)
Pin 5 is pulled down to 0 Vdc when writing value 1 to parameter
IO switch status
, this is undone by writing
value 0.
A device connected to pin 5 (e.g. a shut-off valve) can be activated/deactivated by writing parameter
IO
switch status
.
Note: If the instrument is forced into Valve Safe State, the digital output is also affected, so a (n/c) shut-off
valve connected to pin 5 will be closed when the (n/c) controller is in ‘Valve Safe State’.
Make sure to use 24 Vdc power supply corresponding to the shut-off valve specifications. Cable 7.03.572 (T-
part 9-pin D-sub/loose end) or 7.03.603 (T-part 9-pin D-sub/DIN43650C) can be used for this operating
option.
D9E
Digital frequency output, measure
Measurement value is translated to a frequency within given frequency range.
The default frequency range to represent 0…100% flow is 0…10000 Hz. Any other frequency range must be
specified on order.