WVRC-4 Plus Installation and Operation Manual
OPERATION
Using the Dial-Up Interface - cont.
Alarm Enable Registers
All of the alarm call-outs can be enabled, disabled or polled remotely using DTMF
control.
The status alarms can be controlled by entering 97 followed by the status number 1
through 4 and 1 for enable, 0 of disable or 9 for poll.
The analog (metering) alarms can be controlled by entering 98 followed by the ana-
log number 1 through 4, and 1 for enable, 0 for disable or 9 for poll.
Power fail, silence sensor and temperature are controlled with 99 followed by 1 for
power fail, 2 for silence sensor and 3 for temperature. 1 to enable, 0 to disable or 9
to poll.
Some examples are listed below:
Enable Status 4 alarm:
9741
Disable Status 4 alarm:
9740
Poll Status 4 alarm enable:
9749
Enable Analog (metering) 4 alarm:
9841
Disable Analog (metering) 4 alarm:
9840
Poll Analog 4 alarm enable:
9849
Enable Power Fail Alarm:
9911
Disable Power Fail alarm:
9910
Poll Power Fail alarm enable:
9919
Enable Silence Sensor Alarm:
9921
Disable Silence Sensor Alarm:
9920
Poll Silence Sensor Alarm enable:
9929
Enable Temperature Sensor Alarm:
9931
Disable Temperature Sensor Alarm:
9930
Poll Temperature Sensor Alarm enable:
9939