WVRC-4 Plus Installation and Operation Manual
SET UP
“I/O” Setup Page
Metering
Metering input selection:
Select metering inputs 1 - 4 for configuration.
Meter Label:
Used to identify the metering input source.
Meter Units:
Units label in engineering units, such as V = Volts,
A = Amps, W = Watts, etc.
Calibration:
Enter the value of the desired meter reading.
NOTE:
In order to calibrate, a valid DC sample voltage must be applied to each input that
you are calibrating. The calibration value must be positive and can support a resolution up
to 2 decimal places. The user MUST enter a calibration value and press the “Save Cal” but-
ton in order to store the value. You do not need to press the “Save Settings” button to save
the calibration, only the other settings.
Alarms High:
This option enables the “High Trip Point” alarm.
Alarms Low:
This option enables the “Low Trip Point” alarm.
Alarms Exit:
This option enables the generation of an alarm after exiting a high or
low alarm state.
Email Addresses:
This allows you to assign up to 8 email addresses to send alarm emails
to whenever the input enters an alarm state.
Log Device:
Enables the email snapshot logging of the input.
Delay time:
Specifies the delay time from when the input value is above or below
the set alarm trip points and an alarm is generated. 0-999 seconds
Low trip point:
This option specifies the LOW alarm set-point.
High trip point:
This option specifies the HIGH alarm set-point.
NOTE: After any item has been changed, you MUST press the “Save Settings”
button for your changes to be saved.