16
Table 6:
Heating & Refrigeration Zoning Parameters
Cooling
Parameter
ID
Heating
Parameter
ID
Feature
ID03
ID17
To enable Zone A
ID04
ID18
Select relay for Zone A
ID05
ID19
Select sensor No: for Zone A
ID06
ID20
To enable Zone B
ID07
ID21
Select relay for Zone B
ID08
ID22
Select sensor No: for Zone B
ID09
ID23
To enable Zone C
ID10
ID24
Select relay for Zone C
ID11
ID25
Select sensor No: for Zone C
ID12
ID26
To enable Zone D
ID13
ID27
Select relay for Zone D
ID14
ID28
Select sensor No: for Zone D
For more details please refer to
Table 8:- Master Controller
Parameters
in the Appendix.
Example: Setting up Zone A – Dual Comfort
1.
Access the Installer Parameters (6.3, p.14)
2.
Push the
Mode
Key
until
“n01”
is displayed on the
Master Controller interface, top left hand corner
3.
Press
Key
“1”
and scroll to parameter
“ID03”
. This
parameter value allows you to enable Zone A for
Refrigerated Cooling
4.
Rotate the dial and change the parameter value from
“0”
to
“1”
to enable Zone A
5.
Press
Key
“1”,
rotate the dial
and scroll to parameter
ID04
. This parameter value nominates the relay that will
supply power to the zone motor
6.
Rotate the dial to either relay number that is driving the
associated zone damper motor, either
1, 2, 3, or 4
for a
four zone system
7.
Press
Key
“1”
and scroll to parameter
ID05
. This value
allows you to select the associated zone’s sensor ID
8.
Rotate the dial to select the correct sensor for the zone,
either
“1”, “2”, “3”, or “4”
for a four zone system
9.
To setup Zone B for Refrigerated Cooling conduct the
above steps for ID06, ID07 and ID08
10. Once all zoning parameter changes are complete press
the
On/Off
button to save and exit
The process in the above example also applies to setting up
the zones for Heating. Please refer to the parameter numbers
in this section for Heating and Refrigerated Cooling or
Table 8
,
which is where all Parameter values should be recorded.
6.4.5 Airflow Setting and Balancing
Fan Scaling
Fan scaling customises the required heating or cooling airflow
for individual zones. Fan speed settings range from 1 – 16
(Min – Max) for each zone.
Airflows should be set in accordance with design conditions;
care should be taken not to cause drafts or noise concerns.
We recommend balancing dampers be fitted in the ducting
system (e.g. at supply air outlet, at the branch take-off, or via
an in-line ductwork damper) for final airflow adjustments.