7.2 Service Clearances
Front & Back
A minimum of 500mm must be provided at the side facing away from the house.
End
A minimum of 300mm must be provided at each end of the heater.
Top
A minimum of 1000mm must be provided above the heater roof. This clearance must be maintained for the entire
surface area of the heater roof.
7.3 Thermistor Installation
The thermistor is located on a bracket beneath the heat exchanger and must be positioned correctly prior to
installing unit onto base box:
1.
Locate unit next to the base box and orientate onto fan cabinet end.
2.
Remove all packaging.
3.
Bend thermistor arm down away from the heat exchanger until it touches the stopper
plate. The arm will rotate through an angle of 45° only, excessive force is not required.
Diagram 16.
BX520 Illustrated
Note:
The BX520 thermistor is centrally mounted and the BX526 thermistor is mounted at the unit’s end.
16
Detail View