Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
56
Cooler Operation
(cont.)
Fan Motor will not operate (cont.)
•
Check for 240 Volts at terminals
MOTOR/RUN-BROWN
and
MOTOR/COMMON-
BLUE
on the motor supply loom terminals, located on the service compartment
back wall (max fan speed selected).
OFF
10 A
V
COM
FUSED
1000V- - -
750V
V
VOLTS
Multimeter
240
MOTOR/RUN-BROWN
MOTOR/COMMON-BLUE
If 240 Volts present:
•
Check for Volts at terminals
MOTOR/COMMON-BLUE
and
MOTOR/START-
BLACK
on the motor supply loom terminals located on the service compartment
back wall (max fan speed selected).
•
Replace capacitor and test again.
•
Replace fan motor.
OFF
10 A
V
COM
FUSED
1000V- - -
750V
V
VOLTS
Multimeter
240
MOTOR/COMMON-BLUE
MOTOR/START-BLACK