Service Manual 32 – Contour 3 Series, Profiler & Advance – Approved Issue 5 Printed 2/13/2014 11:50:17 AM
37
Cooler Parameters
N-E5 Parameter Table:
Parameter Name
Parameter
Number
Range
Units
Default
Parameter Description
Installer Parameters
Unit ID Number
7
1 - 15.
number
1
Changes the unit identification
number for multiple unit
installations.
Installer Flush Count
14
1 - 20.
cycles
20
Number of tank refills before a
flush will occurs.
Dump Check
16
0 - 1
number
0
Used to check the dump
operation. If set to 1.
Must be
set back to 0 after dumping
occurs.
Service Parameters
Dump delay
1
1 - 255
10
minutes
6
Time delay after use before
dumping occurs. See servicing
instruction 21 on page 3.
6 x 10 minutes = 60 minutes
Fill time
2
1 - 255
minutes
15
Time allowed for the trough
water level to reach high level
from empty.
Min Fan Speed
3
0 -125
10 x
RPM
Minimum fan speed
Max Fan Speed
4
60 -135
10 x
RPM
Maximum fan speed
Model Selection
Number
5
1 - 7.
1
Cooler model selection
number. Sets the default fan
speed by selecting the unit
number as per the
Specification sheets.
Short Dry Pad Time
13
1 - 255
minutes
2
Time the pump can be off
before a normal Pre-Wet is
necessary.
Service Flush Count
15
1 - 255
cycles
See
notes
Number of tank refills before a
flush will occur.
Profiler (no Aquasave) = 20
Contour (no Aquasave) = 20
Contour (with Aquasave) = 250
Short Pre-wet Time
18
1 - 255
seconds
60
Normal Pre-wet time.
Long Pre-wet Time
19
1 - 255
seconds
120
Extended Pre-wet time.
Long Dry Pad Time
20
1 - 255
minutes
10
Time the pump can be off
before an extended Pre-Wet is
required
Status Mode
21
0 - 2
2
Do not alter/ not used.
Aquasave
22
0 - 1
number
0 or 1
Is used when an Aquasave
present on the cooler.
Brivis Contour = 1
Brivis Profiler = 0
Flush time
43
1-255
seconds
200
Time solenoid is open during a
flush service.
Contour 0 series = 100 sec
Contour 1 series = 60 sec
Contour 2 series = 200 sec
Contour 3 series = 200 sec
Profiler series = 200 sec