I nstal l ati on
26
Operating manual for PROFIBUS fieldbus | 2015-07 | V1.7 EN
3.2.1 Setting the address on the communication card
DANGER
Risk of death due to electrical shock!
Death or serious injury!
De-energise drive controller and secure it against being restarted.
IMPORTANT INFORMATION
The address of an FKO must lie within the range from 2 to 125.
Procedure
1. Switch the drive controller to voltage-free.
2. Unscrew the cover of the drive controller.
3. Set the address with a screwdriver on both switches (Switch 1/Switch 2).
IMPORTANT INFORMATION
You can find the corresponding address for the switch positions in
chapter
" Setting the field bus address via rotary switches
Switch 1/Switch 2"