JB-QB-5Ei
Users’ Manual
JB-QB-5Ei
Fire Alarm Control Panel
34
This function supports Chinese (pinyin), English and digits input. When input device number, if
push
【
menu
】
key, one “*”symbol will be displayed after the “N” in LCD screen. At this time, if
the operator press
【
ENTER
】
key to confirm input numbers, the control panel will not assign out
original position information. The panel will treat current position place information as this
number’s position information. This process is a very simple copy function for position
information editing. Copy the last detector’s position information to this detector to simplify the
device position information editing which has been installed in the same place.
5.3.7 Associated operation programming
In the automatic status, Associated operation programming is the auto-start logic which can
control the fire fighting device according to the fire alarm signal. In debugging menu , press
【
5
】
key to enter associated operation programming function (Figure 16), the system supports 3 logic
relations: “AND”, “OR1”, “OR2”.
“AND”logic expresses
:
any one piece device alarms which has been set into Condition 1 range,
and any one piece device also alarms which has been set into Condition 2 range, it will send out
control signal to associated operation device which has been set into activation range.
“OR1”logic expresses
:
any one piece device alarms which has been set into Condition 1 range, or
any one piece device alarms which has been set into Condition 2 range, it will send out control
signal to associated operation device which has been set into activation range.
“OR2”logic expresses
:
any two pieces devices alarm which have been set into Condition 1 range,
or any two pieces device alarm which have been set into Condition 2 range, it will send out control
signal to associated operation device which has been set into activation range.
After set up needed associated operation programming data, first data item in next page should be
set to 0. If we set 5 pieces (one piece per page, start from Page 0) programming data, we need to
set first data item in No.5 page to 0.
Figure 16 associated logic programming setting
5.3.8 Other parameters setting
Record select
This control panel can record fire alarm, supervising, start, feedback, fault, event
into black box. Beside fire alarm, all other type messages are optional . They can be record or
non-record according to the setting. In debugging menu, press
【
7
】
key->
【
3
】
key to enter record
select function (Figure 17). Each item can be set to “Yes” or “No”. The users can set them
according to their requirement.