13). There are two display methods for parameter test function. One is digital value display.
Another is curve display. Push
【
menu
】
key to be able to make conversion between these two
display methods.
Device test
UP DOWN LEFT RIGHT-page
No: 001
Loop: 1 2 3
RegValue: 27 26 159
CurValue: 11 27 26 8 113
Type: HEAT SMOK
device registered
value
device current
smoke value
device current
heat value
MENU-linear mode,ESC-return
Device test
UP DOWN LEFT RIGHT-page
No: 001
Loop: 1 2 3
RegValue: 27 26 159
CurValue: 11 27 26 8 113
Type: HEAT SMOK
device registered
value
device current
smoke value
device current
heat value
MENU-linear mode,ESC-return
Figure 13 Device test interface
Each detector have 2 analogue values : smoke value and heat value. According to the detector type,
we can know whether current value is smoke value or heat value. If the detector type is heat
detector type, the current value is referred to the heat value. Other type devices are referred to
smoke value. If the detector current value is lower than 12, the detector will be not registered into
the system. It should be replaced.
If detector current type is not the same with the displayed type, the operator can change the
detector type the current type in “type settings” menu. In debugging menu, push
【
7
】
key->
【
2
】
key to enter type setting function (Figure 14).Attention: the smoke or heat detector’s type can be
changed to other type.
Type settings
MENU-type,ENTER-confirm,ESC-return
Range: 01L-008N-009N
Type: SMOK
number range which
need to re set-up device type
Type settings
MENU-type,ENTER-confirm,ESC-return
Range: 01L-008N-009N
Type: SMOK
number range which
need to re set-up device type
Figure 14 type setting
5.3.6 Edit device position information
Position information is the detector installation position. If there is fire alarm, the operator will
accurately find the alarm position. In debugging menu, press
【
4
】
key to enter position
information editing function(position description) (Figure 15).
4.Location
ENTER-confirm,ESC-return
Number: 01L-111N
Location:
ABCD
4.Location
ENTER-confirm,ESC-return
Number: 01L-111N
Location:
ABCD
Figure 15 Edit position information setting