9
Briggs & Stratton Power Products Manual Transfer Switch
Installation and Owner’s Manual
SYSTEM OPERATION
To transfer from utility power to generator power:
1.
Turn OFF main breaker labeled “UTILITY SUPPLY”.
2.
Turn OFF all branch circuit breakers in transfer switch.
3.
Slide mechanical interlock and turn “GENERATOR
SUPPLY” breaker to ON position.
4.
Turn ON branch circuit breakers one at a time.
To transfer from generator power back to utility
power:
1.
Turn OFF main breaker labeled “GENERATOR
SUPPLY”.
2.
Turn OFF all branch circuit breakers in transfer switch.
3.
Slide mechanical interlock and turn “UTILITY SUPPLY”
breaker to ON position.
4.
Turn ON branch circuit breakers one at a time.
Specifications
UL® 1008 Listed Transfer Switch
Model 071002
Enclosure . . . . . . . . . . . . . . . . . . . NEMA 1
Maximum Load/Circuit:
from Load Center . . . . . . . . . . 60 Amps
Rated AC Voltage. . . . . . . . . . . . . 250 Volts
Poles . . . . . . . . . . . . . . . . . . . . . . 2
Fault Current Rating . . . . . . . . . . 10,000 RMS Symmetrical
Amperes
Weight . . . . . . . . . . . . . . . . . . . . . 27 lbs.
Model 071003
Enclosure . . . . . . . . . . . . . . . . . . . NEMA 3R
Maximum Load/Circuit:
from Load Center . . . . . . . . . . 60 Amps
Rated AC Voltage. . . . . . . . . . . . . 250 Volts
Poles . . . . . . . . . . . . . . . . . . . . . . 2
Fault Current Rating . . . . . . . . . . 10,000 RMS Symmetrical
Amperes
Weight . . . . . . . . . . . . . . . . . . . . . 34 lbs.
When Calling the Factory
Before contacting Briggs and Stratton Power Products
regarding service or repair of this transfer switch, obtain
the Model Number from the unit data decal located on or
inside the case.
To contact Briggs and Stratton Power Products call
1-800-743-4115, between 8:00 AM and 5:00 PM CT.