background image

42” min.

 

(106.7 cm)

13” max.

 

(

33.0 cm)

6” min.

(15.2 cm)

18” min.

(45.7 c

m)

3/8”

 

(0.95 cm)

36” 

(91.4 cm)

29-7/8”

(75.9 cm)

A

(opening width)

Clearance Dimensions

(Wood/Composite Overlay)

9

Clearance Dimensions 

(Proximity to Cabinets)

8

The bottom of a standard hood should be
30” (76.2 cm) min. to 36” (91.4 cm) max.
above the countertop. This would typically
result in the bottom of the hood being
66” (167.6 cm) to 72” (182.9 cm) above the
floor. Refer to the range hood installation
instructions for additional information. These
dimensions provide for safe and efficient
operation of the hood.

66”min.

(167.6 cm)

to

72”max.

(182.9 cm)

66”min.

(167.6 cm)

to

72”max.

(182.9 cm)

24”

(61.0 cm)

or

27”

(38.6 cm)

30”

(76.2 cm)

6”

(15

.2 c

m)

Wood/Composite 

Overlay

Wood/Composite 

Overlay

30”min.

(76.2 cm)

to

36”max.

(91.4 cm)

0”

 

(

0 cm)

30”min.

(76.2 cm)

to

36”max.

(91.4 cm)

Wall Installation

Island Installation

Note: 

Minimum clearance for back wall

is 0” with backguard or high-shelf.

CAUTION

Burn hazard.

To avoid risk of personal injury;
the use of cabinets for storage
above the appliance may result

in a potential burn hazard. Combustible
items may ignite, metallic items may
become hot and cause burns. If a cabinet
storage is to be provided the risk can be
reduced by installing a rangehood that
projects horizontally a minimum 5” (12.7 cm)
beyond the bottom of cabinets.

• This range may be installed directly 

adjacent to existing 36” (91.4 cm) high 
base cabinets.

IMPORTANT:

The side trim MUST be

3/8” (.95 cm) above the adjacent base 
cabinet countertop. This can be 
accomplished by raising the unit using the 
adjustment spindles on the legs.

• The range CANNOT be installed directly 

adjacent to sidewalls, tall cabinets, tall 
appliances, or other side vertical surfaces 
above 36” (91.4 cm) high. There must be a
minimum of 6” (15.2 cm) side clearance 
from  the range to such combustible 
surfaces above the 36” (91.4 cm) counter 
height.

• Within the 6” (15.2 cm) side clearance to 

combustible vertical surfaces above 36” 
(91.4 cm), the maximum wall cabinet 
depth must be 13” (33.0 cm) and wall 
cabinets within this 6” (15.2 cm) side 
clearance must be 18” (45.7 cm) above the
36” (91.4 cm) high countertop.

• Wall cabinets above the range must be a 

minimum of 42” (106.7 cm) above the 
range cooking surface for the full width of 
the range. This minimum height 
requirement does not apply if a range 
hood is installed over the cooking surface.

CAUTION

To prevent possible damage to cabinets
and cabinet finishes, use only materials
and finishes that will not discolor or
delaminate and will withstand temperatures
up to 194

°

F (90

°

C). Heat and moisture

resistant adhesive must be used if the
product is to be installed in laminated
cabinetry. Check with your builder or
cabinet supplier to make sure that the
materials meet these requirements.

Note: 

Minimum clearance for back wall is 0” with backguard

or high-shelf.

Note: 

If a range hood is installed, wall cabinets above the

range have a different minimum clearance height.

Range

Width

“A”

Dimension

30”

30” (76.2 cm)

Important: 

This range comes standard

with an Island Trim. There must be a
minimum of 6” (15.2 cm) clearance from
rear of range to a 

combustible

wall.

Clearances from non-combustible
materials are not part of the ANSI Z21.1
scope and are not certified by CSA.
Clearances to non-combustible materials
must be approved by the authority having
jurisdiction.

Summary of Contents for CVESC530-4B

Page 1: ...ont Street Greenwood Mississippi 38930 USA 662 455 1200 For product information call 1 888 845 4641 or visit our web site at www brigade ca F21091 EN 030113 BRIGADE TM Installation Guide Professional...

Page 2: ..._____22 Performance Checklist ______________________________________________________________22 Service Registration_______________________________________________________________23 Before beginning pl...

Page 3: ...ll withstand temperatures up to 194 F 90 C Heat resistant adhesive must be used if the product is to be installed in laminated cabinetry Check with your builder or cabinet supplier to make sure that t...

Page 4: ...16 1 2 41 9 cm Oven interior depth AHAM 16 13 16 42 7 cm Overall 19 1 2 49 5 cm Oven volume Total oven capacity 4 7 cu ft Measure to AHAM standards 4 1 cu ft Approximate shipping weight 426 lbs 193 2...

Page 5: ...les on the legs The range CANNOT be installed directly adjacent to sidewalls tall cabinets tall appliances or other side vertical surfaces above 36 91 4 cm high There must be a minimum of 6 15 2 cm si...

Page 6: ...sult in damage to the oven or surrounding cabinets Viking Range Corporation will NOT warranty any problems resulting from GFI outlets which are not installed properly or do not meet the requirements b...

Page 7: ...ers Leg Installation 12 CAUTION To avoid risk of personal injury or product damages DO NOT use the handle or oven door to lift the oven Remove door before installation to ensure that it is not used to...

Page 8: ...codes If ground to the frame is not permitted then a 4 conductor power cord must be used WARNING Electrical shock hazard To avoid risk of electrical shock personal injury or death verify your applianc...

Page 9: ...l injury or death grounding product to the frame of the unit may or may not be permitted through your local codes If ground to the frame is not permitted then a 4 conductor power cord must be used WAR...

Page 10: ...el For uneven or sloped floors level unit with metal shims only as the adjustment required may exceed the thread available in the leg 3 3 8 3 8 0 95 cm 0 95 cm 3 8 0 95 cm 4 Move unit into opening Lev...

Page 11: ...3 8 0 95 cm 0 95 cm 3 8 0 95 cm 3 Check that unit is level side to side and front to back The side trim must be 3 8 0 95 cm above countertop If unit is not level repeat steps 5 7 of Leveling Adjustme...

Page 12: ...spatula or any other material tool to scrape stainless steel Scratches are almost impossible to remove NOTICE When conducting performance test DO NOT run self clean cycle for more than 10 minutes wit...

Reviews: