E16521D-Manual_EN_Rev12 2021_JAN_14
Page 14 of 26
Parameter Group P01.xx (continued)
Reset, Sensor Monitoring
Parameter No.
Meaning of Parameter
Setting Range of Parameter
Description of Parameters and their Settings
P01.07
Reset necessary after power up
Range: 0 .. 1
Depending on this setting, the Reset input must be actuated once after
power up of the Monitor to enable operation.
0 : Reset necessary (recommended setting for safety applications)
1 : Reset not necessary
Note: a positive edge of the Starter signal also acts as Reset
P01.08
Sensor monitoring on/off
Range: 0 .. 2
If the sensor is monitored, the fault alarm may be latched until it is reset.
Setting:
0 : off (sensor monitor disabled)
1 : on
2 : on, latched
Note: If P01.08 set to 0 , Step P01.09 is meaningless.
P01.09
Mode of sensor monitoring
Range: 0 .. 7
Setting:
0 : Without monitoring
(see Note 3)
1 : Checks sensor current drain
2 : Checks signal voltage level at standstill
(see Note 1)
3 : Current drain and voltage level (E16521D.1 with A5S sensors)
4 : Inductive sensor (E16521D.3 with MPU sensors)
5 : Reserved for future use
6 : Eddy Current sensor voltage level (E16521D.2 with
EC Sensors)
(see Note 2)
7 : Eddy Current sensor voltage level and current drain (E16521D.2 with
EC Sensors)
(see Note 2)
Note 1: The voltage level check is only possible with BRAUN-sensor type
A5S... . In this instance, even at a standstill a defective sensor or
supply cable can be detected.
Note 2: The signal voltage level (and current drain) is compared versus
max/min-values as set in P08.01 to P08.04.
Note 3: Selection of Setting 0 makes Step P01.08 meaningless.
P01.10
Fix value 001