Parameter Group P02.xx
Display
Parameter No.
Meaning of Parameter
Setting Range of Parameter
Description of Parameters and their Settings
P02.00
Fix value 0
P02.01
Display updating sequence
Range: 0.1 .. 9.9
Independent from the response time used for other functions, the display
may have its own up-dating sequence - again in the interest of stabilized and
well legible readings. Set the time between updates in steps of 0.1 sec.
A recommended value is 0.3 sec.
Parameter Group P03.xx
Analog Output
Parameter No.
Meaning of Parameter
Setting Range of Parameter
Description of Parameters and their Settings
P03.00
High end of analog output
at speed
Range: 00001 .. 99999
The high end defines at which speed (RPM) the output delivers 20 mamps.
P03.01
Low end of analog output
at speed
Range: 00001 .. 99999
The low end defines at which speed (RPM) the output delivers
0 resp. 4 mamps.
P03.02
Live Zero
Range: 0 .. 1
The analog signal can be without or with live zero.
Setting:
0 : " without live zero" = 0...20 mA
1 : "with live zero" = 4...20 mA
P03.03
Fix value 1
P03.04
Forced output level at
sensor fault condition
Range: 0 .. 2
Setting:
0 : no,
output follows measured speed
1 : min:
output goes to < 0 mamps
2 : max:
output goes to approx. 21 mamps
P03.05
Output direction
Range: 0 .. 1
Setting:
0 : normal
(0/4. .20 mA with increasing speed)
1 : inverted
(20...0/4 mA with increasing speed)