Parameter Group P05.xx
Speed Setpoint SP2 and Alarm Output OR2
Parameter No.
Meaning of Parameter
Setting Range of Parameter
Description of Parameters and their Settings
P05.00
Speed setpoint SP2
Range: 00001 .. 99999
Speed setpoint SP2 is set in RPM.
P05.01
Hysteresis bandwidth SP2
Range: 00.1 .. 99.9
The hysteresis is the margin between condition "excess" (>) and "no excess"
(<), defined by its bandwidth. The hysteresis bandwidth is set as a
percentage of the setpoint in steps of 0.1%.
P05.02
Hysteresis position SP2
Range: 0 .. 1
Setting:
0 : hysteresis above SP2 (recommended when monitoring n < SP2)
1 : hysteresis below SP2 (recommended when monitoring n > SP2)
P05.03
De-energized state OR2 at
' n > SP2 ' or ' n < SP2 '
Range: 0 .. 3
Without power supply the relays are de-energized (alarm condition). To
consider safety aspects of the application, this No-Power condition can be
assigned to alarm state n > SP2 or n < SP2 condition.
Setting:
0 : OR2 de-energized at ' n < SP2 '
1 : OR2 de-energized at ' n > SP2 '
2 : OR2 de-energized and latched at ' n < SP2 '
3 : OR2 de-energized and latched at ' n > SP2 '
P05.04
Starter effective for SP2
Range: 0 .. 1
The starter function may be effective for each setpoint individually. Thereby
it is possible, for instance, to disable a low-speed alarm during the starter
phase, whereas a high-speed alarm remains active all the time.
Setting:
0 : starter not effective for setpoint SP2
1 : starter effective for setpoint SP2
P05.05
OR2 state at starter condition
Range: 0 .. 1
At starter condition, the relay may be forced to state energized or
de-energized (if starter function is effective for the alarm).
Setting:
0 : OR2 de-energized
1 : OR2 energized
P05.06
OR2 in forced de-energized
state at
sensor fault condition
Range: 0 .. 2
At sensor fault, OR2 may be forced to de-energized state.
Setting:
0 : no forced state, state acc. to measured speed
1 : OR2 in de-energized state as if n > SP2 (if P05.03 is 1 or 3)
2 : OR2 in de-energized state as if n < SP2 (if P05.03 is 0 or 2)