Description 

 

 2.1 

Function 

The  device  measures  the  speed  of  rotating  equipment  such  as  turbines,  compressors  or  ex-
panders and monitors it versus setpoints and converts it into an analog output. 
Parameters may be set via front keyboard and display or via the USB2.0 data interface. 
 

 2.2 

Display and Operating Elements  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Note: E16521D.4 does not have LEDs, keys and display. 
 

 2.3 

Display 

During normal operation, the speed will be displayed. 
 

 2.4 

Status LEDs 

LEDs 1 to 4 are on if the corresponding output relays OR1 to OR4 are energized. 
 

 2.5 

Functions during normal operation 

Key     : Reset of latched max./min. speed values 
Key     : Display of latched max. speed value 
Key     : Display of latched min. speed value 
Keys      and     : Reset of latched alarms 
 
 
 
 
 
 
 
 
 

LEDs  
1 to 4 

Display 

Data Interface 

Operation 
Keys 

Summary of Contents for E16521D Series

Page 1: ...e 1 of 26 Manual Series E16521D Revision 12 Original Instructions valid for E16521D 1 E16521D 4 and E16521D 2 and E16521D 3 E16521D Front View version E16521D 1 is shown Single Channel Speed Monitor f...

Page 2: ...nd their default values as set on delivery 9 3 2 Setting the Parameters via Interface 10 3 2 1 Setting the Parameters via USB 2 0 Interface from serial number 2011250001 10 3 2 2 Setting the Parameter...

Page 3: ...r Trigger hysteresis 0 07 to 2 5 V pp EC Sensor Sensor supply approx 24 V max 40 mA for model E16521D 2U1 approx 24 V max 120 mA E16521D 3 Max input frequency 50 kHz Signal input for Max signal voltag...

Page 4: ...rature stability 0 02 C within a range of 0 60 C Display 5 digits LED red 10 mm with adjustable decimal point not with E16521D 4 Programming Interface with interface software IS RS232 S and RS232 up t...

Page 5: ...6 1 1 Dimensions Dimensions mm of snap on track standard version Dimensions of Field Mounting Enclosure Option G 3 cable conduits PG 9 160 mm 88 mm 120 mm 148 mm 4 bore holes of 4 2 mm 70 95 75 35 110...

Page 6: ...SB2 0 data interface 2 2 Display and Operating Elements Note E16521D 4 does not have LEDs keys and display 2 3 Display During normal operation the speed will be displayed 2 4 Status LEDs LEDs 1 to 4 a...

Page 7: ...he programmed application data relation between machine speed and signal frequency 2 9 Performance at Signal Break In normal operation the function closely tracks the input sequence with the programme...

Page 8: ...of conversion programmable 2 15 Pulse Repeating Output Push pull with approx 20 volts level isolated versus signal input and versus power supply Repeating the input pulse signals by the same sequence...

Page 9: ...yes 1 no 08 1 Sensor monitoring 0 off 1 on 2 on latched 09 0 Mode of sensor monitoring see parameter description 10 001 Fix value 001 P02 xx Display P02 00 0 Fix value 0 01 0 3 Display updating sequen...

Page 10: ...sis bandwidth SP4 00 1 99 9 02 0 Hysteresis position 0 above SP4 1 below SP4 03 1 De energized state OR4 at n SP4 or n SP4 see parameter description 04 1 Starter effective for SP4 0 no 1 yes 05 1 OR4...

Page 11: ...and Step Fields with the key Current value of the Parameters is displayed with key Select active position with the key Adjust the number in the active field with keys Acknowledge and set with key Dis...

Page 12: ...front side change of parameter values possible P00 03 Minimum Measuring Period in milliseconds Range 0005 9999 The measurement is based on a time interval measurement over a variable number of input s...

Page 13: ...operation however it may be overrun without error Example A rotating shaft to be measured carries 36 slots At a shaft speed of 1500 RPM this produces a signal frequency of 1500 36 pulses per minute 54...

Page 14: ...on latched Note If P01 08 set to 0 Step P01 09 is meaningless P01 09 Mode of sensor monitoring Range 0 7 Setting 0 Without monitoring see Note 3 1 Checks sensor current drain 2 Checks signal voltage...

Page 15: ...Range of Parameter Description of Parameters and their Settings P03 00 High end of analog output at speed Range 00001 99999 The high end defines at which speed RPM the output delivers 20 mamps P03 01...

Page 16: ...tion To consider safety aspects of the application this No Power condition can be assigned to alarm state n SP1 or n SP1 condition Setting 0 OR1 de energized at n SP1 1 OR1 de energized at n SP1 2 OR1...

Page 17: ...on can be assigned to alarm state n SP2 or n SP2 condition Setting 0 OR2 de energized at n SP2 1 OR2 de energized at n SP2 2 OR2 de energized and latched at n SP2 3 OR2 de energized and latched at n S...

Page 18: ...on can be assigned to alarm state n SP3 or n SP3 condition Setting 0 OR3 de energized at n SP3 1 OR3 de energized at n SP3 2 OR3 de energized and latched at n SP3 3 OR3 de energized and latched at n S...

Page 19: ...on can be assigned to alarm state n SP4 or n SP4 condition Setting 0 OR4 de energized at n SP4 1 OR4 de energized at n SP4 2 OR4 de energized and latched at n SP4 3 OR4 de energized and latched at n S...

Page 20: ...upper limit in xxx mA P08 03 Current drain lower limit Range 000 to 999 current drain lower limit in xxx mA P08 04 EC and MPU signal input hysteresis Range 0 0 to 2 5 Signal input hysteresis sensitivi...

Page 21: ...European Committee for Electrotechnical Standardization CENELEC for the Electromagnetic Compatibility 2014 30 EU Testing and inspection have been performed according to Standards EN 61326 3 2 Thereby...

Page 22: ...operation the measured speed must be above SP2 If analog output is used for plausibility check With machine in operation the value of the analog output must be checked by a system capable of diagnosis...

Page 23: ...on Rating see specifications of relay outputs 5 4 High Starter active 12 24 V Reference to Starter Reset input 3 Positive edge Reset of Latched Alarms 12 24 V 8 Safety Output OR1 Measurement and signa...

Page 24: ...eed signal EC Input reference 0 volts Speed signal A5S0 1 3 4 17 18 14 brown green white Cable screen must be connected to screen bar Lead colors of BRAUN cables L3A or L3T or A5S with fixed cables Pi...

Page 25: ...E16521D Manual_EN_Rev12 2021_JAN_14 Page 25 of 26 6 3 Example for 2oo3 Wiring of Safety Outputs OR1 Other versions of 2oo3 wiring are also possible...

Page 26: ...eding 170630000 30 01 2019 06 Editorial Chapter 5 2 1 modified 14 01 2020 07 Editorial Parameter P01 06 now 0 instead of 1 No functional change 25 01 2020 08 Editorial Parameter P01 00 and P01 02 fix...