background image

Installation instructions

RTG 199 ME – 6 720 811 615 (2015/04)

24

1. The referenced "special venting system" instructions shall be included 
with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be product approved by the 
Board, and the instructions for that system shall include a parts list and 
detailed installation instructions.
(e) A copy of all installation instructions for all products approved side 
wall horizontally vented gas fueled equipment, all venting instructions, 
all parts lists for venting instructions, and/or all venting design 
instructions shall remain with the appliance or equipment at the 
completion of the installation.

4.4

Combustion air requirements

Twin pipe and Concentric pipe

The water heater is designed as a sealed combustion appliance. It is 
recommended that the combustion air be provided by a dedicated 3” or 
4” pipe from the outside (twin pipe) or by connecting to the Concentric 
vent kit (see Fig.8, 9 & 10). The combustion air pipe may be PVC or any 
other rigid sealed 3" or 4" pipe. The combustion air piping must pitch 
down 1/4 inch per foot towards termination to prevent rain water from 
entering the appliance. In twin pipe penetrations, the combustion air 
inlet, whether terminating vertically or horizontally, must be located in 
such a manner as to provide a minimum 3 foot clearance from the 
exhaust vent termination. See Fig.11 and 12 Letter I, page 15.
For the maximum length of the combustion air pipe, see Table 9.

Single pipe

Note:

 

This appliance requires 9950 cubic feet of available 

combustion air, or a minimum of 1243 square feet of space with an 
8 foot ceiling to operate.  If the large amount of air space, which 
equates to about half of most average sized homes, is not available, 
the appliance must pull air from the outside (see twin pipe above).

Although it is permissible to draw combustion air from inside the 
structure, it is not the manufacturer’s recommended installation 
method. Always install a 3 inch elbow on the top of the combustion air 
inlet adaptor to prevent foreign objects from falling into the unit.
If a single pipe installation is utilized, follow guidelines below for 
providing adequate combustion air for the water heater as well as any 
other appliances that may consume air in the space. Always follow local 
codes if they are more stringent.

This Installation Manual specifies the minimum vertical vent pipe and the 
amount of combustion air required for this unit. When all requirements 
are followed, the unit will operate properly and safely. However, there 
may still be a risk of freezing due to negative draft if the other 
combustion appliances in the building are not supplied with sufficient 
combustion air. A wood stove or furnace can pull its combustion air from 
the heater's vent pipe, allowing the cold incoming air to freeze the cold 
water in the heat exchanger. Supplying more combustion air for all 
combustion appliances is the solution. A HVAC specialist should be 
consulted to design solutions for providing more combustion air.
Observe the following guidelines:

Installations in structures that have been tightly constructed (air 
infiltration rate of 0.40 ACH or less) must be provided with combustion 
air per the National Fuel Gas Code. Consult a HVAC specialist if your air 
infiltration rate is questionable.

The space must have two permanent openings, one commencing within 
12 inches of the top and one commencing within 12 inches of the 
bottom of the enclosure.

Appliances located in unconfined spaces:

a) 

An unconfined space is one whose volume is greater than 50 

cubic feet (1.42 cubic meter) per 1000 BTU/hr (292.81 Watts) 
of the combined rating of all appliances installed in the space. 
That would be 9950 cubic feet (281.8 cubic meters) for the 
water heater alone.

b)

 In unconfined spaces in buildings of conventional frame, 

masonry, or metal construction, infiltration air is normally 
adequate to provide air for combustion.

Appliances located in confined spaces:

The confined space must be provided with two permanent openings, 
one commencing within 12 inches (304.8mm) of the top and one 
commencing within 12 inches (304.8mm) of the bottom of the 
enclosure. Each opening must have a minimum free area of one 
square inch per:
– 1000 BTU/hr (292.81 Watts) if all air is taken from inside the 

building

– 2000 BTU/hr (585.62 Watts) if all air is taken from the outside by 

horizontal ducts

– 4000 BTU/hr (1171.24 Watts)if all air is taken from the outside 

by direct openings or vertical ducts

Or the confined space must be provided with one permanent opening or 
duct that is within 12 inches (304.8mm) of the ceiling of the enclosure. 
This opening must have a minimum free area of one square inch per:

– 3000 BTU/hr (878.43 Watts) if all air is taken from the outside by 

a direct opening or vertical duct.

Louvers, grills and screens have a blocking effect, when used, increase 
the sizes of your openings by 300% for wood louvers (as wood type will 
reduce the free air by 75%) and 43% for metal louvers (as metal will 
reduce the free air by 30%). Refer to the National Fuel Gas Code for 
complete information. In buildings of tight construction all air should be 
taken from outside.

4.5

Proper location for installing your heater

Carefully select the location of the water heater. For your safety and for 
proper heater operation, you must provide combustion air to the heater 
and a proper exhaust vent system.
Follow the guidelines below:

1. 

Locate the heater where venting, gas and plumbing connections 

are feasible and convenient.

2. 

The hot water lines should be kept short and insulated to save 

energy. Centrally locating the water heater is recommended to keep 
hot water distribution times even throughout the structure.

CAUTION: 

▶ In areas where outside temperatures routinely come 

close to freezing, sealed combustion operation is 
required. Use a concentric termination or separate 
terminations for combustion and vent, which must 
be installed on the same wall or roof surface, 
however never facing the direction of prevailing 
winds. Failure to do so may result in heat exchanger 
freezing up and bursting. This failure is not covered 
under the manufacturer's warranty. 

CAUTION: 

▶ When installed in an environment where corrosive 

chemicals or dirty air (e.g. hair salons, car washes) 
are present the twin pipe system is required.

CAUTION: 

▶ Terminations must prevent rain and debris from 

entering the combustion air and exhaust vent piping.

WARNING: 

▶ Single pipe venting is forbidden in manufactured 

(mobile) home installations.

Summary of Contents for RTG 199 MEN

Page 1: ...d plumber or gas fitter Upon completion of the installation these instructions should be handed to the user of the appliance for future reference What to do if you smell gas Turn off the gas shut off...

Page 2: ...5 2 Position of the fuses in control unit 33 6 Operation instructions 34 6 1 Description LCD Display 34 6 2 For your safety read before operating your water heater 35 6 3 Power 35 6 4 Temperature sele...

Page 3: ...installer If you smell flue gas Switch off the appliance Open windows and doors Inform a trained and certified installer Insufficient ventilation may cause toxic flue gas to escape Risk of poisoning...

Page 4: ...r heater Select and install the automatic mixing valve in accordance with the valve manufacturer s recommendations and instructions Water exiting from drain valves can be extremely hot To avoid injuri...

Page 5: ...adjacent to the appliance or to lower floors of the structure When such locations cannotbeavoided itisrecommendedthatasuitable drainpan adequatelydrained beinstalledunderthe appliance The pan must no...

Page 6: ...ble water shall not be connected to any heating system or component s previously used with a nonpotable water heating appliance WARNING Installation in mobile homes Installationinmobilehomesshallconfo...

Page 7: ...ecifications Technical data Approved in US Canada Bradford White is constantly improving its products therefore specifications are subject to change without prior notice Technical characteristics Unit...

Page 8: ...e homes boats or any mobile installation Modular homes are acceptable for installation Use above 8000 ft A S L altitude see page 22 Outdoor installation without installation of Outdoor kit Application...

Page 9: ...s or any occupied rooms normally kept closed See chapter 4 4 page 24 4 Youmustcorrectlyventyourheater Seechapter4 3 page11 on VENTING 5 The appliance and its gas connection must be leak tested before...

Page 10: ...RTG 199 ME 6 720 811 615 2015 04 10 3 5 Dimensions and minimum installation clearances Fig 6 Dimensions 1 On Off button 2 Reset button 3 Program key 4 Power ON or stand by LED 5 LCD display 6 Up butt...

Page 11: ...llation practice is to first determine the venting combustion air point of termination then design the piping layout back to the heater NOTICE Do not reduce the exhaust or combustion air vent pipe siz...

Page 12: ...t piping see Fig 16 Fig 8 Concentric kit Fig 9 Concentric kit vent assembly Fig 10 Concentric kit installation LA 12 inches LB 3 inches stainless steel pipe NOTICE In areas where outside temperatures...

Page 13: ...ion air inlet terminations for twin pipe penetration is 3 feet Minimum combustion air and exhaust pipe length The minimum exhaust pipe length is 1 foot 0 3m of straight vent pipe The minimum combustio...

Page 14: ...n of example Max length 28 5 90 elbow reduction 10 sub total 18 5 45 elbow reduction 2 5 Total 16 Table 14 For this example the maximum allowable combustion air pipe length is 16 feet System used Twin...

Page 15: ...nventilated soffit F Clearance to outside corner G Clearance to inside corner H Clearance to each side of center line extended above meter regulator assembly 36 in within a height 15 feet above meter...

Page 16: ...entilated soffit F Clearance to outside corner G Clearance to inside corner H Clearance to each side of center line extended above meter regulator assembly 36 in within a height 15 feet above meter re...

Page 17: ...nger strap Fig 14 Horizontal venting installation combustion air piping not shown 1 Termination 2 Minimumabovegroundornormallyexpectedsnowaccumulation level 3 Appliance 4 Elbow note minimum 1ft of str...

Page 18: ...18 Fig 17 1 Appliance 2 Condensate drain 3 Elbow 4 Hose clamp 5 Firestop support 6 Firestop support 7 Rain cap 8 Storm collar 9 Flashing 10 4 minimum air space Fig 18 LA 3ft minimum WARNING Single pip...

Page 19: ...he flue gas exhaust accessory to the top of the unit fig 20 position 1 using the 4 screws and gasket provided and fully insert vent pipe into the accessory If using 4 venting a 3 to 4 increaser should...

Page 20: ...iting backdraft under the following conditions see fig 23 The vent hood is only to be used in the exhaust vent piping The vent hood can only be used for horizontal terminations The vent hood is able t...

Page 21: ...shown for clarity purposes 1 Good 2 Better 3 Best 4 Enclosed vent pipe Do not install damper 5 Unconditioned space Do not install damper 6 Preferred damper position for vertical terminations 4 3 7 Ve...

Page 22: ...wer fan speed P1 Maximum power fan speed P1 0 2000 ft 0 610 m 3 5 32 ft 7 No modification required No modification required For operation at elevations above 2 000 ft 610 m the equipment ratings shall...

Page 23: ...ide detector with alarm and battery back up may be installed on the next adjacent floor level b In the event that the requirements of this subdivision can not be met at the time ofcompletion of instal...

Page 24: ...infiltration rate of 0 40 ACH or less must be provided with combustion air per the National Fuel Gas Code Consult a HVAC specialist if your air infiltration rate is questionable The space must have tw...

Page 25: ...xcept for the times the burner is on In the event of power outage in conjunction with freezing temperatures it is recommended that the heater be drained See chapter 7 2 page 37 Winterizing for drainin...

Page 26: ...ater heater as shown in fig 32 Use the included screws to secure the brackets at the bottom of the water heater to the wall If the wall is sheathed with plaster or drywall it is recommended that a sup...

Page 27: ...l gas fittings Bubbles are asignofa leak A combustible gas detector may also be used to detect for leaks GAS LINE SIZING The gas supply piping for a single heater should be sized for a maximum drawof1...

Page 28: ...um pipe capacity in cubic feet of Natural Gas per hour for gas pressures of 14 W C 0 5psig or 25 mbar or less and a pressure drop of 0 5 W C 1 25mbar based on 0 60 specific gravity gas EHD EquivalentH...

Page 29: ...wanceisnecessaryforanordinarynumberof fittings 4 10 Water connections When facing the heater the cold connection is on the bottom right and the hot connection is on the bottom left Centrally locating...

Page 30: ...and the heater No reducing coupling or other restriction may be installed in the discharge line The discharge line must be a minimum of 4 above a drain and installed such that it allows complete drai...

Page 31: ...nklesswaterheaterinacombinationDHW and space heating application will result in the product warranty being reduced to 3 years Fig 38 Pressure drop curve CAUTION If the set point temperature is above 1...

Page 32: ...ve and connect manometer tube to test point Static Pressure Test Turn gas supply back on Record static gas pressure reading in table 33 Operating Pressure Test Press ON OFF button into ON Immediately...

Page 33: ...Theheater is wired as shown in thewiring diagram chapter 10 Fig 66 Fig 42 Connecting power supply cord 1 Power cord length 3ft Note The outlet the appliance is plugged into should be clear from possi...

Page 34: ...all parts in reverse order 6 Operation instructions Fig 45 1 On Off button 2 Reset button 3 Program Key 4 LCD display 5 Up button 6 Down button 7 Power On or stand by LED 6 1 Description LCD Display...

Page 35: ...e gas supply and call a qualified service technician Forceful repair may result in a fire or explosion C Do not use this appliance if any part has been under water Immediately call a qualified service...

Page 36: ...w to reset error first Record the error code on LCD and consult Problem solving chapter 9 1 page 44 Fig 57 After following instructions indicated in Troubleshooting section press reset button firmly i...

Page 37: ...warranty NOTE Use of agents such as anti freeze is not permitted and voids the warranty as they may cause damage to the water heater s internal components 1 Press ON OFF switch on the water heater to...

Page 38: ...ural Gas and 8 WC for Propane Do not proceed in adjusting CO2 until pressure is at or above these levels but not to exceed 10 5 WC for Natural Gas and 13 WC for Propane A Once Gas Pressure is adequate...

Page 39: ...sitive and should be made in small increments It may take several minutes for readings to stabilize 3 Verifyboth P1 and P2 CO2 readings are within the rangesspecified in table36 Repeat steps 1 and 2 a...

Page 40: ...er 4 14 page 32 note reducing P1 values below maximum will reduce maximum power of the appliance P2 Minimum Power 7 7 20 see chapter 4 3 8 page 22 P3 Remote Controls installed _0 _0 6 Not available P4...

Page 41: ...u chapter 7 6 Select the sub mode H0 Write the number that shows in the display Select the sub mode H1 Write the number that shows in the display Select the sub mode H2 Write the number that shows in...

Page 42: ...shower heads faucet aerators and whole house filters are clear of debris 4 Confirm the heater s gas type coincides with the type of gas being supplied See fig 2 page 8 for location of rating plate 5...

Page 43: ...ater pressure For installation on a private well system with the use of a pressuretank thelowestpressurerangesettingrecommendedis40 60 psi 2 75 4 15 bar Consult your installer or local plumber for eff...

Page 44: ...y damage due to freezing conditions is not covered under warranty 2 In areas where water has a high mineral content periodic descaling may necessary 3 Check wire connections at outlet temperature sens...

Page 45: ...ty 3 Check sensor ref page 48 chapter 11 Backflow temperature sensor over 309 F The appliance will close the burner and lock non volatile 1 Check inlet outlet vent pipes 2 Check if secondary fan conne...

Page 46: ...ee chapter 7 4 page 38 6 Check that the minimum power fan speed has been adjusted to the proper value See page 22 Internal hardware software failure 1 Disconnect power supply cord and check the two wi...

Page 47: ...Water flow sensor 8 Flue gas limiter 9 Heat exchanger overheat sensor ECO 10 Gas valve 11 Jumper resistance 12 Water valve 13 Primary fan 14 ON OFF switch 15 Secondary fan 16 AC plug 17 Main connecti...

Page 48: ...Sensor resistance charts RTG 199 ME 6 720 811 615 2015 04 48 11 Sensor resistance charts Fig 67 Outlet Inlet immersion sensor characteristics Fig 68...

Page 49: ...Functional scheme RTG 199 ME 6 720 811 615 2015 04 49 12 Functional scheme Fig 69 Functional scheme...

Page 50: ...me sensor 4 Primary fan Mixer 5 Outlet temperature sensor 6 LCD display 7 On Off button 8 Reset button 9 Program key 10 Flue gas limiter 11 Heat exchanger overheat sensor 12 Ignition electrodes 13 Obs...

Page 51: ...the product life Contact your city authorities for information about the disposal of recyclable products Saving water resources Make sure you close all the taps after any use Avoid leaving the taps d...

Page 52: ...hipping or delivery charges ii any removal installation or re installation charges iii any material and or permits required for installation re installation or repair iv charges to return the defectiv...

Page 53: ...ssociated with repair and or replacement 3 Replace and or repair any heater without complete model serial number 4 Replace any heater without prior receipt of actual rating plate from appliance and co...

Page 54: ...located on rating plate on right side panel ___ ___ ___ ___ ___ ___ ___ ___ Gas Pressure Reading 1 1 See Chapter 4 14 page 32 and gas pressure table to be filled out by installer Static Operating Wate...

Page 55: ...RTG 199 ME 6 720 811 615 2015 04 55 Notes...

Page 56: ......

Reviews: