background image

12 

 

Installation Instructions cont.- 

 

Condensate Drain Connection 

 

This unit has a condensate drain; therefore, a floor 
or other drain no higher than 36 in (91.4 cm) above 
the floor must be available. It must be in close 
proximity to the water heater to allow for the 
shortest possible drain line with minimal turns. The 
drain must meet state and local codes. It is 
important to 

install a ¾” FNPT fitting suitable for 

either rigid or flexible drain line to the primary drain 
port coming off the side of the unit. Diameter 
reductions from a ¾” drain line are discouraged. 

 

Ensure that the rigid or flexible drain line maintains a downward slope to allow for proper gravity drainage of 
condensate to the drain and to allow for proper function of the condensate drain blockage sensor. If no drain is 
available, then a common condensate pump with a capacity no less than 1 gallon/day (3.8 L/day) must be 
purchased and installed. It is important to route the flexible or rigid drain line so that the discharge water cannot 
contact live electrical parts or cause water damage. 

 

 
Catch Pan Installation

 

(if required) 

 

Auxiliary catch pan MUST conform to local codes. Catch 
pan kits are available from the distributor where the water 
heater was purchased or any water heater supplier. The 
catch pan should be at minimum 4 in (10.2 cm) larger than 
the water heater base diameter. To prevent corrosion and 
improve drain valve access it is recommended that the 
water heater be placed on risers inside the catch pan. 

 

 
Thermal Expansion 

 

Determine if a check valve exists in the inlet water line. It may have been installed in the cold water line as a 
separate backflow preventer, or it may be part of a pressure-reducing valve, water meter, or water softener. A 
check valve located in the cold water inlet line can cause what is referred to as a “closed” water system. A cold 
water inlet lin

e with no check valve or backflow prevention device is referred to as an “open” water system. As 

water is heated, it expands in volume and creates an increase in the pressure within the water system. This 
action is referred to as thermal expansion.” 
 
In 

an “open” water system, expanding water which exceeds the capacity of the water heater flows back into the 

city main where the pressure is easily dissipated. 

A “closed” water system prevents the expanding water from 

flowing back into the main supply line, and the result of thermal expansion can create a rapid and dangerous 
pressure increase in the water heater and system piping. This rapid pressure increase can quickly reach the 
safety setting of the relief valve, causing it to operate during each heating cycle. 
 
Thermal expansion, and the resulting rapid and repeated expansion and contraction of components in the 
water heater and piping system, can cause premature failure of the relief valve, and possibly the heater itself. 
Replacing the relief valve will NOT

 

correct the problem. 

 
The suggested method of controlling thermal expansion is to install an expansion tank in the cold water line 
between the water heater and the check valve. The expansion tank is designed with an air cushion built in that 
compresses as the system pressure increases, thereby relieving the over-pressure condition and eliminating 
the repeated operation of the relief valve. Other methods of controlling thermal expansion are also available. 
Contact a qualified service provider for additional information regarding this subject. 
 

 
 

 

 

                                                             

 

 

 

 

 

 

 

 

 

 

 

 

(Typical Installations) 

Flexible or 

rigid ¾” drain line and 

associated ¾” FNPT fitting 

 

 

¾” MNPT  
Condensate  
Drain Port 

¾” MNPT  
Condensate  
Drain Port 

Summary of Contents for RE2H50S 1NCWT Series

Page 1: ...1NCWT RE2H80T 1NCWT For your family s comfort safety and convenience we recommend this water heater be installed and serviced by a plumbing professional ECO 8384 1 Effective Sept 2020 238 52169 00A 9...

Page 2: ...on and instruction manual will explain in detail the installation and maintenance of your new Heat Pump Water Heater We strongly recommend that you contact a plumbing professional for the installation...

Page 3: ...hot water faucet due to a reaction between the sacrificial anode and impurities in the water If this should happen an alternative anode s may be purchased from the supplier that installed this water...

Page 4: ...e tank of hot water to last about 25 longer as less hot water is mixed in at the shower or faucet Increasing the water temperature setpoint may improve the cleaning performance of dishwashers and wash...

Page 5: ...mption is based on operating the unit in Hybrid Mode at required Department of Energy DOE test conditions Operating at lower temperature settings or in Heat Pump Only Mode will provide even greater en...

Page 6: ...d Mode at required Department of Energy DOE test conditions Operating in Heat Pump Only Mode may provide greater savings in energy and operating costs than the claimed savings Electric Only Mode Elect...

Page 7: ...n and hot water capacity are factors to be considered when selecting the water temperature setting of the water heater Water temperatures above 125 F can cause severe burns or death from scalding Be s...

Page 8: ...stallation Instructions Local Installation Regulations This water heater must be installed in accordance with these instructions local codes and utility company requirements or in the absence of local...

Page 9: ...re and pressure relief valve will not result in damage to the area adjacent to the water heater or to lower floors of the structure When such locations cannot be avoided a suitable drain pan must be i...

Page 10: ...r in the event service is needed A minimum 8 20 3 cm clearance above the water heater to remove the filter for cleaning and for service access and clear access to the front of the water heater is reco...

Page 11: ...met will lead to higher power consumption increased use of resistance heating elements and or heat pump efficiency reduction Corner Installation Model RE2H50S Model RE2H65T RE2H80T Alcove Installatio...

Page 12: ...sure reducing valve water meter or water softener A check valve located in the cold water inlet line can cause what is referred to as a closed water system A cold water inlet line with no check valve...

Page 13: ...r flows through the faucets close them and check all water connections for possible leaks NEVER OPERATE THE WATER HEATER WITHOUT FIRST BEING CERTAIN IT IS FILLED WITH WATER CAUTION For protection agai...

Page 14: ...oduced in a hot water system served by this water heater when there has been no usage for a long period of time generally two weeks or more HYDROGEN GAS IS EXTREMELY FLAMMABLE To reduce the risk of in...

Page 15: ...1 watt 3 412 BTUH Connect the outlet of the relief valve to a suitable open drain so that the discharge water cannot contact live electrical parts or persons and to eliminate potential water damage Pi...

Page 16: ...er is filled Close the faucets and check for water leaks at the water heater drain valve combination temperature pressure relief valve and the hot and cold water connections F11 Fault Code During Inst...

Page 17: ...round connection is essential The presence of water in the piping and water heater does NOT provide sufficient conduction for a ground Nonmetallic piping dielectric unions flexible connectors etc can...

Page 18: ...unit and at least 7 in 17 5 cm clearance around the sides of the unit 6 in 15 2 cm clearance for earthquake strap installations with additional clearance on the opposite side of the unit Front of unit...

Page 19: ...rom the system 4 When a steady stream of water flows from the faucets the water heater is filled Close the faucets and check for water leaks at the water heater drain valve combination temperature pre...

Page 20: ...hot water heater discharges periodically this may be due to thermal expansion in a closed water system Contact the water supplier or your plumbing contractor on how to correct this Do not plug the re...

Page 21: ...4 until the water runs clear 6 Close the drain valve and fill the tank BEFORE returning power to the unit The tank is full when water runs out of a nearby open hot water faucet Cleaning the Filter In...

Page 22: ...ater to run The water heater will continue to produce hot water using the backup resistance heating elements until the condensate drain has been cleared and is able to drain properly Once the drain ha...

Page 23: ...soft set sealant thread into the port using the torque wrench tighten to 50 5ft lbs of torque 7 Turn water supply ON open a tap to remove any air in the plumbing system inspect for leaks then reassem...

Page 24: ...Phone Days ________________________________ Nights ______________________________ Address __________________________________________________________________ Supplier _________________________________...

Page 25: ...t energy efficient models Heat Pump Only and Hybrid the method used to heat the water used a fan that can be heard while running Q The heat pump is not running its normal length of time What causes th...

Page 26: ...operating range is 35 F T5 ambient 120 F If ambient temperature as viewed by T5 sensor is outside of this range the water heater will switch to Electric Standard Mode for that heating cycle only NO fa...

Page 27: ...utton becomes free the fault code will clear by itself Dirty Filter F14 5 Filter LED is on and audible alarm is sounding Filter is too dirty to enable proper function of water heater Number of Dirty F...

Page 28: ...28 Notes...

Reviews: