Copper Brute II
Page 15
Figure 4. Water Heater Piping — One Heater, One Tank.
NOTES:
6. CAUTION: PUMP SIZING MUST BE BASED UPON WATER HARDNESS AT
JOB SITE
1. OPTIONAL CWMU & RECIRC. LINE LOCATION.
2. LOCATE PENNANT DHW SENSOR OR REMOTE AQUASTAT
WELL IN LOWER 1/3 OF TANK.
3. BACK FLOW PREVENTER MAY BE REQUIRED. CHECK LOCAL CODES.
4. THERMAL EXPANSION TANK MAY BE REQUIRED. CHECK LOCAL CODES.
5. WHEN USING FACTORY MOUNTED PUMP, MAX PIPE LENGTH IS
30 FEET TOTAL, SIX 90° ELBOWS , FULL PIPE SIZE.
SUPPL
Y
RECIRC.
CWMU
1
CAUTION: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND VALVING, CHECK
WITH LOCAL CODES AND ORDINANCES FOR
ADDITIONAL REQUIREMENTS.
LEGEND
CHECK VALVE
THERMOMETER
TEMPERATURE
SENSOR
GLOBE VALVE
EXPANSION TANK
3-WAY VALVE
VALVE
PRESSURE REDUCING
VALVE
PUMP
PRV
TPRV
WATER CATEGORY
GRAIN HARDNESS PER GALLON
PPM / 17.1 = Grains Per Gallon
KEY:
S = SOFT
N = NORMAL
H = HARD
1 THROUGH 7.5
7.6 THROUGH 17
OVER 17
LOCATION OF
FACTORY-MOUNTED
PUMP
2
5
3
4
7. MINIMUM INLET WATER TEMPERATURE IS 120°F.
Table 8. Water Flow Requirements
Model
(Size)
gpm
ft
temp rise °F
lpm
m
temp rise °C
S
N
H
S
N
H
S
N
H
S
N
H
S
N
H
S
N
H
500
45
68
90
1.8
2.3
3.5
19
13
9
170
257
341
0.5
0.7
1.1
10
7
5
750
45
68
90
2.1
3.0
6.0
28
19
14
170
257
341
0.6
0.9
1.8
16
10
8
1000
45
68
90
2.3
3.6
6.1
38
25
19
170
257
341
0.6
1.1
1.9
21
14
10
1250
68
68
90
3.8
3.8
6.3
31
31
24
257
257
341
1.2
1.2
1.9
17
17
13
1500
68
68
90
3.9
3.9
6.5
38
38
28
257
257
341
1.2
1.2
2.0
21
21
16
1750
68
68
90
4.0
4.0
6.7
44
44
33
257
257
341
1.2
1.2
2.0
24
24
18
2000
112
112
112
10.0
10.0
10.0
30
30
30
424
424
424
3.0
3.0
3.0
17
17
17
Notes:
1. S = soft water (1 to 7.5 grains hardness)
2. N = normal water (7.6 to 17 grains hardness)
3. H = hard water (more than 17 grains hardness)
4. gpm = gallons per minutes, lpm = liters per minute, ft = head loss in feet, m = head loss in meters
5. Head loss is for heater’s heat exchanger only